Page 2 - Environmentally sound; Table of contents
2 The compact footprint and service from the front of the units save valu-able floor space in equipment rooms. Belt drive condensers provide adequate static to overcome ducting and louver static losses. This allows units to be po-sitioned against an existing window or wall louver, or ducted to the o...
Page 3 - AHRI* capacity ratings; Model number nomenclature
3 AHRI* capacity ratings LEGEND *AHRI — Air Conditioning, Heating, and Refrigeration Institute. NOTE: Unit is tested in accordance with AHRI standard 340/360. UNIT 50XCA NOMINAL TONS EVAPORATOR CFM CONDENSER CFM NET COOLING (Btuh) TOTAL kW EER IEER 06 5 1,875 2,800 65,000 5.8 11.2 11.4 08 7 1 / 2 2,...
Page 4 - Physical data
4 LEGEND UNIT 50XCA 06 08 12 14 16 24 NOMINAL CAPACITY (tons) 5 7 1 / 2 10 12 15 20 UNIT OPERATING WEIGHT (lb) 891 1144 1269 1298 1575 2000 COMPRESSOR Copeland S croll Compressor Model ZP57 ZP67 ZP51 ZP57 ZP72 ZP103 Qty 1 1 2 2 2 2 Steps of Control 1 1 2 2 2 2 Operating Charge R-410A (lb) 17.4 21.4 ...
Page 7 - Selection procedure (50XCA08 unit example); SERVICE CLEARANCE
7 Selection procedure (50XCA08 unit example) I Determine design conditions. Given: Cooling Requirements Total Cooling Capacity (TC) . . . . . . . . . 82,000 BtuhSensible Cooling Capacity (SHC) . . . . . 65,000 BtuhEvaporator Air Quantity. . . . . . . . . . . . . 3,000 CfmCondenser Air Quantity . . ....
Page 8 - Performance data
8 GROSS COOLING CAPACITIES LEGEND 50XCA06 (5 TONS) Entering Condenser Air AIR ENTERING EVAPORATOR — 80 F Edb (F) - CFM 2500 2000 1500 Air Entering Evaporator — Ewb (F) ECT (F) CFM 57 62 67 75 57 62 67 75 57 62 67 75 BF 0.20 0.10 0.10 0.03 0..34 0.15 0.14 0.10 0.44 0.22 0.18 0.15 55 2100 TC 73.4 74.8...
Page 26 - Electrical data
26 UNIT ELECTRICAL DATA LEGEND NOTE S : 1. In compliance with NEC requirements for multimotor and combination load equipment (NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse orHACR circuit breaker. Canadian units may be fuse or circuit breaker. 2. Wire sizing ...
Page 28 - Typical wiring schematic
28 IFM COMP1 121/BLK 12 3 /BLU 122/YEL 11 8 /BLK 120/BLU 119/YEL C1 125/BLK 126/BLK CH1 TB1 CLO1-Loop 10 3 /BLK 104/YEL 105/BLU 106/BLK 107/YEL 10 8 /BLU 109/GRN 111/BLK 112/YEL 11 3 /BLU 2 1 3 T2 L2 T1 L1 T 3 L 3 150/BLK 151/YEL 501/RED 500/BRN IFC/IFR DISC1 L2L 3 L1 GND 100/BLK 101/BLK 102/BLK T 3...
Page 30 - Operating sequence; Controls
30 Operating sequence All units require the addition of a thermostat accessorypackage to complete the control circuit. The sequence ofoperation may vary depending on which package isselected. Room-mounted thermostat — The unit uses an electronic thermostat mounted in the conditioned space.Fan circul...
Page 31 - Typical piping and wiring
31 LEGEND NOTE S : 1. Wiring and piping shown are general points of connection guides only and are not intended for or to include all details for a specific installation. 2. All wiring must comply with applicable local and national codes.3. All piping must follow standard piping techniques. Refer to...
Page 32 - Application data
32 Location For best results unit must be properly located and installed.Selected location should not be adjacent to an acousticallysensitive space, for example a conference room or execu-tive office. The best location is in mechanical rooms nearareas like elevators, restrooms, stairways, or similar...
Page 33 - Setting condenser fan speed
33 Setting condenser fan speed The 50XCA condenser has a centrifugal blower and a vari-able pitch drive which allow adjusting the condenserairflow to match the static from the louvers, ductwork, filters, and sound traps (if used). It is best to adjust the fanto the nominal airflow and the rpm which ...
Page 34 - HVAC Guide Specifications; Guide specifications
34 Indoor Self-Contained Air-Cooled UnitConstant Volume Application HVAC Guide Specifications Size Range: 5 to 20 Tons Carrier Model Number: 50XCA Part 1 — General 1.01 SYSTEM DESCRIPTION Indoor packaged vertical air-cooled cooling unitusing hermetic scroll compressors and built-in con-denser fan fo...