Page 2 - INSTALLATION; Check Equipment and Job Site; WARNING; Mounting Infinity Control; CCUI
2 INSTALLATION Check Equipment and Job Site Inspect equipment. File claim with shipping company prior toinstallation if shipment is damaged or incomplete. Infinity Control Location and Wiring Considerations ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or...
Page 3 - Control
3 A03185 Fig. 3 -- Infinity t Control A03186 Fig. 4 -- Recessed Mount Backplate A03187 Fig. 5 -- Surface Mount Backplate A04017 Fig. 6 -- Thin Decorative Backplate Recessed terminal block in wall 1 1 / 2 ˝ wide by 2 1 / 8 ˝ high Recessed Mount Interlocking Tabs (4) A03190 Fig. 7 -- Recessed Mount As...
Page 4 - INSTALLING INFINITY CONTROL; ELECTRICAL OPERATION HAZARD; NOTE
4 A03192 Fig. 10 -- Decorative Backplate Assembly INSTALLING INFINITY CONTROL ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury, death or equipment damage.Before installing, modifying, or servicing system, the main electrical disconnect switch must be in the ...
Page 5 - Humidifier Connection; CAUTION; Power Up Sequence
5 be used when connecting to furnace (or fan coil). Ensure connectoris inserted properly into circuit board. (See Fig. 14.) A B C D A03193 Fig. 14 -- Wire ABCD Connector ELECTRICAL OPERATION HAZARD Failure to follow this caution may result in equipment damage or improper operation.Improper wiring of...
Page 6 - Selecting Outdoor Unit; Selecting Electric Heater; Hydronic Heat Applications; INSTALLED FILTER
6 Installer will be asked to select Accessories. Packaged Productswill be automatically identified and the Installer will be asked to select Accessories. Proceed to Selecting Accessories. NOTE : If the variable--speed indoor equipment (furnace or fan coil) cannot be found, the User Interface will di...
Page 7 - Equipment Summary; Static Pressure Check; QUICK START; Override Heating Schedule; INSTALL / SERVICE MENUS
7 UV Lights Installed This screen will appear to select whether UV lights are installed on the system, select YES or NO, then press right--side button tocontinue. Equipment Summary EQUIPMENT SUMMARY FURNACE 58MVB0100-12 AC 24ANA136A003 FILTER EAC HUMIDIFIER YES UV LIGHTS YES NO YES SETUP COMPLETE! S...
Page 8 - EQUIPMENT SUMMARY MENU; INSTALL MENU; SETUP
8 INSTALL/SERVICE EQUIPMENT SUMMARY INSTALL SETUP CHECKOUT SERVICE SOFTWARE VERSION 1 EXIT SELECT A03200 Fig. 22 -- Install / Service Menus NOTE : The INSTALL / SERVICE menu will automatically exit after 60 minutes of no push button activity. EQUIPMENT SUMMARY: Shows all equipment recognized by and ...
Page 11 - Humidifier Installed:
11 Setup -- Hybrid Heat HYBRID HEAT SETUP FURNACELOCKOUT: > 30 F HEAT PUMPLOCKOUT: < 15 F DEFROST W/FURNACE: YES < BACK HP TO FURNACESTAGE TIME: 15 MIN OUTSIDE LOCKOUT TEMPS A07030 Fig. 28 -- Hybrid Heat Setup FURNACE LOCKOUT -- Temperature above which only the heat pump will operate, excep...
Page 12 - CHECKOUT MENUS; FURNACE CHECK; Checkout -- Heat Pump Cooling or AC Cooling; SERVICE MENUS
12 SYSTEM MAINTENANCE < BACK REMIND OWNER OFMAINTENANCE EVERY: 12 MONTHS % USED: 50% RESET > A07033 Fig. 30 -- System Maintenance Pressing the right side button will reset the timer. Pop--up confirmation will be shown. Setup -- Utility Saver Cooling/Heat Pump Heating: (Hybrid Heat & Hydron...
Page 13 - Service -- Furnace Status or Gas PAC Status; TODAY’S DATE
13 Service -- Furnace Status or Gas PAC Status The Status screens will show all of the current operating parametersof each installed piece of equipment. NOTE : To view a less detailed Equipment Status screen, press and hold the right side button for 3 seconds. This will displayequipment stage, fan s...
Page 14 - OPERATIONAL INFORMATION
14 system. This name and phone number will appear to thehomeowner whenever a service reminder pop--up message is displayed (i.e. Change Filter, etc.)To edit: S Use Temp +/-- button to move cursor left and right. S Use Time +/-- button to select numbers and letters. S Use Scroll button to move up and...
Page 15 - TROUBLESHOOTING
15 static pressure. If it is reduced before one hour has elapsed, it willresume cooling operation. After one hour, cooling will be resumed. Dehumidify Operation Once a target cooling humidity setpoint is selected in the Advanced Setup COOLING HUMIDITY screen, two other setup optionsaffect Dehumidify...
Page 16 - SYSTEM MALFUNCTION SCREEN; HVAC SERVICE; Outdoor Unit
16 SYSTEM MALFUNCTION SCREEN OUTSIDE: 84 _ | FAN: AUTO 71 _ HVAC SERVICE 1 --- 800 --- 555 --- 1212 SYSTEM MALFUNCTION CALL TECHNICIAON A07036 Fig. 34 -- System Malfunction Screen Fan Coil The code number represents flash code on circuit board of fan coil.Certain faults will generate a system malfun...