Page 3 - TABLE OF CONTENTS
i TABLE OF CONTENTS I MPORTANT S AFETY I NSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 G LOSSARY OF S YMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 1.0 I NTRODUC...
Page 4 - ii; OMMUNICATION; FIGURES
ii 6.0 C OMMUNICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 6.1 DB-9 Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 6.2 Remote Shutdown Via...
Page 5 - SAVE THESE INSTRUCTIONS; Size of Branch Circuit Overcurrent Protection; CAUTION; 0 amperes maximum branch circuit overcurrent protection.; user-serviceable parts inside except the internal battery pack.; WARNING; liquid or aerosol cleaners.; WARNING; injury to the skin and eyes.; Table 5
1 I MPORTANT S AFETY I NSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and mainte- nance of the UPS. • Intended for installation in a temperature-controlled, indoor area free of conductive contaminants. • Maximum ambient tem...
Page 6 - —The Liebert PSI XR complies with part 15 of the FCC; NOTICE
2 CONDITIONS OF USE —The input supply outlet must be within 6 ft. (1.8m) of the UPS and be eas- ily accessed.This UPS provides conditioned power to connected equipment. It is not intended for use with life-sup- port and other designated “critical” devices. Maximum load must not exceed that shown on ...
Page 8 - Introduction; NTRODUCTION; The Liebert PSI; Figure 1
Introduction 4 1.0 I NTRODUCTION The Liebert PSI ™ XR is a 2U, line-interactive UPS that may be installed in a rack or used as a tower UPS.Status indicators on the front of the Liebert PSI XR display load level, battery level, buck/boost, site- wiring fault, overload, battery status and UPS operatio...
Page 9 - Figure 3
Introduction 5 Figure 3 2200—rear view Figure 4 3000—rear view DC 48V OUTPUT EPO INPUT VOLTAGE=110V VOLTAGE=120V VOLTAGE=127V 2 1 FUNCTION Network Surge Protection USB Port DB-9 Port (Contact Closure) Power Cord; 5-20P (not shown for clarity) EPO External Battery Cabinet Connector Voltage Configurat...
Page 10 - What’s Included; HAT; The Liebert PSI XR is shipped with the following items:; Figure 5
What’s Included 6 2.0 W HAT ’ S I NCLUDED The Liebert PSI XR is shipped with the following items: • Multi-Language User Manual on CD • Liebert MultiLink Software and User Manual, downloadable at multilink.liebert.com • Contact Closure (ML9P9S) Cable• USB Cable • Tower Stands• Mounting Hardware• Rack...
Page 11 - Installation; NSTALLATION; Preparation; Figure 6; The UPS and battery cabinets are heavy (see; Table 6; and; Table 7; when lifting or moving either the UPS or battery cabinets.; mm; AIR
Installation 7 3.0 I NSTALLATION 3.1 Preparation The Liebert PSI XR may be installed in either a tower or rack configuration. Determine the method that suits the application and proceed.Decide where to install the Liebert PSI XR. The UPS must be installed indoors in a controlled envi- ronment. Place...
Page 12 - Tower UPS Installation; See; when using the Liebert PSI XR in a tower configuration.; Figure 7
Installation 8 3.2 Tower UPS Installation See Figure 7 when using the Liebert PSI XR in a tower configuration. Figure 7 Tower configuration—attach Tower Stands Step 1 Step 2
Page 13 - Rack-Mount UPS Conversion and Installation; Figure 8; used to move the UPS into and out of the rack.
Installation 9 3.3 Rack-Mount UPS Conversion and Installation See Figure 8 when installing the Liebert PSI XR in a rack. External battery cabinets are installed in same manner. Figure 8 Convert the Liebert PSI XR for rack installation NOTICE When rack-mounted, the UPS must be supported by a shelf, s...
Page 14 - Orient Display for Installation; correctly, then press it into the UPS until it is seated.; Figure 9; Charge Batteries and Perform Battery Startup; Figure 10 Connect input power and load
Installation 10 3.4 Orient Display for Installation The Liebert PSI XR features a rotating display that may be oriented for either tower or rack installations.To set the display for your installation, pull out on the display and rotate it until it is oriented correctly, then press it into the UPS un...
Page 15 - Connect Network Surge protection; Figure 11 Connect network surge protection; Connect Communication Interface; can be monitored with any of these communication methods:; Figure 12 Connect communication interface
Installation 11 3.7 Connect Network Surge protection Connect a 10 base-T/100 network cable to the network surge protection IN jack on the rear of the UPS. Connect from the OUT jack with network cabling to network equipment (see Figure 11 ). Figure 11 Connect network surge protection 3.8 Connect Comm...
Page 16 - Set Up Liebert MultiLink software; • Install the software.; Figure 13 EPO connection for normally open operation; Short Pin 1 and Pin 2 to
Installation 12 3.9 Set Up Liebert MultiLink software To start using Liebert MultiLink (software and user manual available at multilink.liebert.com ): • Install the software. See the Liebert MultiLink quick-start guide or user manual for installation instructions. • Connect one end of the USB cable ...
