1 I MPORTANT S AFETY I NSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and opera- tion of the MP2-220N POD™. This product is designed for commercial / industrial use only, with Liebert UPS systems. It is not intended for use...
Page 7 - Introduction and System Description; NTRODUCTION; System Description; The 3U POD has two modes of operation:
Introduction and System Description 3 1.0 I NTRODUCTION AND S YSTEM D ESCRIPTION Congratulations on your choice of the Liebert MP2-220N POD™ (3U POD). The 3U POD provides maintenance bypass capability as well as power output distribution. The 3U POD can be used on UPSs in the rack mount or tower con...
Page 8 - Rack Mount Installation; ACK; utilizing the rack mount brackets provided.; Figure 4; The 3U POD may be
Rack Mount Installation 4 2.0 R ACK M OUNT I NSTALLATION 1. Rack mount installation of the 3U POD is possible with the use of the rack mounting brackets (shipped with the 3U POD). See Figure 4 . 2. The rack mounting brackets allow you to rack mount the 3U POD in a 19" enclosure (23" to 19...
Page 9 - Installation and Electrical Connections; NSTALLATION; Power Connection Options; Installation; Cord-Receptacle Installation and Start-Up; Table 1; Type of installation; NOTE; for UPS operation and installation instructions.
Installation and Electrical Connections 5 3.0 I NSTALLATION AND E LECTRICAL C ONNECTIONS Unpack the 3U POD carefully, noting the packing method. Retain the box and packing material for possible future shipments.Visually inspect the 3U POD for freight damage. Report damage to the carrier and your loc...
Page 10 - Alternate Hardwire Installation; LTERNATE; Electrical Installation Considerations; the operator. Please refer to; for breaker specifications.; Conduit Entry and Wiring Access Doors; Electrical Connections; Table 2; shows the standard; WARNING; and disconnect all cords to and from the UPS.
Alternate Hardwire Installation 6 4.0 A LTERNATE H ARDWIRE I NSTALLATION 4.1 Electrical Installation Considerations The utility input supply cable must be connected to the unit via a wall-mounted circuit breaker. The UPS output port must also be protected with a circuit breaker connected to the load...
Page 11 - Conversion From Cord-Receptacle to Hardwire; DO NOT LOOSEN THE UPPER TERMINAL BLOCK; the unit, using the eight screws removed in
Alternate Hardwire Installation 7 4.3 Conversion From Cord-Receptacle to Hardwire Two wiring access panels on the front of the 3U POD allow access to the wiring compartments. Each access door is retained using four Phillips head screws. 1. Remove the eight Phillips head screws from the wiring access...
Page 12 - Indicator Lamps; NDICATOR; UTILITY Indicator Lamp; This amber lamp is illuminated when utility power is present (see; UPS Indicator Lamp; Figure 5
Indicator Lamps 8 5.0 I NDICATOR L AMPS 5.1 UTILITY Indicator Lamp This amber lamp is illuminated when utility power is present (see Figure 5 ). It signals that you may transfer the loads to maintenance bypass (UTILITY mode) operation via the rotary switch. During a utility power outage, this lamp w...
Page 13 - Operation; PERATION; Transfer to Maintenance Bypass; Troubleshooting; Transfer to UPS; switch from UTILITY to UPS. If the lamp does not illuminate, refer to
Operation 9 6.0 O PERATION 6.1 Transfer to Maintenance Bypass To transfer to maintenance bypass (utility) from UPS, use the following steps:1. Ensure the UTILITY lamp (amber) is illuminated. If the lamp is not illuminated, refer to 7.0 - Troubleshooting . 2. Transfer the rotary switch from UPS to UT...
Page 14 - ROUBLESHOOTING; Problem
Troubleshooting 10 7.0 T ROUBLESHOOTING Problem Cause Solution UTILITY lamp(amber) notIlluminated. Utility not present. Call qualified service personnel to restore power. Utility Branch Circuit Breaker may be open. Verify that the branch circuit breaker is closed. 3U POD input power not connected to...
Page 15 - Specifications; PECIFICATIONS; Product Warranty Registration; Quick Links; See Model Label on 3U POD
Specifications 11 8.0 S PECIFICATIONS This 3U POD is intended for use with a UPS meeting all the following requirements: • UPS input cord is compatible with the rating and type of receptacle on the 3U POD labeled “CON- NECT UPS LINE CORD HERE.” • UPS output receptacle is compatible with the 3U POD i...
Page 18 - Via Leonardo Da Vinci 8; OWER
The Company Behind the Products With over a million installations around the globe,Liebert is the world leader in computer protectionsystems. Since its founding in 1965, Liebert hasdeveloped a complete range of support andprotection systems for sensitive electronics: • Environmental systems—close-co...