Page 2 - Anti-short cycle timer; Table of contents
2 Quiet operation The Carrier console WSHP provides exceptionally quiet operation for maxi-mum comfort. Design flexibility Aquazone™ console WSHP units are offered in 4 capacity sizes to meet indi-vidual zone needs efficiently and effec-tively. Standard and extended operat-ing range units are availa...
Page 4 - Puron; • Non-ozone depleting potential and; coils
4 The PremierLink™ peer-to-peer, In- ternet ready communicating control is designed specifically for constant vol-ume (CV) and variable volume and temperature (VVT ® ) applications. This comprehensive controls system allows water source heat pumps to be linked together to create a fully functional H...
Page 5 - Model number nomenclature
5 Model number nomenclature A qua zone™ W a ter S o u rce He a t P u mp Con s ole Unit with P u ron ® Refriger a nt (R-410A) ** W W S HP Open M u ltiple Protocol Comm u nic a ting Control with Complete C – Y W S HP Open M u ltiple Protocol Comm u nic a ting Control with Del u xe D – NRTL/C As an ENE...
Page 7 - Factory-installed options; Options and accessories
7 Factory-installed options Cupronickel heat exchangers are available for higher corrosion protection for applications such as open tower,geothermal, etc. Consult the water quality guidelines forproper application and selection of this option. Thermostat options include a unit-mounted manual changeo...
Page 8 - Field-installed accessories
8 falls below 50 F. When return-air temperature is raisedabove 55 F the compressor and blower stop.Override function — An override function is available forunits operating in occupied/unoccupied mode under thecontrol of an external timeclock or an energy managementsystem. A contact closure from the ...
Page 9 - offer; Hose kit assemblies; provide all the necessary compo-; Remote sensors; are available for Aquazone flush-mount; PremierLinkTM accessories; are available to provide a
9 Solenoid valves (brass body) offer 3.5 watt coil, 24 volt, 50/60 Hz, 740 amps inrush, .312 amps holding.Slow operation for quiet system application. Five sizes areavailable ( 1 / 2 , 3 / 4 , 1, 1 1 / 4 , 1 1 / 2 in.). Hose kit assemblies provide all the necessary compo- nents to hook up a water-si...
Page 10 - AQUAZONETM THERMOSTATS
10 Options and accessories (cont) COOL HEAT AUTO R 5-DAY PROGRAMMABLE/ NON-PROGRAMMABLE AUTO Pm COOL HEAT Carrier ® AQUAZONE™ THERMOSTATS 7-DAY PROGRAMMABLE/ LIGHT-ACTIVATED PROGRAMMABLE 7-DAY PROGRAMMABLE FLUSH MOUNT LON WALL SENSORS SENSOR ONLY SENSOR WITH OVERRIDE SENSOR WITH SET POINT ADJUSTMENT...
Page 11 - Dimensions; 0PEC09-15 BOTTOM RETURN CABINET DIMENSIONS — RIGHT HAND PIPING
11 Dimensions NOTES: 1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters.2. Access is reduced if optional disconnect box is selected.3. Optional autoflow valve, motorized water valve and disconnect box are shown. 3 0 11.5 (292) 4.9 (125) 3 .5 ( 8 9) 25.9 (65 8 ) DAMPER OP...
Page 12 - 0PEC18 BOTTOM RETURN CABINET DIMENSIONS — RIGHT HAND PIPING
12 Dimensions (cont) NOTES: 1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters.2. Access is reduced if optional disconnect box is selected.3. Optional autoflow valve, motorized water valve and disconnect box are shown. a50-8340 3 0˚ 11.50(292) 4.90 (125) 3 .50 ( 8 9) 25....
Page 13 - 0PEC09-15 BOTTOM RETURN CABINET DIMENSIONS — LEFT HAND PIPING
13 a50-8341 NOTES: 1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters.2. Access is reduced if optional disconnect box is selected.3. Optional autoflow valve, motorized water valve and disconnect box are shown. 3 0° 11.5 (292) 4.9 (125) 3 .5 ( 8 9) 25.9 (65 8 ) DAMPER OPE...
