Page 2 - Table of contents
2 Lower cost When 36R,T terminals are specified, the users are able to match the equip-ment closely to the job requirements. Carrier’s optimized computer selec-tion assures that the terminals meet the performance and sound criteria needed, without causing additional op-erating expense or energy wast...
Page 4 - Model number nomenclature
4 3 6RV 1 0 F R 0 1 -- 0 – – 3 6RH – Horizont a l Byp ass Unit 3 6RM – Vertic a l Byp ass Unit with M a n ua l Control 3 6RP – Vertic a l Byp ass Unit with Pne u m a tic Control 3 6RV – Vertic a l Byp ass Unit 3 6TE – Vertic a l Byp ass Unit with Electric He a ter Electric Heater S ize ( 3 6TE only)...
Page 5 - Ratings and capacities
5 PRIMARY COIL COOLING CAPACITY RATINGS (Btuh) NOTE: Units are rated in accordance with ARI (Air Conditioning andRefrigeration Institute) Standard 445, under the following conditions:1.5 gpm of 50 F water, 8 ft of water pressure drop thru coil (16 ft for 36ST), 75 F dry bulb and 57 F wet bulb air en...
Page 6 - Physical data
6 UNIT OPERATING WEIGHTS (lb) NOTE: Weights include water in the coil but do not include field-supplied control valve packages. COIL WATER QUANTITIES ACCESSORY LINT SCREEN DIMENSIONS (in.) UNIT UNIT SIZE 1 2 3 4 36RH 38 47 54 66 36RM,RP,RV 33 42 48 59 36TE 39 48 54 65 UNIT SIZE QUANTITY Gallons lb 3...
Page 7 - Options and accessories
7 Factory-installed options Control options — Self-contained control packages are available for the 36RV and 36RH units for changeover andnon-changeover systems. The non-changeover controlpackage is also used on 36TE units. All control units havea washable filter contained in an easily accessible ho...
Page 8 - Dimensions — 36RH
8 RIGHT S IDE VIEW FRONT VIEW A D E " 3 F 3 " PLENUMEND PLUG OPTIONAL AIR VENT AVAILABLE S EE CHART BELOW FOR OPTIONAL FITTING S OPTIONALLINT S CREEN AVAILABLE OPTIONALCONDEN S ATE PAN WITH 11/16" DRAINODF S WEAT S UPPLY RETURN CONTROL S S EE OPTION S BALANCINGDAMPER ADJU S TMENT BELLOW ...
Page 10 - Dimensions — 36TE
10 RIGHT S IDE VIEW FRONT VIEW BALANCINGDAMPER ADJU S TMENT A E D 2 5/ 8 " 3 1/ 8 " PLENUMEND PLUG OPTIONAL AIR VENTAVAILABLE S EE CHART BELOW FOR OPTIONAL FITTING S OPTIONALLINT S CREEN AVAILABLE OPTIONALCONDEN S ATE PAN WITH 11/16" DRAINODF S WEAT S UPPLY RETURN BELLOW S AIR CONNECTION...
Page 11 - General unit selection criteria; Cooling; Heating; Selection procedure
11 General unit selection criteria Two parameters must be satisfied in selecting an inductionair terminal, the unit must have enough capacity to main-tain proper room temperature and the unit must supply airat an acceptable sound level. After room air conditioning loads have been calculatedand the p...
Page 13 - Performance data
13 COIL CAPACITY MULTIPLIERS FOR FLOW RATES NOTE: For capacities not at 1.50 gpm, multiply capacities from Coil Cooling Capacities tables by the above multipliers. COIL WATER PRESSURE DROP (ft of water) GPM NOZZLE ARRANGEMENT F G H J K Unit Size 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 0.6 0.91 0.90 ...
Page 16 - Sequence of operation; Controls
16 Sequence of operation After a mixture of outdoor and return air is conditioned bythe central station air-handling unit, it is distributed througha high-velocity, high-pressure duct system to the Weather-master ® air terminal units. Here the conditioned primary (supply) air enters the unit's acous...
Page 17 - Changeover system —; Non-changeover system —; 6TE terminal units; Application data
17 Controls and control systems 36R series terminal units The 36R Series units are available with system-powered,self-contained controls. These controls operate with wall orunit-mounted, bi-metallic, bleed-type thermostats having a65 to 85 F operating range and a throttling range of±1.5 F. The power...
Page 23 - Electrical data
23 ELECTRIC HEATER ELECTRICAL DATA (36TE ONLY) LEGEND * Copper wire sizes based upon 60 C. Use latest NEC (National Electrical Code) standards for wire lengths (allow 3 % voltage drop) and fuse sizes. Follow all local codes required. To obtain maximum wirelength, divide allowable amperage per ft by ...
Page 24 - HVAC Guide Specifications; Guide specifications
24 Water Control Induction Bypass Air Terminals HVAC Guide Specifications Size Range: 19.4 to 131.9 nominal cfm Carrier Model Number: 36RH, 36RM, 36RP, 36RV, 36TEPart 1 — General 1.01 SYSTEM DESCRIPTION A. Water control induction system for ventilation, cool- ing, and heating. B. Equipment shall be ...