Page 3 - ATEX Installation Instructions and Drawings; For installing the following Micro Motion transmitters:; EC Type Examination Cer tificate; ATEX Installation Instructions
1 Model 3350/3700 Transmitters ATEX Installation Instructions and Drawings • For installing the following Micro Motion transmitters: - Model 3350/3700 with 4-wire connection to a core processor - Model 3350/3700 with 9-wire connection to a junction box - Model 3350/3700 with a remote core processor ...
Page 4 - Subject and type
Model 3350/3700 Transmitters 2 ATEX Installation Instructions 1) Subject and type Transmitter type 3**0******Z**** Instead of the *** letters and numerals will be inserted which characterize the following modifications: Letter for language 3 * * 0 A * * * * * * * * Number 3, 4, 5, or 6 for sensor in...
Page 5 - Description
Model 3350/3700 Transmitters ATEX Installation Instructions 3 2) Description The transmitter is, in combination with a sensor, used for mass flow measurement and for indicating as well as entering of parameters.The electrical components of the transmitters are mounted in a light metal housing which ...
Page 6 - Ri
Model 3350/3700 Transmitters 4 ATEX Installation Instructions 3.3) Intrinsically safe sensor circuits for 3**0A***3*Z**** For drive circuit terminals, the maximum external inductance L (sensor coil) can be calcualted with the following term: Where:E = 40 μ J for group IIC and E = 160 μ J for group I...
Page 7 - Marking
Model 3350/3700 Transmitters ATEX Installation Instructions 5 3.5) For type 3**0A***5*Z**** and 3**0A***6*Z**** (terminals J19-13/14 and J19-15/16) 4-wire board 3.6) Circuits to the display (terminals J19-1 bis J19-4) 3.7) Ambient temperature range Ta –30 (–20) °C to +60 °C 4) Marking –20 °C ≤ Ta ≤ ...
Page 8 - Figure 1: Model 3700 transmitter to remote core processor; MODEL
Model 3350/3700 Transmitters 6 ATEX Installation Instructions Model 3350/3700 installation drawings Figure 1: Model 3700 transmitter to remote core processor COMBINE THIS DRAWING WITH ONE OF FIGURE 2, 3, 4, OR 5 Reference no. EB-20003017 Rev. AA Hazardous AreaEx de [ib] IIB / IIC 4-wire IS cable 370...
Page 9 - Figure 2: Sensor with enhanced core processor; Sensor mounted
Model 3350/3700 Transmitters ATEX Installation Instructions 7 Figure 2: Sensor with enhanced core processor Figure 3: CMF, D (except D600), DL, F, H, R, CNG and T sensors with core processor COMBINE THIS DRAWING WITH FIGURE 1 I.S. cable See note 5. Hazardous Area Ex ib IIC / IIB Refer to sensor tag ...
Page 10 - Figure 4: D600 with core processor
Model 3350/3700 Transmitters 8 ATEX Installation Instructions Figure 4: D600 with core processor Figure 5: Remote core processor with remote transmitter Hazardous AreaEx de [ib] IIB T4 Refer to sensor and booster amplifier tags for complete hazardous area classification. Core processor mounted on se...
Page 11 - Figure 6: Model 3700 transmitter to remote junction box; Sensor junction
Model 3350/3700 Transmitters ATEX Installation Instructions 9 Figure 6: Model 3700 transmitter to remote junction box Figure 7: CMF, D (except D600), DL, F, H, and T sensor with junction box COMBINE THIS DRAWING WITH ONE OF FIGURE 7, 8, OR 9 Reference no. EB-20001045 Rev. EA Conditions for safe use:...
Page 12 - Figure 8: D600 with junction box
Model 3350/3700 Transmitters 10 ATEX Installation Instructions Figure 8: D600 with junction box Figure 9: DT with junction box Reference no. EB-20000272 Rev. BA Hazardous Area Exde [ib] IIB Installation method Fitting required Per EN60079–14 Conduit Ex d IIB conduit seal Cable Ex d IIB cable gland C...
Page 14 - Micro Motion Inc. USA; Worldwide Headquarters; Micro Motion Europe
Micro Motion Inc. USA Worldwide Headquarters 7070 Winchester CircleBoulder, Colorado 80301T +1 303-527-5200+1 800-522-6277 F +1 303-530-8459 Micro Motion Europe Emerson Process ManagementNeonstraat 16718 WX EdeThe NetherlandsT +31 (0) 318 495 555 F +31 (0) 318 495 556 Micro Motion Japan Emerson Proc...