Page 14 - 0PEC18 BOTTOM RETURN CABINET DIMENSIONS — LEFT HAND PIPING
14 Dimensions (cont) NOTES: 1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters.2. Access is reduced if optional disconnect box is selected.3. Optional autoflow valve, motorized water valve and disconnect box are shown. 3 0˚ 11.50 (292) 4.90 (125) 3 .50 ( 8 9) 25.90 (65 8...
Page 15 - 0PEC09-15 FRONT RETURN CABINET DIMENSIONS — RIGHT HAND PIPING
15 a50-8343 NOTES: 1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters.2. Access is reduced if optional disconnect box is selected.3. Optional autoflow valve, motorized water valve and disconnect box are shown. 4 8 .0 3 0 3 .5 ( 8 9) 21.0 (5 33 ) 21.0 (5 33 ) REAR VIEW DI...
Page 16 - 0PEC18 FRONT RETURN CABINET DIMENSIONS — RIGHT HAND PIPING
16 Dimensions (cont) a50-8344 NOTES: 1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters.2. Access is reduced if optional disconnect box is selected.3. Optional autoflow valve, motorized water valve and disconnect box are shown. 54.00 3 0˚ 3 .50 ( 8 9) 21.00 (5 33 ) 21.00...
Page 17 - 0PEC09-15 FRONT RETURN CABINET DIMENSIONS — LEFT HAND PIPING
17 ° ( 8 9) L.H. (NOTE 2) .50 (1 3 ) 11.50 (292) .75 (19) 4.12 (105) (Note 2) a50-8345 NOTES: 1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters.2. Access is reduced if optional disconnect box is selected.3. Optional autoflow valve, motorized water valve and disconnect b...
Page 18 - 0PEC18 FRONT RETURN CABINET DIMENSIONS — LEFT HAND PIPING
18 Dimensions (cont) a50-8346 NOTES: 1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters.2. Access is reduced if optional disconnect box is selected.3. Optional autoflow valve, motorized water valve and disconnect box are shown. 54.00 3 0˚ 3 .50 ( 8 9) 21.00(5 33 ) 21.00(...
Page 19 - SIS DIMEN
19 Power S upply Blower Deck Blower Acce ss P a nel Compre ss or Acce ss P a nel Control Box 40.98 (1041) 4.46 (1 13) 0.75 (19) 0.75 (19) * 20.50 (521) 11 .5 4 (293) *16.66 (423) 30° 0.87 (22) Hard Wire Power S upply Blower Deck Blower Acce ss P a nel Compre ss or Acce ss P a nel Control Box 7.50 (1...
Page 20 - SSIS DIM
20 Dimensions (cont) NO TES: 1. Dimensions sho w n are in inches . Dimensions in parenthe ses are in millimeters . 2. Option al auto flo w v a lv e , motor iz ed w a te r v a lv e a nd disconnect bo x are sho w n. 3. Chassis ca n mount directly on f loor . Power S upply Blower Deck Compre ss or Acce...
Page 21 - ASSIS DI
21 Blower Deck Blower Acce ss P a nel Compre ss or Acce ss P a nel Control Box 46.98 (1 193) 4.49 (1 14) 0.75 (19) 0.75 (19) * 20.50 (521) Hard Wire Power S upply Blower Deck Blower Acce ss P a nel Compre ss or Acce ss P a nel Control Box 0.75 (19) 0.75 (19) 4.46 (1 13) * 20.50 (521) 46.98 (1 193) C...
Page 23 - Correction of Heat Extraction; Selection procedure (with 50PEC12 example)
23 I Determine the actual cooling and heating loads at the desired dry bulb and wet bulbconditions. Given:Total Cooling (TC) . . . . . . . . . . . . . . . 10,750 BtuhSensible Cooling (SC) . . . . . . . . . . . . . 8,650 BtuhEntering-Air Temperature db . . . . . . . . . . . . 80 FEntering-Air Tempera...
