2 105192 UNVENTED PROPANE/LP GAS LOG HEATER FIREPLACE MANUFACTURERS INCORPORATED SAFETYINFORMATION DANGER: Carbon monoxide poisoning may lead to death! Carbon Monoxide Poisoning: Early signs of carbon monoxide poisoning re-semble the flu, with headaches, dizziness,or nausea. If you have these signs,...
Page 3 - OWNER’S MANUAL; LOCAL CODES; American National Standards Institute, Inc.; OPERATION; UNPACKING; Figure 1 - Heat MajicTM Log Set; Base Assembly; CAUTION: Do not remove the; Do not pick up
3 105192 OWNER’S MANUAL LOCAL CODES Install and use heater with care. Follow alllocal codes. In the absence of local codes, usethe latest edition of The National Fuel GasCode ANS Z223.1, also known as NFPA 54*. *Available from: American National Standards Institute, Inc. 1430 Broadway New York, NY 1...
Page 4 - Unusually Tight Construction; per
4 105192 UNVENTED PROPANE/LP GAS LOG HEATER FIREPLACE MANUFACTURERS INCORPORATED AIR FORCOMBUSTION ANDVENTILATION PROVIDING ADEQUATEVENTILATION The following are excerpts from NationalFuel Gas Code. NFPA 54/ANS Z223.1, Sec-tion 5.3, Air for Combustion and Ventilation. All spaces in homes fall into o...
Page 5 - DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION; Determining if You Have a Confined or Unconfined Space; Continued
5 105192 OWNER’S MANUAL DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION Determining if You Have a Confined or Unconfined Space Use this work sheet to determine if you have a confined or unconfined space. Space: Includes the room in which you will install heater plus any adjoining rooms with doorless ...
Page 6 - Figure 3 - Ventilation Air from Outdoors; Ventilation Air From Outdoors; Do not provide openings for; Figure 2 - Ventilation Air from Inside Building
6 105192 UNVENTED PROPANE/LP GAS LOG HEATER FIREPLACE MANUFACTURERS INCORPORATED AIR FORCOMBUSTION ANDVENTILATION Continued VENTILATION AIR Ventilation Air From InsideBuilding This fresh air would come from an adjoiningunconfined space. When ventilating to anadjoining unconfined space, you must pro-...
Page 7 - LOG SIZING REQUIREMENTS; B. Clearances from the top of the fireplace; INSTALLATION; CHECK GAS TYPE; *Measured at 14” depth
7 105192 OWNER’S MANUAL LOG SIZING REQUIREMENTS Log Minimum Firebox Size Height Depth Front Rear* Width Width 18" 17" 14" 24" 20" 24" 17" 14" 28" 21" 30" 17" 14" 34" 24" INSTALLATION ANDCLEARANCES (Vent-FreeOperation Only) Figure 4 - Minimu...
Page 8 - If using a mantel, proceed to If Using
8 105192 UNVENTED PROPANE/LP GAS LOG HEATER FIREPLACE MANUFACTURERS INCORPORATED INSTALLATION Continued Minimum NoncombustibleMaterial Clearances If Not Using Mantel Note: If using a mantel, proceed to If Using Mantel. If not using a mantel, follow theinformation below. You must have noncombustible ...
Page 9 - Figure 7 - Minimum Mantel Clearances When Using Hood; Figure 6 - Minimum Mantel Clearances Without Using Hood; MANTEL CLEARANCES; FLOOR CLEARANCES; A. If installing appliance on the floor level,; flue damper open
9 105192 OWNER’S MANUAL Figure 7 - Minimum Mantel Clearances When Using Hood Minimum Non-Combustible Material 8"Min. 12" 15" 18" All minimum distances arein inches 20" 2 1 /2 " 6" 8" 10" 12" Distances to Underside ofMantel Hood(HDABK, HDABR) Top of FireplaceOp...
Page 10 - You prefer vented operation; Figure 10 - Attaching Damper Clamp; Make sure the heater burner; Damper; Masonry Fireplace
10 105192 UNVENTED PROPANE/LP GAS LOG HEATER FIREPLACE MANUFACTURERS INCORPORATED INSTALLATION ContinuedINSTALLING DAMPERCLAMP ACCESSORY FORVENTED OPERATION Note: When used as a vented heater, appli- ance must be installed only in a solid-fuelburning fireplace with a working flue andconstructed of n...
Page 11 - Masonry Screw; Figure 12 - Attaching Base Assembly to Fireplace Floor; Figure 11 - Attaching Flexible Gas Hose to Heater Gas Regulator; Fitting; Installation Items Needed
11 105192 OWNER’S MANUAL Masonry Screw Figure 12 - Attaching Base Assembly to Fireplace Floor Bracket withScrew Holes INSTALLATION Continued Heater GasRegulator Flexible Gas Hose(if allowed by localcodes) Figure 11 - Attaching Flexible Gas Hose to Heater Gas Regulator Fitting Continued Installation ...
Page 12 - Tee Joint; Figure 14 - Gas Connection; * Minimum inlet pressure for purpose of input adjustment.; CAUTION: Avoid damage to; WARNING: Never connect; External Regulator
12 105192 UNVENTED PROPANE/LP GAS LOG HEATER FIREPLACE MANUFACTURERS INCORPORATED INSTALLATION Continued Tee Joint PipeNipple Cap 3" Minimum Sediment Trap GasRegulator From ExternalRegulator (11"W.C.** to 14"W.C. Pressure) A.G.A. Design-CertifiedManual Shutoff ValveWith 1/8" NPT Tap ...
