Emerson 185SE– User Manual in PDF format online.
Manuals:
User Manual Emerson 185SE
Summary
Rev. A 3 Service How will I know if the controller is non-operational? 1. The indicator lights are not showing proper indications. 2. The switch transfers even if there is no loss of utility power and no transfer test operation or exercise with transfer is confirmed. 3. The relays are not operating ...
Rev. A 4 Why won’t the generator shut down? 1. Generator is still running on cool-down state. Approximately 5 minutes. 2. If the ATS has transf erred to the utility source and the generator is still running after 5 minutes, check if generator has its own cool-down tim er/setting. Contact local gener...
Rev. A 5 Wiring Where do I connect the engine start wires? The generator starting contact connections are on the controller terminal block. Connect the generator start wires to terminal block TB7 (TB7-4 and TB7-5 f or norm ally open contacts, and TB7-5 and TB7-6 for normally closed contacts) Caution...