Page 2 - PROCEDURE 2—WIRING FOR HEAT PUMPS; switch to same NC terminal of isolation relay.; REQUIRED CHANGES FOR COOLING UNITS AND HEAT PUMP UNITS

PROCEDURE 2—WIRING FOR HEAT PUMPS Heat pumps require a normally closed isolation relay with the 24-v coil connected to the C and O terminals of defrost board. A. 208/230-v Applications For 208/230-v heat pump applications, refer to Fig. 3 and wire low-ambient pressure switch as follows: 1. Remove bl...

Page 3 - Fig. 4—Power Wiring for 460-v Heat Pump Applications

START-UP To start units equipped with the low-ambient pressure switch, perform the following steps: 1. Turn power on to unit. 2. Set thermostat below room temperature. 3. Wait for the unit to start. There may be a 5-minute delay in the thermostat or in the outdoor unit. 4. Observe unit operation as ...

Page 4 - Carrier WeatherMaker Units; BAFFLE; OUTDOOR; BAFFLE ASSEMBLY

Carrier WeatherMaker Units A95444 7 / 32 ″ x 3 / 8 ″ (5.56 x 9.53) SLOT 4 REQ'D 1 / 2 ″ (12.7) TYP J 7 / 16 ″ (11.6) TYP C A 7 / 16 ″ (11.6) TYP B M 6 1 / 16 ″ (154.0) 1 / 2 ″ (12.7) TYP H 3 / 8 ″ (9.6) TYP G J K E D L 9 / 64 ″ (3.45) DIA HOLE 1 REQ'D 7 / 32 ″ (5.56) DIA HOLE 3 REQ'D 7 / 32 ″ x 2 ″ ...

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
9 Page 9
10 Page 10
11 Page 11
12 Page 12
13 Page 13
14 Page 14
15 Page 15
16 Page 16
17 Page 17
18 Page 18

Summary

Page 2 - CAUTION; KS

2 Table 1—Kit Usage and Cut In/Cut Out Pressures KIT PART NO. REFRIGERANT PRESSURE SWITCH CLOSES (PSIG) PRESSURE SWITCH OPENS (PSIG) WIRE COLORS KSALA0201R22 R --- 22 225 100 Blue and Yellow KSALA0301410 R --- 410A 365 200 Blue and Violet SERVICE FITTING CAP VALVE CORE END ADAPTER TEE FLARE NUT ON P...

Page 3 - Low Voltage Wiring for Winter Start Control

3 C TDR LPS LPS C TDR T LOW-PRESSURE SWITCHCONTACTOR COILTIME DELAY RELAYRELAY COIL FACTORY WIRINGFIELD WIRING T A93165 Fig. 5 — Low Voltage Wiring for Winter Start Control START--UP To start units equipped with the low--ambient pressure switch, perform the following steps: 1. Turn power on to unit....

Page 4 - BAFFLE; BAFFLE ASSEMBLY

4 7 / 32 ″ x 3 / 8 ″ (5.56 x 9.53) SLOT 4 REQ'D 1 / 2 ″ (12.7) TYP J 7 / 16 ″ (11.6) TYP C A 7 / 16 ″ (11.6) TYP B M 6 1 / 16 ″ (154.0) 1 / 2 ″ (12.7) TYP H 3 / 8 ″ (9.6) TYP G J K E D L 9 / 64 ″ (3.45) DIA HOLE 1 REQ'D 7 / 32 ″ (5.56) DIA HOLE 3 REQ'D 7 / 32 ″ x 2 ″ (5.56 x 50.8) SLOT 1 / 4 ″ (6.3)...