Page 2 - SAFETY CONSIDERATIONS; WARNING; CAUTION; INTRODUCTION; Step 1 — Check Equipment; except
2 SAFETY CONSIDERATIONS Improper installation adjustment, alteration, service, maintenance,or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or propertydamage. Consult a qualified installer, service agency, or your distributor or branch f...
Page 6 - Step 3 — Provide Clearances; IMPORTANT; Step 4 — Rig and Place Unit; ELECTRICAL SHOCK HAZARD; Rigging/Lifting of Unit; UNIT FALLING HAZARD; UNIT FALLING HAZARD
6 Step 3 — Provide Clearances The required minimum service clearances are shown in Fig. 5 and6. Adequate ventilation and outdoor air must be provided. The outdoor fan draws air through the outdoor coil and discharges it through the top fan grille. Be sure that the fan discharge does notrecirculate t...
Page 7 - DETAIL A; Step 5 — Select and Install Ductwork
7 ACCESS PANELS MUST BE IN PLACE WHEN RIGGING. PANNEAUX D'ACCES DOIT ÊTRE EN PLACE POUR MANIPULATION. 50CY502286 2.0 CAUTION - NOTICE TO RIGGERSPRUDENCE - AVIS AUX MANIPULATEUR Use top skid as spreader bar. / Utiliser la palette du haut comme barre de répartition SEAL STRIP MUST BE INPLACE BEFORE PL...
Page 8 - PROPERTY DAMAGE HAZARD; Step 6 — Provide for Condensate Disposal; NOTE
8 CONVERTING HORIZONTAL DISCHARGE UNITS TODOWNFLOW (VERTICAL) DISCHARGE UNITS ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death.Before installing or servicing system, always turn off main power to system and tag lockout. There may be more than one discon...
Page 9 - Step 7 — Install Electrical Connections; UNIT COMPONENT DAMAGE HAZARD
9 TRAPOUTLET 1-in. (25 mm) min. 2-in. (51 mm) min. A09052 Fig. 10 -- Condensate Trap Step 7 — Install Electrical Connections ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death.The unit cabinet must have an uninterrupted, unbroken electrical ground. This g...
Page 11 - TOP COVER; A. Accessory Electric Heaters
11 INDOORTHERMOSTAT DISCONNECTPER NEC FROMPOWERSOURCE RETURNAIR TOP COVER POWER ENTRY CONTROL ENTRY A09091 Fig. 11 -- Typical Installation GROUND SCREW (IN SPLICE BOX) YEL BLK GROUND LEAD SINGLE-PHASE CONNECTIONS TO DISCONNECT PER NEC LEGEND NEC – National Electrical Code Field Wiring Splice Connect...
Page 12 - The fan coil control board terminal marked HUM is provided for
12 NOTE : Mis--wiring OAT inputs will not cause damage to either Infinity control or thermistor. If the thermistor is wired incorrectly,no reading will appear at UI. Re--wire thermistor correctly fornormal operation. C. Humidifier Connections The fan coil control board terminal marked HUM is provide...
Page 13 - ENVIRONMENTAL HAZARD
13 PRE--START--UP FIRE, EXPLOSION, ELECTRICAL SHOCK AND ENVIRONMENTAL HAZARD Failure to follow this warning could result in personal injury or death and/or property damage. 1. Follow recognized safety practices and wear protective goggles when checking or servicing refrigerant system. 2. Do not oper...
Page 17 - Step 2 — Sequence of Operation
17 STATUS CODE 36, HEATER OUTPUT NOT SENSED WHENENERGIZEDFan coil control is provided with circuitry to detect presence of a24--vac signal on electric heater stage 1 and stage 2 outputs.If fan coil control energizes either heater stage and does not detect the 24--vac signal on output, Status Code 36...
Page 18 - Table 2 – Heat Pump/Air Conditioner Board Status Codes; After second stage is satisfied, the unit returns to low--stage; Outdoor fan motor will continue to operate for one
18 Table 2 – Heat Pump/Air Conditioner Board Status Codes OPERATION FAULT AMBER LED FLASH CODE POSSIBLE CAUSE AND ACTION Standby – no call for unit opera- tion None On solid, no flash Normal operation. Emergency Mode Standard Ther- mostat Control Rapid, con- tinuous flashing Unit being controlled by...
Page 20 - Step 3 — Check for Refrigerant Leaks
20 QUIET SHIFTQuiet Shift is a field--selectable defrost mode which may eliminate occasional noise that could be heard at the start of the defrost cycleand restarting of the heating cycle. This feature must be enabled at the UI. When activated, the following sequence of operation will occur. Reversi...
Page 22 - MAINTENANCE
22 Table 3 – Wet Coil Pressure Drop (in. wc) UNIT SIZE STANDARD CFM (SCFM) 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 24 0.005 0.007 0.010 0.012 0.015 – – – – – – – – – – – 30 – 0.007 0.010 0.012 0.015 0.018 0.021 0.024 – – – – – – – – 36 – – – 0.019 0.023 0.027 0.03...
Page 23 - UNIT OPERATION HAZARD; Infinity Top
23 Step 1 — Air Filter IMPORTANT : Never operate the unit without a suitable air filter in the return--air duct system. Always replace the filter with thesame dimensional size and type as originally installed. See Table 1for recommended filter sizes.Inspect air filter(s) at least once each month and...
Page 24 - Step 11 — Refrigerant System
24 Step 9 — Pressure Switches Pressure switches are protective devices integrated into the controlcircuit (low voltage). They shut off compressor if abnormally high or low pressures are present in the refrigeration circuit. These pressure switches are specifically designed to operate with Puron(R--4...
Page 25 - TROUBLESHOOTING
25 cylinder in upright position and a commercial metering device inmanifold hose. Charge refrigerant into suction line. TROUBLESHOOTING LED DESCRIPTIONLEDs built into Infinity control boards provide installer or service person information concerning operation and/or fault condition of the unit contr...
Page 26 - FINAL CHECKS; CARE AND MAINTENANCE
26 COMPRESSOR INTERNAL RELIEFThe compressor is protected by an internal pressure relief (IPR) which relieves discharge gas into compressor shell whendifferential between suction and discharge pressures exceeds 550 -- 625 psi. The compressor is also protected by an internal overload attached to motor...
Page 27 - Never
27 HEAT PUMP WITH PURON REFRIGERATION SECTION QUICK--REFERENCE GUIDE Puron refrigerant operates at 50--70 percent higher pressures than R--22. Be sure that servicing equipment and replacement components are designed to operate with Puron. Puron refrigerant cylinders are rose colored. S Puron refrige...
Page 28 - Table 7 – Troubleshooting Chart
28 Table 7 – Troubleshooting Chart SYMPTOM CAUSE REMEDY Compressor and outdoor fan will not start Power failure Call power company Fuse blown or circuit breaker tripped Replace fuse or reset circuit breaker Defective contactor, transformer, HP/AC control board, or high--pressure, loss--of--charge or...