Page 17 - External Battery Cabinet Installation; or; Mount UPS Conversion and Installation; rear of the UPS (see; connector on the UPS.; Table 1
Installation 13 3.11 External Battery Cabinet Installation Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery run time. External battery cabinets are designed to be placed all on one side of the UPS or stacked beneath the UPS. The batteries have a ma...
Page 18 - Figure 15 Connect battery cabinets to UPS; Table 8; for approximate battery run times.
Installation 14 Figure 15 Connect battery cabinets to UPS See Table 8 for approximate battery run times. DC 24V OUTPUT INPUT EPO VOLTAGE=110V VOLTAGE=120V VOLTAGE=127V 2 1 FUNCTION
Page 19 - Controls and Indicators; ONTROLS; Refer to; Table 2; Item
Controls and Indicators 15 4.0 C ONTROLS AND I NDICATORS Buttons on the front panel display control the Liebert PSI XR. Eight LEDs indicate the UPS’s status. Refer to Figure 16 and Table 2 . Figure 16 Display and status indicators Table 2 Display and status indicators function, legend Item Name Stat...
Page 20 - Control Buttons; 00% or greater — Red
Controls and Indicators 16 4.1 Control Buttons 4.1.1 On/Alarm Silence/Manual Self-Diagnostic Test This button controls output power to connected load(s). It has three functions: • On• Alarm Silence• Manual Self-Diagnostic Test ON —Start the UPS by pressing this button for more than 3 seconds, then r...
Page 21 - Normal Mode—; Status
Controls and Indicators 17 4.2.3 Battery Level Indicator The five LEDs illuminate with a steady glow to indicate battery capacity. Battery capacity is shown for five seconds after the Status Change button is pressed. The LEDs show the battery capacity as a range, ± 5% The LEDs’ battery level meaning...
Page 22 - Operational Modes; PERATIONAL; Normal Mode; shooting; Battery Mode; Battery Recharge Operation; recharging the batteries.
Operational Modes 18 5.0 O PERATIONAL M ODES 5.1 Normal Mode When the UPS is in Normal Mode, the Normal Mode Indicator illuminates green. 5.2 Buck/Boost Mode The Automatic Voltage Regulator (AVR) circuitry compensates for fluctuations in utility power, such as voltage surges and sags. When the Liebe...
Page 23 - Communication; computer to gracefully shut down the operating system.; Remote Shutdown Via the DB-9 Connector; after utility power returns.; Network Surge Protection Connectors; Table 4; Assignment Description; Common; Pin Assignment
Communication 19 6.0 C OMMUNICATION 6.1 DB-9 Connector The UPS has a DB-9 (9 pin female) connector on the rear to allow UPS status communications with a computer running Liebert MultiLink software in contact closure mode. The connection provides On Battery and Low Battery notification.When power is ...
Page 24 - UPS Communications; Figure 17 DIP switch settings for 120V system; Setting
Communication 20 6.4 UPS Communications The Liebert PSI XR is equipped with a Liebert IntelliSlot port to provide advanced communication and monitoring options.Liebert MultiLink software continually monitors the UPS and can shut down your computer or server via USB, contact closure and SNMP (via IS-...
Page 25 - Battery Maintenance; ATTERY; Battery Charging, Storage; representative or Channel Support Applications.; Figure 18 Battery replacement
Battery Maintenance 21 7.0 B ATTERY M AINTENANCE 7.1 Battery Charging, Storage The batteries are valve-regulated, nonspillable, lead acid and must be kept charged to retain their design life. The Liebert PSI XR continuously charges the batteries when connected to the utility sup- ply, even while the...
Page 26 - Specifications; PECIFICATIONS
Specifications 22 8.0 S PECIFICATIONS Table 6 Liebert PSI XR specifications Model Number PS1000RT3-120XR PS1000RT3120XRW PS1500RT3-120XR PS1500RT3120XRW PS2200RT3-120XR PS2200RT3120XRW PS3000RT3-120XR PS3000RT3120XRW Power Rating, VA/W 1000VA/900W 1500VA/1350W 1920VA/1920W * 3000VA/2700W Dimensions,...
Page 27 - Model Number
Specifications 23 Table 7 Battery cabinet specifications Model Number PSRT3-24VBXR PSRT3-48VBXR Used w/UPS Model PS1000RT3-120XR PS1000RT3120XRW PS1500RT3-120XR PS1500RT3120XRW PS2200RT3-120XR PS2200RT3120XRW PS3000RT3-120XR PS3000RT3120XRW Dimensions, W x D x H, in (mm) Unit 17.3 x 19.3 x 3.5 (440 ...
Page 30 - Troubleshooting; ROUBLESHOOTING; riences a problem. See; for suggested solutions.; Table 9; reduced, the condition will trip the branch circuit breaker.
Troubleshooting 26 9.0 T ROUBLESHOOTING The information below indicates various symptoms a user may encounter if the Liebert PSI XR expe- riences a problem. See Table 9 for suggested solutions. 1. An alarm sounds, alerting that the UPS requires attention. The alarm can be silenced except for low bat...
Page 32 - AC Power
EmersonNetworkPower.com Ensuring The High AvailabilityOf Mission-Critical Data And Applications. Emerson Network Power, the global leader in enabling business-criticalcontinuity, ensures network resiliency and adaptability througha family of technologies—including Liebert power and coolingtechnologi...