Page 25 - Performance data
25 50PEC09 — NOMINAL AIRFLOW 350 CFM LEGEND NOTES: 1. Interpolation is permissible; extrapolation is not.2. All entering air conditions are 80 F db and 67 F wb in cooling and 70 F db in heating. 3. ARI/ISO certified conditions are 80.6 F db and 66.2 F wb in cooling and 68 F db in heating. 4. Table d...
Page 30 - AQUAZONE PRODUCT GUIDE; Water loop system; Application data
30 Aquazone™ water source heat pump products are available in a flexible, efficient array of models, which can be used inall types of water loop, ground water, and ground looptype systems. Use Aquazone products to provide optimalenergy efficient solutions and adapt to the most challeng-ing design re...
Page 31 - Hybrid systems —; Condensate drainage; WATER QUALITY GUIDELINES; Acoustical design
31 pipe inserted into a hole. The hole is back-filled andgrouted after the pipe is inserted. The completed loop isconcealed below ground. The number of loops required de-pends on ground conditions, heating and cooling require-ments, and the depth of each hole. Hybrid systems — In some applications, ...
Page 32 - ASSOCIATED WITH NC CURVES; Environment; AIR LIMITS
32 Some of the factors that affect conversion of sound power to sound pressure and consequent NC level include:• Type of acoustical ceiling• Use of metal or flex duct• Absorption in the occupied space• Location in the occupied space• Open or closed layout plan• Use of open or ducted returns• Orienta...
Page 33 - COMPLETE C AND DELUXE D ELECTRONIC CONTROL FEATURES COMPARISON
33 COMPLETE C AND DELUXE D ELECTRONIC CONTROL FEATURES COMPARISON LEGEND BASIC FEATURES COMPLETE C COMPLETE C WITH LON DELUXE D DELUXE D WITH LON COMPLETE C OR DELUXE D WITH WSHP OPEN CONTROLLER High and Low Refrigerant Pressure Protection S S S S S Water Coil Freeze Protection S S S S S True 24 VA ...
Page 34 - ANTIFREEZE CORRECTION TABLE; Electrical data
34 ANTIFREEZE CORRECTION TABLE LEGEND Electrical data LEGEND ANTIFREEZE TYPE ANTIFREEZE % COOLING HEATING WPD CORRECTION FACTOR EWT 30 F EWT 90 F EWT 30 F Total Capacity Sensible Capacity Power Heating Capcity Power Water 0 1.000 1.000 1.000 1.000 1.000 1.000 Propylene Glycol 5 0.995 0.995 1.003 0.9...
Page 35 - WSHP Open sequence of operation; Scheduling —; Controls
35 WSHP Open sequence of operation The WSHP Open multi-protocol controller will control me-chanical cooling, heating and waterside economizer out-puts based on its own space temperature input and setpoints. An optional CO 2 IAQ (indoor air quality) sensor mounted in the space can maximize the occupa...
Page 37 - Waterside economizer —; Cooling
37 connected to a coil on the discharge side of the unit andsupplied by a boiler in order to maintain the desired heat-ing set point should the compressor capacity be insufficientor a compressor failure occurs. Unless a compressor faultcondition exists, the valve will only operate to supplementthe h...
Page 38 - Demand limit —; The WSHP Open controller has the; Condenser water linkage —; The control provides opti-
38 the entering water loop temperature is suitable (at least5 F below space temperature). If the optional coil is pro-vided and the water loop conditions are suitable, then thevalve will open to provide cooling to the space when re-quired. Should the capacity be insufficient for a periodgreater than...
Page 39 - Typical control wiring schematics
39 Typical control wiring schematics LEGEND NOTES: 1. Compressor and blower motor thermally pro- tected internally. 2. All wiring to the unit must comply with local codes. 3. Transformer is wired to 115-V (WHT) lead for 115/1/60 units; 265-V (BRN) lead for 265/1/60units; or 208-V (RED) lead for 208/...
Page 40 - 0PEC UNIT WITH COMPLETE C AND LON CONTROLLERS
40 Typical control wiring schematics (cont) LEGEND NOTES: 1. Compressor and blower motor thermally pro- tected internally. 2. All wiring to the unit must comply with local codes. 3. Transformer is wired to 115-V (WHT) lead for 115/1/60 units, 265-V (BRN) lead for 265/1/60units, 240-V (ORG) lead for ...
