Page 3 - Remote operating mode with volt-free contacts
3 Interface access, sizes 026-033 Remote operating mode with volt-free contacts (standard) A simple two-wire communication bus between the RS485 port of the Aquasnap and the Carrier Comfort Network offers multiple remote control, monitoring and diagnostic possibilities. Carrier offers a vast choice ...
Page 4 - Eurovent qualification programmes; Options and accessories
4 Eurovent qualification programmes 30RB/RQ 017-033 Programme Operating mode Operating conditions Class A criteria 30RB 30RQ Outside air temperature, °C Water temperature, °C Air conditioning Cooling mode 35 12/7 3.1 X X Heating mode 7/6 40/45 3.2 - X Heating/cooling floors Cooling mode 35 23/18 3.8...
Page 5 - Physical data, 30RB units
5 Physical data, 30RB units 30RB 017 021 026 033 Data at Eurovent LCP/A/AC conditions*Nominal cooling capacity, standard unit kW 16.5 21.6 27.6 33.6 Power input kW 5.25 6.64 8.52 9.74 EER kW/kW 3.15 3.25 3.24 3.45 Eurovent class, cooling - A A A A ESEER part-load performance kW/kW 3.61 3.64 3.64 3.8...
Page 6 - Physical data, 30RQ units
Physical data, 30RQ units 30RQ 017 021 026 033 Data at Eurovent LCP/A/AC conditions*Nominal cooling capacity, standard unit kW 16.1 20.4 27 33 Power input kW 4.92 6.3 8.62 9.84 EER kW/kW 3.28 3.24 3.13 3.36 Eurovent class, cooling - A A A A ESEER part-load performance kW/kW 3.76 3.60 3.51 3.76 Nomin...
Page 7 - Operating limits; Water heat exchanger water flow rate
7 Electrical data, 30RB/RQ units 30RB/RQ 017 021 026 033 Power circuit Nominal power supply V-ph-Hz 400-3-50 Voltage range V 340-440 Control circuit supply 24 V via internal transformer Maximum start-up current (Un)* A 75 95 118 118 Unit power factor at nominal capacity** 0.84 0.79 0.77 0.81 Maximum...
Page 8 - Dimensions/clearances
8 Dimensions/clearances 30RB/RQ 017-021 1 3 2 150 100 100 82 50 50 100 651 706 794 281 162 200 mm 300 mm 300 mm 200 mm 200 mm 200 mm 200 mm 400 mm 400 mm 400 mm 400 mm 500 mm 700 mm 700 mm 1000 mm 1000 mm 660 522 4 1136 1579 584 1579 559 User interface Service panel Disconnect switch Fixing holes ø ...
Page 10 - Part load performances; ESEER (European seasonal energy efficiency ratio); Part-load performances in accordance with Eurovent
10 Part load performances With the rapid increase in energy costs and the care about environmental impacts of electricity production, the power consumption of air conditioning equipment has become an important topic. The energy efficiency of a unit at full load is rarely representative of the actual...
Page 11 - Cooling capacities, 30RB units
11 Legend: LWT Leaving water temperature CAP kW Cooling capacity COMP kW Compressor power input UNIT kW Unit power input (compressors, fans and control circuit) COOL l/s Evaporator water flow rate COOL kPa Evaporator pressure drop Application data: Standard units, refrigerant: R410A Evaporator tempe...
Page 12 - Cooling capacities, 30RQ units
1 Cooling capacities, 30RQ units 30RQ 017-033 Condenser entering air temperature, °C 25 30 35 40 45 LWT CAP COMP UNIT COOL COOL CAP COMP UNIT COOL COOL CAP COMP UNIT COOL COOL CAP COMP UNIT COOL COOL CAP COMP UNIT COOL COOL °C kW kW kW l/s kPa kW kW kW l/s kPa kW kW kW l/s kPa kW kW kW l/s kPa kW kW...
Page 13 - Heating capacities, 30RQ units
13 Heating capacities, 30RQ units 30RQ 017-033 Outdoor temperature, °C -15 -7 0 7 15 LW T CAP* CAP** COMP UNIT COND CAP* CAP** COMP UNIT COND CAP* CAP** COMP UNIT COND CAP* CAP** COMP UNIT COND CAP* CAP** COMP UNIT COND °C kW kW kW kW l/s kPa kW kW kW kW l/s kPa kW kW kW kW l/s kPa kW kW kW kW l/s k...
Page 14 - Typical hydronic circuit diagram
14 Hydronic module Typical hydronic circuit diagram The hydronic module reduces the installation time. The unit is factory-equipped with the main hydronic components required for the installation: screen filter, water pump, expansion tank, safety valve and pressure gauge. The water heat exchanger an...
Page 15 - Available static system pressure
15 60 80 100 120 140 160 180 200 220 240 260 280 300 0 0,5 1,0 1,5 2,0 2,5 1 2 3 4 5 Available static system pressure 30RB/RQ 017-033 Available static pressure, kPa Water flow rate, l/s Legend 1. 30RB/RQ 017 2. 30RB/RQ 021 3. 30RB 026 4. 30RB 033 - 30RQ 026 5. 30RQ 026