PROCEDURE 2—WIRING FOR HEAT PUMPS Heat pumps require a normally closed isolation relay with the 24-v coil connected to the C and O terminals of defrost board. A. 208/230-v Applications For 208/230-v heat pump applications, refer to Fig. 3 and wire low-ambient pressure switch as follows: 1. Remove bl...
START-UP To start units equipped with the low-ambient pressure switch, perform the following steps: 1. Turn power on to unit. 2. Set thermostat below room temperature. 3. Wait for the unit to start. There may be a 5-minute delay in the thermostat or in the outdoor unit. 4. Observe unit operation as ...
Carrier WeatherMaker Units A95444 7 / 32 ″ x 3 / 8 ″ (5.56 x 9.53) SLOT 4 REQ'D 1 / 2 ″ (12.7) TYP J 7 / 16 ″ (11.6) TYP C A 7 / 16 ″ (11.6) TYP B M 6 1 / 16 ″ (154.0) 1 / 2 ″ (12.7) TYP H 3 / 8 ″ (9.6) TYP G J K E D L 9 / 64 ″ (3.45) DIA HOLE 1 REQ'D 7 / 32 ″ (5.56) DIA HOLE 3 REQ'D 7 / 32 ″ x 2 ″ ...
Manual Carrier KSALA0301410
Summary
2 Table 1—Kit Usage and Cut In/Cut Out Pressures KIT PART NO. REFRIGERANT PRESSURE SWITCH CLOSES (PSIG) PRESSURE SWITCH OPENS (PSIG) WIRE COLORS KSALA0201R22 R --- 22 225 100 Blue and Yellow KSALA0301410 R --- 410A 365 200 Blue and Violet SERVICE FITTING CAP VALVE CORE END ADAPTER TEE FLARE NUT ON P...
3 C TDR LPS LPS C TDR T LOW-PRESSURE SWITCHCONTACTOR COILTIME DELAY RELAYRELAY COIL FACTORY WIRINGFIELD WIRING T A93165 Fig. 5 — Low Voltage Wiring for Winter Start Control START--UP To start units equipped with the low--ambient pressure switch, perform the following steps: 1. Turn power on to unit....
4 7 / 32 ″ x 3 / 8 ″ (5.56 x 9.53) SLOT 4 REQ'D 1 / 2 ″ (12.7) TYP J 7 / 16 ″ (11.6) TYP C A 7 / 16 ″ (11.6) TYP B M 6 1 / 16 ″ (154.0) 1 / 2 ″ (12.7) TYP H 3 / 8 ″ (9.6) TYP G J K E D L 9 / 64 ″ (3.45) DIA HOLE 1 REQ'D 7 / 32 ″ (5.56) DIA HOLE 3 REQ'D 7 / 32 ″ x 2 ″ (5.56 x 50.8) SLOT 1 / 4 ″ (6.3)...