Page 2 - Who Should Use this Installation Manual; This manual for the; should be used to assist individuals who will:; Prerequisites; A working knowledge of; Important information; Product; appropriate ATS manual; Tip; Connectivity Module; Users; DANGER; Encryption disabled mode; assigned must be the same for both devices.; Encryption enabled mode
ii Welcome Connectivity Module Windows and Internet Explorer are registered trademarks of Microsoft Corporation. Who Should Use this Installation Manual This manual for the Connectivity Module should be used to assist individuals who will: • install the Connectivity Module (mount and wire) • configu...
Page 3 - Overview; The; brings together several; Specifications; Termination Resistor, upper two actuators; DIP Switch on bottom of unit
Connectivity Module Overview, Specifications, Installation Overview, DIP Switch iii Modbus is a registered trademark of Gould Inc. Overview The Connectivity Module brings together several different serial devices that communicate at different baud rates and with different protocols to a common Ether...
Page 9 - Status LEDs; LED; POWER
Connectivity Module Status LEDs ix Status LEDs LED LED Description LED Function / Mode of Operation POWER Power indication status. GREEN/AMBER Solid GREEN – functioning as a Connectivity Module (Acc. 72E). Solid AMBER – functioning as a Serial Module (Acc. 72A). RX Data receiving status. GREEN Blink...
Page 10 - Connectivity Module Kit; for; Connectivity Module will mount on the right side.; Install the Connectivity Module onto DIN rail.
1-1 Installation Connectivity Module How to Install the Connectivity Module on 7000 & 4000 Series and Series 300 ATSs The Connectivity Module (CM) mounts on a DIN rail under the ATS Controller (Group 5 & 1). A short serial cable connects the CM to the Controller. If a Power Manager (PM) or D...
Page 11 - for a stand-alone Power Manager or Digital; blank; Appendix
Connectivity Module Installation 1-2 How to Install the Connectivity Module for a stand-alone Power Manager or Digital Power Meter The Connectivity Module (CM) mounts on a DIN rail near the Power Manager (PM) or Digital Power Meter (DPM). A long serial cable connects the Connectivity Module to the P...
Page 12 - Start; You can add the address to your
1-3 Installation Connectivity Module How to View & Change Configuration Pages from a Connectivity Module To view and change configuration pages on a client computer, follow these steps: 1. Be sure that your computer is connected to the Internet. 2. Start Microsoft Internet Explorer browser on co...
Page 13 - Device Configurator Screen for; Device Configurator Screen; Connectivity Module (server) Configuration; Update Server; Update Server
Connectivity Module 7000 & 4000 Series ATSs 2-1 Device Configurator Screen for 7000 & 4000 Series ATSs The Device Configurator Screen for 7000 & 4000 Series ATSs shows the Group 5 controller configuration settings (right side) and Connectivity Module (server) configuration settings (left...
Page 14 - Config PM; Power Manager or Power Meter Configuration; Input Name & Output Names; NOTE
2-2 7000 & 4000 Series ATSs Connectivity Module Device Configurator Screen for 7000 & 4000 Series ATSs with a PM or DPM If a Power Manager (PM) or Digital Power Meter (DPM) is used with a 7000 & 4000 Series ATS, a button appears on the lower left corner of the Connectivity Module Device ...
Page 15 - Configurator Screen Input and Output Names for a
Connectivity Module 7000 & 4000 Series ATSs 2-3 Configurator Screen Input and Output Names for a 7ATB with Power Manager For 7ATB only (7000 Series Automatic Transfer & Bypass-Isolation Switch), the Power Manager selection (Accessory 85 suffix letter designation) must be specified. The selec...
Page 16 - Detail Screen
2-4 7000 & 4000 Series ATSs Connectivity Module Detail Screen for 7000 & 4000 Series ATSs The Detail Screen for 7000 & 4000 Series ATSs shows the switch location, ratings, timer settings, actual timer values, pickup and dropout settings, event logging, and other status indications. Detai...
Page 18 - Connectity Module
3-2 Series 300 ATSs Connectity Module Device Configurator Screen for Series 300 ATSs with a PM or DPM If a Power Manager (PM) or a Digital Power Meter (DPM) is used with a Series 300 ATS, a button appears on the lower left corner of the Connectivity Module Device Configurator screen. Press the Confi...
