Page 4 - Hanger Bracket Dimensions; LEFT RETURN STRAIGHT DISCHARGE
4 B A C G F E D R H L M N 1.8” K 1 2 5 4 3 CAP CSP BSP STRAIGHT (RIGHT)DISCHARGE LEFT INLET Hanger Bracket Dimensions O P Q A C T 2.2" S 34.1" 74.1" PLAN VIEW (TOP) FRONT FRONT OF UNIT V U LEFT RETURN STRAIGHT DISCHARGE Left Return Left View - Air Coil Opening 24” ServiceAccess Filter Br...
Page 5 - Right Discharge
5 B A C G F E D R H L M N 1.8” K 1 2 5 4 3 CAP CSP BSP LEFT INLET Hanger Bracket Dimensions O P Q A C T 2.2" S 34.1" 74.1" PLAN VIEW (TOP) 25.5” FRONT FRONT OF UNIT V U Left Return Left View - Air Coil Opening 24” ServiceAccess Filter Bracket Shown 24” ServiceAccess 4.2” Right Discharge ...
Page 11 - Step 6 — Condensate Drain; Fig. 5 — Horizontal Unit Pitch
11 Step 6 — Condensate Drain HORIZONTAL UNITS (50HQL) — Slope the unit towardthe drain at a 1 / 4 in. per foot pitch. See Fig. 5. If it is not possi- ble to meet the required pitch, a condensate pump should beinstalled at the unit to pump condensate to building drain. Horizontal units are not intern...
Page 13 - Table 3 — Water Quality Guidelines; Fig. 7 — Typical Ground-Water Piping Installation
13 Table 3 — Water Quality Guidelines *If the concentration of these corrosives exceeds the maximum allowable level, then the potential for serious corrosion problems exists. †Sulfides in the water quickly oxidize when exposed to air, requiring that no agitation occur as the sample is taken. Unless ...
Page 17 - VQ
17 AQUAZONE THERMOST A T Fig. 9 A — 50 VQ L08 0 -120 w it h C o mpl e te C Cont rols ( T ypica l)
Page 18 - Del
18 AQUAZONE THERMOST A T Fig. 9 B — 50V Q L 080- 1 20 w it h Del u x e D Co n tr o ls ( T yp ic al)
Page 26 - Table 5G — 50VQL160 Blower Performance Data; Table 5H — 50VQL200 Blower Performance Data
26 Table 5G — 50VQL160 Blower Performance Data LEGEND NOTES:1. Due to alternate sheaves, ‘Turns Open’ may vary within ±0.5 turn from the position shown above. 2. Units factory shipped with standard static sheave and drive at 2.5 turns open (5200 cfm at 0.4 in. wg ESP Wet Coil). Other speedsrequire f...
Page 29 - D Control DIP Switches —; The D Control has 2 DIP; Fig. 11 — Low Voltage Field Wiring; Fig. 13 — Typical Aquazone Accessory Wiring
29 D Control DIP Switches — The D Control has 2 DIP switch blocks. Each DIP switch block has 8 switches and islabeled either S1 or S2 on the circuit board. See Fig. 8B, 9Band 10B.DIP SWITCH BLOCK 1 (S1) — This set of switches offersthe following options for D Control configuration:Performance Monito...
Page 30 - D Control Accessory Relay Configurations —; Use the procedure outlined below to initiate proper unit; Operating Limits; line power to all heat pump units.
30 Table 6 — DIP Switch Block S2 — Accessory 1 Relay Options LEGEND NOTE: All other DIP switch combinations are invalid. Table 7 — DIP Switch Block S2 — Accessory 2 Relay Options LEGEND NOTE: All other switch combinations are invalid. Auto Dehumidification Mode or High Fan Mode — Switch 7provides se...
Page 32 - Table 10 — Antifreeze Percentages by Volume; Cooling Tower/Boiler Systems —; These systems; OPERATION; The unit will not operate until all the; Units with AquazoneTM Complete C Control; Output EH2 will be off if FP1 is greater than 45 F AND
32 Alcohols and glycols are commonly used as antifreeze agents. Freeze protection should be maintained to 15 F belowthe lowest expected entering loop temperature. For example, ifthe lowest expected entering loop temperature is 30 F, the leav-ing loop temperature would be 22 to 25 F. Therefore, the f...
Page 33 - SYSTEM TEST; System testing provides the ability to check the control; Test Mode —; To enter Test mode on C or D controls, cycle; Retry Mode —; In Retry mode, the status LED will start to; Table 11 — C Control Current LED Status
33 EMERGENCY HEAT — In Emergency Heat mode, the FanEnable and Fan Speed relays are turned on. The EH1 output isturned on immediately. With continuing Emergency Heat de-mand, EH2 will turn on after 5 minutes. Fan Enable and FanSpeed relays are turned off after a 60-second delay. The controlreverts to...
Page 35 - Fig. 15 — Forced Circulation Method; Fig. 14 — Gravity Flow Method
35 Condenser Cleaning — Water-cooled condensers may require cleaning of scale (water deposits) due to improperlymaintained closed-loop water systems. Sludge build-up mayneed to be cleaned in an open water tower system due toinduced contaminants. Local water conditions may cause excessive fouling or ...
Page 36 - TROUBLESHOOTING; When troubleshooting problems with a WSHP, consider the; Thermistor —; A thermistor may be required for single-; Control Sensors —; The control system employs 2 nom-; Fig. 16 — Thermistor Nominal Resistance; Fig. 17 — FP1 and FP2 Thermistor Location; COAX —
36 TROUBLESHOOTING (Fig. 16 and 17, and Table 14) When troubleshooting problems with a WSHP, consider the following: Thermistor — A thermistor may be required for single- phase units where starting the unit is a problem due to lowvoltage. See Fig. 16 for thermistor nominal resistance. Control Sensor...
Page 37 - Table 14 — Troubleshooting
37 Table 14 — Troubleshooting LEGEND FAULT HEATING COOLING POSSIBLE CAUSE SOLUTION Main Power Problems X X Green Status LED Off Check line voltage circuit breaker and disconnect.Check for line voltage between L1 and L2 on the contactor.Check for 24 VAC between R and C on controller.Check primary/sec...
Page 39 - UNIT VOLTAGE — COOLING OPERATION
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. PC 111 Catalog No. 536-203 Printed in U.S.A. Form 62AQ-1SI Pg CL-1 7-99 Replaces: New Book 1 1 1 4 4 4 Tab 1a 1b 5a 5a 6a 6b CL-1 50HQL,VQL START-UP CHEC...
Page 40 - HEATING CYCLE ANALYSIS
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. PC 111 Catalog No. 535-00096 Printed in U.S.A. Form 50H,V-9SI Pg CL-2 6-03 Replaces: 50H,V-8SI Book 1 4 Tab 5a 5a Copyright 2003 Carrier Cor poration - -...