Page 41 - 0PEC UNIT WITH DELUXE D AND LON CONTROLLERS
41 *Optional wiring. AL — Alarm Relay Contacts BM — Blower Motor CAP — Capacitor CB — Circuit Breaker CO — Sensor, Condensate Overflow CR — Compressor Relay DM — Damper Motor FP1 — Sensor, Water Coil Freeze Protection FP2 — Sensor, Air Coil Freeze Protection HP — High-Pressure Switch JW1 — Jumper Wi...
Page 42 - 0PEC UNIT WITH MANUAL OR AUTO CHANGEOVER AND DELUXE D CONTROLLER
42 Typical control wiring schematics (cont) *Optional wiring. AL — Alarm Relay Contacts BM — Blower Motor BR — Blower Relay CAP — Capacitor CB — Circuit Breaker CO — Sensor, Condensate Overflow CR — Compressor Relay DM — Damper Motor FP1 — Sensor, Water Coil Freeze Protection FP2 — Sensor, Air Coil ...
Page 45 - WSHP OPEN CONTROL
45 WSHP OPEN CONTROL 01220 7-1 BT 4 8 5BT LE D 1 DB In s t a ll BT4 8 5 where device i s loc a ted a t the end of network s egment only. + 24v a c (If not in s t a lled, it m us t b e connected to DO-5) DEHUMIDIFY OUTPUT CONTACT (DO-6) (FACTORY OPTION) FAN S PEED (DO-7) (MED OR LOW) OA DAMPER (AO-2)...
Page 46 - PREMIERLINK CONTROLLER APPLICATIONS WITH DELUXE D CONTROL; PREMIERLINKTM CONTROLLER APPLICATIONS WITH COMPLETE C CONTROL
46 Typical control wiring schematics (cont) Y1 G R C AL1 CMP1 FAN PWR PREMIER LINK DELUXE D CONTROL J4 J8 J1 PWR CMPSAFE HS2 HS1 CMP2 Y2 W1 O/W2 J6 J5 S P T SAT L W T LEGEND NOTE: Reversing valve is on in Cooling mode. LWT — Leaving Water Temperature Sensor SAT — Supply Air Temperature Sensor SPT — ...
Page 47 - Typical piping; WATER IN; CONDEN; WATE; oNAL; or
47 Typical piping LEGEND *Dimension reduced by fitting if selected.NOTE: Dimensions shown are in inches. Dimensions in parentheses are in millimeters. EPT — External Pipe Thread IPT — Internal Pipe Thread WATER IN WATER OUT COMPRE SS OR ACCE SS PANEL CONTROL BOX 1. 8 4 (77) CONDEN S ATE 5/ 8 " (...
Page 48 - OUT; BLOWER DECK; OPTIONAL; VINYL HO; WATER; IPT OR
48 Typical piping (cont) LEGEND *Dimension reduced by fitting if selected.NOTE: Dimensions shown are in inches. Dimensions in parentheses are in millimeters. EPT — External Pipe Thread IPT — Internal Pipe Thread RIGHT HAND CONFIGURATION OPTMOTWAT OPTAUTVAL V WATE R . 8 75 ( OD C 3 /4" IP 3 /4...
Page 49 - Console Water Source Heat Pumps; HVAC Guide Specifications; Guide specifications
49 Console Water Source Heat Pumps HVAC Guide Specifications Size Range: 8,600 to 16,200 BtuhCooling Capacity11,400 to 20,100 BtuhHeating Capacity Carrier Model Number: 50PEC Part 1 — General 1.01 SYSTEM DESCRIPTION A. Install water source heat pumps, as indicated on the plans with capacities and ch...
Page 51 - Comfort
51 will permit all units to be daisy chain connectedby a 2-wire twisted pair shielded cable. The fol-lowing points must be available at a central orremote computer location:a. space temperatureb. leaving water temperaturec. discharge air temperatured. command of space temperature set pointe. cooling...