Page 3 - Maintenance; actuator cannot suddenly open or close the valve.; loosening the packing box pipe plug.; WARNING; Installation; other foreign material.
Instruction Manual D103361X012 24000SB Valve March 2011 3 WARNING Personal injury could result from packing leakage. Valve packing is tightened before shipment; however, the packing mightrequire some readjustment to meet specific service conditions. Maintenance WARNING Avoid personal injury and prop...
Page 4 - Air Piping; will damage the valve's seating surfaces.; Actuator Removal
Instruction Manual D103361X012 24000SB Valve March 2011 4 2. Install the valve so the controlled fluid will flow through the valve body in the direction indicated by the arrow cast on the valve body. 3. A three-valve bypass must be used to permit removal of the control valve from the line without sh...
Page 5 - thoroughly and examine for signs of wear or damage.; Note; Lapping the Valve Seat
Instruction Manual D103361X012 24000SB Valve March 2011 5 2. Loosen the drive nut (key 9) and then remove the plug and stem (keys 4 and 5) assembly by holding the actuator stem still while unthreading the plug and stem assembly counterclockwise. 3. Remove the stem locknuts (key 27), travel indicator...
Page 6 - Instruction Manual; Replacing Packing; CAUTION
Instruction Manual D103361X012 24000SB Valve March 2011 6 Lapping is the process of mating the valve plug to the seat ring, with an abrasive to produce a close fit. When valveseat leakage becomes excessive, lapping becomes necessary. The plug and seat ring seating surfaces should be free oflarge scr...
Page 7 - Parts Ordering; Use only genuine Fisher
Instruction Manual D103361X012 24000SB Valve March 2011 7 Parts Ordering When corresponding with your Emerson Process Management sales office about this equipment, always mention thevalve serial number. When ordering replacement parts, also specify the key number, part name, and desired materialusin...
Page 10 - Table 3. Plug and Seat Ring for Soft Seat
Instruction Manual D103361X012 24000SB Valve March 2011 10 Table 3. Plug and Seat Ring for Soft Seat KEYNO. DESCRIPTION PLUG TYPE PLUG NO. ORIFICE DIAMETERmm (Inch) C v K v VALVE SIZE DN 15 (NPS 1/2) DN 20 (NPS 3/4) DN 25 (NPS 1) 4* Plug & Stem Assy PTFE Seat (Equal %) 577 9.5 (0.375) 1.0 0.86 2...
Page 11 - Figure 6. Optional 151 Low Flow Trim Assembly
Instruction Manual D103361X012 24000SB Valve March 2011 11 Figure 6. Optional 151 Low Flow Trim Assembly E1270 Figure 7. Optional 177 Low Flow Trim Assembly E1271 Table 4. Plug and Seat Ring for Baumann 151 Trim KEYNO. DESCRIPTION PLUG TYPE PLUG NO. ORIFICE DIAMETER mm (Inch) C v K v VALVE SIZE DN 1...
Page 12 - Figure 8. Packing Kits; Special ENVIRO-SEAL Packing Note
Instruction Manual D103361X012 24000SB Valve March 2011 12 Figure 8. Packing Kits E1240 Spring-Loaded PTFE V-Ring Packing Kit P/N 24494T001 E1241 Molded Graphite (Flexible Graphite) Packing Kit P/N 24492T001 E1248 ENVIRO-SEAL Packing Kit P/N 24490T001 Table 7. Spring-Loaded PTFE V-Ring Packing Kit P...
Page 13 - Figure 9. Dimensional Drawings
Instruction Manual D103361X012 24000SB Valve March 2011 13 Figure 9. Dimensional Drawings NOTE: ACTUATOR REMOVAL REQUIRES 115 mm (4.5 INCHES) VERTICAL CLEARANCE. 216 ( 4 8.5) 279 ( 4 11.0) 333 ( 4 13.1) 141 (5.5) 127 (5.0) 276 (10.9) 60 (2.4) 271 (10.7) 229 (9.0) 94 (3.7) MAX 276 (10.9) E1347 229 (9...
Page 14 - Table 10. Valve Dimensions
Instruction Manual D103361X012 24000SB Valve March 2011 14 Table 10. Valve Dimensions VALVE SIZE A VALVE BODY B BONNET E DIAMETER NPT Flanged Buttweld CL150 CL300 CL600 CL900/1500 CL2500 Standard Extension DN NPS mm inch mm inch mm inch mm inch mm inch mm inch mm inch mm inch mm inch mm inch 15 1/2 ...