Carrier Air Conditioner - Manuals
Carrier Air Conditioner – Manual in PDF format online.
Manuals:
Manual Carrier Air Conditioner
Summary
4 Control Module Communication RED LED — Proper operation of the control boards can bevisually checked by looking at the red status LEDs (light-emitting diodes). When operating correctly, the red statusLEDs should be blinking in unison at a rate of once every2 seconds. If the red LEDs are not blinki...
10 CEPL130346-01 STATUS LEN J1 J2 J4 J3 J5 J6 J7 J8 J9 J10 CCN RED LED - STATUS GREEN LED -LEN (LOCAL EQUIPMENT NETWORK) YELLOW LED -CCN (CARRIER COMFORT NETWORK) INSTANCE JUMPER EMERGENCY ON/OFFSWITCH ENABLE/OFF/REMOTECONTACT SWITCH GFI-CONVENIENCEOUTLET ACCESSORYON 208/230V 460 AND575V ONLY RESET ...
11 OPERATING DATA Sensors — The electronic control uses 4 to 10 thermistors to sense temperatures for controlling chiller operation. SeeTable 2. These sensors are outlined below. See Fig. 7-10 forthermistor locations. Thermistors T1-T9 are 5 k Ω at 77 F (25 C). Thermistors T1, T2, T3-T6 and T7-T9 ha...
12 *When thermistor is viewed from perspective where the compressor is on the left and the cooler is on the right. Fig. 8 — Thermistor T3 and T4 Locations 040-070 080-110 AND ASSOCIATED MODULAR UNITS* 130-210 AND ASSOCIATED MODULAR UNITS*
13 Fig. 9 — Compressor Thermistor Locations (T7 and T8) LEGEND EXV — Electronic Expansion Valve Fig. 10 — Typical Thermistor Location (30GTN,R and 30GUN,R 210, 315A, 390A, 420A/B Shown)
14 T10 — REMOTE SPACE TEMPERATURE SENSOR — Sensor T10 (part no. HH51BX006) is an accessory sensor thatis remotely mounted in the controlled space and used for spacetemperature reset. The sensor should be installed as awall-mounted thermostat would be (in the conditioned spacewhere it will not be sub...
16 Electronic Expansion Valve (EXV) (SeeFig. 15) — Standard units are equipped with a bottom seal EXV. This device eliminates the use of the liquid line solenoidpumpdown at unit shutdown. An O-ring has been added to bot-tom of orifice assembly to complete a seal in the valve on shut-down. This is no...
17 The capacity control algorithm runs every 30 seconds. The algorithm attempts to maintain the leaving chilled water tem-perature at the control point. Each time it runs, the control readsthe entering and leaving fluid temperatures. The control deter-mines the rate at which conditions are changing ...
18 Table 5A — Part Load Data Percent Displacement, Standard Units *Unloaded compressor. NOTE: These capacity control steps may vary due to lag compressor sequencing. UNIT 30GTN,R 30GUN,R CONTROL STEPS LOADING SEQUENCE A LOADING SEQUENCE B % Displacement (Approx) Compressors % Displacement (Approx) C...
19 Table 5A — Part Load Data Percent Displacement, Standard Units (cont) *Unloaded compressor. NOTE: These capacity control steps may vary due to lag compressor sequencing. UNIT 30GTN,R 30GUN,R CONTROL STEPS LOADING SEQUENCE A LOADING SEQUENCE B % Displacement (Approx) Compressors % Displacement (Ap...
26 ADDING ADDITIONAL UNLOADERS — See Table 6 below for required hardware. Follow accessory instructions for installation. Connect un- loader coil leads to PINK wires in compressor A1/B1 junctionbox. Configuration items CA.UN and CB.UN in the OPT1sub-mode of the configuration mode must be changed to ...
27 Low Cooler Suction Temperature — To avoid freezing thecooler, the control will compare the circuit Cooler Suction tem-perature (T5/T6) with a predetermined freeze point. If the cool-er fluid selected is Water, the freeze point is 34 F (1.1 C). If thecooler fluid selected is Brine, the freeze poin...
28 *Control box.†Fan numbers 11 and 12 do not apply to 30GTN,R and 30GUN,R 130-170 and associated modular units (see Table 1). Fig. 18 — Condenser Fan Sequence FAN ARRANGEMENT FAN NO. FAN RELAY NORMAL CONTROL 30GTN,R040-05030GUN,R040-050 1 — Compressor No. A1 2 — Compressor No. B1 3 1 First Stage of...
29 Marquee Display Usage (See Fig. 19 andTables 7-25) — The Marquee display module provides the user interface to the ComfortLink™ control system. The dis-play has up and down arrow keys, an key, and an key. These keys are used to navigate through the dif- ferent levels of the display structure. See...
30 Table 7 — Marquee Display Menu Structure LEGEND Ckt — Circuit RUN STATUS SERVICE TEST TEMPERATURES PRESSURES SET POINTS INPUTS OUTPUTS CONFIGURATION TIME CLOCK OPERATING MODES ALARMS Auto Display(VIEW) Manual Mode On/Off (TEST) Unit Temperatures (UNIT) Ckt A Pressures (PRC.A) Cooling (COOL) Unit ...
