Page 2 - Fig. 1 — Motormaster® V Control
2 Table 2 — Motormaster® V Control Package Contents — 48/50P030-060 Units ITEM CRLOWAMB033A00 CRLOWAMB034A00 CRLOWAMB035A00 Connector ( 1 / 2 -in.) HW60EA001 Connector (1-in.) HW60HH006 Controller, 230 V 2 Hp HR46TN001 — — Controller, 460 V 2 Hp — HR46TN002 — Controller, 575 V 2 Hp — — HR46TN003 Enc...
Page 3 - Table 4 — Motormaster V Control Package Usage; INSTALLATION
3 Table 3 — Motormaster V Control Package Contents — 48/50P070-100 Units Table 4 — Motormaster V Control Package Usage INSTALLATION Pre-Installation — Inspect the contents of this accessory package before installing. File a claim with the shipper if there is shipping damage or if a part is missing. ...
Page 4 - Fig. 2 — Wind Baffle Details; UNIT SIZE; BAFFLE INSTALLATION LOCATION (SIZES 050 AND 060 SHOWN)
4 WIND BAFFLE Fig. 2 — Wind Baffle Details NOTE: 48/50P030, 035, and 070-100 units do not requirebaffles. UNIT SIZE QUANTITY DIMENSION “A” in. mm 030,035 Not Used — — 040-060 2 78.125 ± 0.125 1984 ± 3 070-100 Not Used — — BAFFLE INSTALLATION LOCATION (SIZES 050 AND 060 SHOWN) a48-8561 a48-8560
Page 5 - WARNING
5 Step 2 — Mounting and Electrical Connec-tions for Motormaster® V Control 48/50P030-060 UNITS — For 48/50P030-035 units, the Mo- tormaster controlled outdoor-fan motor (OFM) is the no. 1 OFM (see Fig. 3). The no. 2 OFM is controlled by the Com- fort link head pressure control routine. For 48/50P040...
Page 11 - Table 4 — Configuration Table; Comfort; Step 4 — Test Motormaster V Control —
11 Step 3 — Configure Motormaster ® V Con- trol — The Motormaster V control is configured for propor- tional integral (PI) control mode. The Motormaster V varies the condenser fan motor speedto maintain a set point of 320 psig liquid line pressure in response to a 0 to 5 vdc feed- back signal from t...
Page 12 - Fig. 11 — Motormaster
12 OFM-1 (070,075)OFM-2 (090,100) MMV-B L1 L2 L3 T1 T2 T3 B- B+ BLK BLK BLU YEL 11 12 13 22 23 21 OFM-3 (070,075)OFM-6 (090,100) 1 2 5 6 11 12 2 14 13A 13B 13C 15 5 9 FR-B MMPT-B 230-3-60 SHOWN.REFER TO TABLE 4 FORALTERNATE VOLTAGECONNECTIONS FR-B OFC 13 14 C1 C2 ADD FAN RELAY (FR-B) IN PARALLEL WIT...
Page 13 - CANNOT; Fault Lockout —
13 Drive Programming — Table 5 shows all program pa- rameters for each of the operating modes. Refer to Trouble- shooting section before attempting to change programming in the Motormaster V control. TO ENTER PASSWORD AND CHANGE PROGRAM VALUES: 1. Press MODE.2. The display will read “00” and the upp...
Page 14 - Table 5 — Program Parameters for the Operating Mode; PARAMETERS
14 Table 5 — Program Parameters for the Operating Mode LEGEND PARAMETERS DESCRIPTION MODE 1 MODE 2 MODE 4 P01 Line Voltage: 01 = low line, 02 = high line 01 02 02 P02 Carrier Freq: 01 = 4 kHz, 02 = 6 kHz, 03 = 8 kHz 01 01 01 P03 Startup mode: flying restart 06 06 06 P04 Stop mode: coast to stop 01 0...
Page 15 - Table 6 — Fault Codes
15 EPM Chip — The drive uses a electronic programming module (EPM) chip to store the program parameters. This is an EEPROM memory chip and is accessible from the front of the VFD. It should not be removed with power applied to the VFD. Loss of CCN Communications — Carrier Comfort Network ® (CCN) com...