Page 22 - Detail Screen for
4-2 ASCO 940/962 ATSs Connectivity Module Detail Screen for ASCO 940/962 ATSs The Detail Screen for ASCO 940/962 ATSs shows the switch location, ratings, timer settings, actual timer values, pickup and dropout settings, and other status indications. Detail Screen for ASCO 940/962 ATSs with a Power M...
Page 23 - Power Manager
Connectivity Module Stand-Alone Power Managers & Digital Power Meters 5-1 Device Configurator Screen for Power Manager or Digital Power Meter If a stand-alone Power Manager (PM) or Digital Power Meter (DPM) is used, a button appears on the lower left corner of the Connectivity Module Device Conf...
Page 24 - connected to a Load; Digital Power Meters; connected to a Load
5-2 Stand-Alone Power Managers & Digital Power Meters Connectivity Module Detail Screen for Power Managers connected to a Load The Detail Screen for Power Managers shows energy levels, power measurements, settings, discrete I/O status, and other status information. Detail Screen for Digital Powe...
Page 25 - connected to a Generator
Connectivity Module Stand-Alone Power Managers & Digital Power Meters 5-3 Detail Screen for Power Managers connected to a Generator The Detail Screen for Power Managers shows energy levels, power measurements, settings, discrete I/O status, and other status information. Detail Screen for Digital...
Page 26 - connected to a Circuit Breaker
5-4 Stand-Alone Power Managers & Digital Power Meters Connectivity Module Detail Screen for Power Managers connected to a Circuit Breaker The Detail Screen for Power Managers shows energy levels, power measurements, settings, discrete I/O status, and other status information. Detail Screen for D...
Page 27 - How to Create an Ethernet TCP/IP Network Connection in; Windows XP; deselected
Connectivity Module Ethernet TCP/IP Network Connections in Windows XP & 7 A-1 How to Create an Ethernet TCP/IP Network Connection in Windows XP & 7 1. Start Windows , then click the Start button. Select Control Panel . 2. Select Network Connections ( Windows XP ) or Network and Internet and/...
Page 29 - Troubleshooting the Connectivity Module; Problem Cause Solution
Connectivity Module Troubleshooting A-3 Troubleshooting the Connectivity Module Listed below are possible problems, their causes, possible solutions Problem Cause Solution DIAG red light blinks rapidly then stays on when the CM is first powered up. Duplicate IP address. The IP address of one or more...
Page 30 - Party; How to create a; Favorites; folder for ASCO
A-4 Create Favorites folder, 3 rd Party Modbus Configuration Connectivity Module How to create a Favorites folder for ASCO device pages and copy it to another computer To create a favorites folder and copy it to another user’s computer, the administrator should follow these steps: 1. Open the first ...
Page 31 - provides SNMP configuration.; SNMP TRAP messages; SNMP Configuration Screen; button on CM; RESET; button
Connectivity Module SNMP Internet-standard Protocol A-5 How to set SNMP (Simple Network Management Protocol) Configuration Firmware 869764-003 and higher provides SNMP configuration. 1. On the Device Configuration screen (page 2-1 or 3-1) click the SNMP button at the bottom. 2. On the SNMP Configura...
Page 32 - Recommended ASCO SNMP MIB file; Problem Cause Solution; SNMP is not enabled.
A-6 SNMP Internet-standard Protocol Connectivity Module Recommended ASCO SNMP MIB file A file containing 934904-xxx.mib can be downloaded from the location shown below. http://www.emersonnetworkpower.com/ en-US/Products/PowerSwitchingandControls/MonitoringandControl/Pages/ ASCO5150ConnectivityModule...
Page 33 - Communication Address Form for Connectivity Module (CM); Fill in the inform
Communication Address Form for Connectivity Module (CM) Row No. IP Address Subnet mask Gateway ATS Serial No. ATS Catalog No. Address set in ATS Controller* Address set in PM or DPM** Instructions: Fill in the inform ation for each Connectivity Module (CM) with an ATS, Power Manager (PM), and/ or Di...
Page 36 - INDEX; NOTICE
Printed in U.S.A. © ASCO Power Technologies, L.P. 2012 All Rights Reserved. INDEX A Access, NOTICE , ii AES encryption, iii, 2-1, 3-1, 4-1 Annunciators, ATS Remote, ii ASCOSNMP.MIB, A-5 ATS information needed, ii, communication address form ATS Remote Annunciators, ii C Cable, communication, iii CH1...