Page 13 - Figure 15 - Manual Shutoff Valve; Open; Figure 16 - Checking Gas Joints; Test Pressures In Excess Of 1/2 PSIG; Correct all leaks at once.; WARNING: Never use an open
13 105192 OWNER’S MANUAL ON POSITION OFF POSITION INSTALLATION Continued Figure 15 - Manual Shutoff Valve Open Closed ManualShutoffValve Figure 16 - Checking Gas Joints Control ValveLocation Propane/LPSupply Tank ManualShutoffValve Pressure Testing Gas SupplyPiping System Test Pressures In Excess Of...
Page 14 - WARNING: Failure to position; INSTALLING LOGS; Make sure log does not; CAUTION: After installation; Burner
14 105192 UNVENTED PROPANE/LP GAS LOG HEATER FIREPLACE MANUFACTURERS INCORPORATED INSTALLATION Continued WARNING: Failure to position the parts in accordance with thesediagrams or failure to use onlyparts specifically approved withthis heater may result in propertydamage or personal injury. INSTALLI...
Page 15 - FOR YOUR SAFETY; Control Knob; Figure 19 - Control Knob and Ignitor Button Location; LIGHTING; • If fireplace has glass doors,; Note: Appearance of pilot assembly may
15 105192 OWNER’S MANUAL 1. STOP! Read the safety information,column 1. 2. Make sure manual shutoff valve isfully open. 3. Press in and turn control knob clock- wise Clockwise to the OFF position. Figure 20 - Pilot OPERATINGHEATER FOR YOUR SAFETY READ BEFORE LIGHTING WARNING: If you do not fol- low ...
Page 16 - Appearance of pilot; Thermocouple; Figure 21 - Correct Pilot Flame Pattern; Pilot Burner; Figure 22 - Incorrect Pilot Flame Pattern; Shutting Off Heater; WARNING: Do not operate
16 105192 UNVENTED PROPANE/LP GAS LOG HEATER FIREPLACE MANUFACTURERS INCORPORATED INSPECTINGBURNERS Check pilot flame pattern and burner flamepatterns often. PILOT FLAME PATTERN Figure 21 shows a correct pilot flame pat-tern. Figure 22 shows an incorrect pilotflame pattern. ( Note: Appearance of pil...
Page 17 - TROUBLESHOOTING; POSSIBLE CAUSE; All troubleshooting items are listed in
17 105192 OWNER’S MANUAL TROUBLESHOOTING WARNING: Turn off and un- plug heater and let cool beforeservicing. Only a qualified ser-vice person should service andrepair heater. CAUTION: Never use a wire, needle, or similar object to cleanODS/pilot. This can damage ODS/pilot unit. POSSIBLE CAUSE 1. Ign...
Page 18 - OBSERVED PROBLEM; nance, page 20) or replace burner orifice
18 105192 UNVENTED PROPANE/LP GAS LOG HEATER FIREPLACE MANUFACTURERS INCORPORATED TROUBLESHOOTING Continued OBSERVED PROBLEM Burner does not light after ODS/pilot is lit Delayed ignition burner Burner backfiring during combustion Slight smoke or odor during initial operation Heater produces a whistl...
Page 19 - IMPORTANT
19 105192 OWNER’S MANUAL TROUBLESHOOTING Continued WARNING: If you smell gas • Shut off gas supply.• Do not try to light any appliance.• Do not touch any electrical switch; do not use any phone in your building. • Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s ...
Page 20 - WARNING: Turn off heater; LOGS; SERVICE HINTS; When Gas Pressure Is Too Low; Figure 24 - Pilot Inlet Air Hole
20 105192 UNVENTED PROPANE/LP GAS LOG HEATER FIREPLACE MANUFACTURERS INCORPORATED CLEANING ANDMAINTENANCE WARNING: Turn off heater and let cool before cleaning. CAUTION: You must keep control areas, burner, and circu-lating air passageways of heaterclean. Inspect these areas ofheater before each use...
Page 21 - PARTS UNDER WARRANTY; SPECIFICATIONS; FIREPLACE HOOD
21 105192 OWNER’S MANUAL Note: Use only original replacement parts. This will protect your warranty coverage forparts replaced under warranty. PARTS UNDER WARRANTY Contact authorized dealers of this prod-uct. If they can’t supply original replace-ment part(s), call Fireplace Manufactur-ers Incorpora...
Page 22 - ODS Pilot
22 105192 UNVENTED PROPANE/LP GAS LOG HEATER FIREPLACE MANUFACTURERS INCORPORATED ILLUSTRATEDPARTSBREAKDOWN HEAT MAJIC™FVF18PFVF24PFVF30P ODS Pilot 4 12 21 10 11 21 7 21 5 6 8 9 15 14 16 19 2 18 13 19 17 20 18 3 1
Page 23 - PARTS LIST; KEY
23 105192 OWNER’S MANUAL PARTS LIST FVF18PFVF24PFVF30P This list contains replaceable parts used in your heater. When ordering parts, follow theinstructions listed under Replacement Parts on page 21 of this manual. KEY PART NUMBER FOR NO. FVF18P FVF24P FVF30P DESCRIPTION QTY 1 105186-01 105186-02 10...
Page 24 - KEEP THIS WARRANTY; WARRANTY INFORMATION; Model; NOT A UPC; LIMITED WARRANTY; For information about this warranty write:
KEEP THIS WARRANTY WARRANTY INFORMATION Always specify model and serial numbers when communicating with the factory. We reserve the right to amend these specifications at any time without notice. The only warranty applicable is our standard written warranty.We make no other warranty, expressed or im...