31 Table 8 — Run Status Mode and Sub-Mode Directory SUB-MODE KEYPAD ENTRY ITEM RANGE ITEM EXPANSION COMMENT VIEW EWT 0 - 100 F (–18 - 38 C) ENTERING FLUID TEMP LWT 0 - 100 F (–18 - 38 C) LEAVING FLUID TEMP SETP 0 - 100 F (–18 - 38 C) ACTIVE SETPOINT CTPT 0 - 100 F (–18 - 38 C) CONTROL POINT STAT 0 -...
32 Table 9 — Service Test Mode and Sub-Mode Directory LEGEND EXV — Electronic Expansion Valve SUB-MODE KEYPAD ENTRY ITEM RANGE ITEM EXPANSION COMMENT TEST TEST OFF-ON SERVICE TEST MODE Use to Enable/Disable Manual Mode OUTS LLS.A OPEN-CLSE LIQ. LINE SOLENOID VALVE TXV units only EXV.A 0 - 100% EXV %...
42 Table 23 — Operating Modes MODE NO. ITEM EXPANSION DESCRIPTION 01 FSM CONTROLLING CHILLER Flotronic™ System Manager (FSM) is controlling the chiller. 02 WSM CONTROLLING CHILLER Water System Manager (WSM) is controlling the chiller. 03 MASTER/SLAVE CONTROL Lead/Lag Chiller control is enabled. 04 L...
43 Table 24 — Alarms Mode and Sub-Mode Directory Table 25 — Example of Reading and Clearing Alarms Temperature Reset — The control system is capable of handling leaving-fluid temperature reset based on return coolerfluid temperature. Because the change in temperature throughthe cooler is a measure o...
44 Table 26 — Configuring Temperature Reset The following are examples of outdoor air and space tem- perature resets: MODE KEYPAD ENTRY SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION COMMENT CONFIGURATION DISP TEST ON/OFF TEST DISPLAY LEDS UNIT TYPE UNIT TYPE OPT1 FLUD COOLER FLUID OPT2 CTRL CONT...
45 Cooling Set Point (4 to 20 mA) — A field supplied and generated, externally powered 4 to 20 mA signal can beused to provide the leaving fluid temperature set point. Connectthe signal to TB6-3,5 (+,–). See Table 27 for instructions to enable the function. Figure 22 shows how the 4 to 20 mA sig-nal...
46 Demand Limit — Demand Limit is a feature that allows the unit capacity to be limited during periods of peak energyusage. There are 3 types of demand limiting that can be config-ured. The first type is through 2-stage switch control, whichwill reduce the maximum capacity to 2 user-configurable per...
47 TROUBLESHOOTING Compressor Protection Control System(CPCS) Board — The compressor protection board con- trols the compressor and compressor crankcase heater. The ground current protection is provided by the compres- sor board. The large relay located on the board is used to provide a feedback sig...
48 2. Make sure that thermistor leads are connected to the proper pin terminals at the J5 connector on EXV boardand that thermistor probes are located in proper positionin the refrigerant circuit. When these checks have been completed, the actual opera- tion of the EXV can be checked by using the pr...
49 Table 29 — Alarm and Alert Codes ALARM/ ALERT CODE ALARM OR ALERT DESCRIPTION WHY WAS THIS ALARM GENERATED? ACTION TAKEN BY CONTROL RESET METHOD PROBABLE CAUSE T051 Aler t Circuit A, Compressor 1Failure Compressor feedback signal does not match relay state Circuit A shut down. Manual High-pressur...
53 SERVICE Electronic Components CONTROL COMPONENTS — Unit uses an advanced elec-tronic control system that normally does not require service.For details on controls refer to Operating Data section.30GTN,R AND 30GUN,R 040-110, AND 230B-315BUNIT CONTROL BOX — When facing compressors, maincontrol box ...
54 7. Remove the liquid lines by breaking the silver-soldered joints at the cooler liquid line nozzles. 8. On 30GTN,GTR and 30GUN,R 080-110 and 230B-315B units, remove the vertical support(s) under the condensercoil in front of the cooler. Provide temporary support asneeded. Save all screws for rein...
56 3. Apply torque in one-third steps until required torque is reached. Load all bolts to each one-third step before pro-ceeding to next one-third step. 4. No less than one hour later, retighten all bolts to required torque values. 5. After refrigerant is restored to system, check for refriger- ant ...
57 Enviro-Shield™ Coil Cleaner Application Equipment • 2 1 / 2 Gallon Garden Sprayer • Water Rinse with Low Velocity Spray Nozzle Enviro-Shield Coil Cleaner Application Instructions• Although Enviro-Shield Coil cleaner is harmless tohumans, animals, and marine life, proper eye protectionsuch as safe...
58 Refrigerant Feed Components — Each circuit has all necessary refrigerant controls.ELECTRONIC EXPANSION VALVE (EXV) — A cut-away view of valve is shown in Fig. 30. High-pressure liquid refrigerant enters valve through bot- tom. A series of calibrated slots have been machined in side oforifice asse...
59 Thermistors — Electronic control uses 4 to 10 ther- mistors to sense temperatures used to control the operation ofchiller. Thermistors T1-T9 vary in their temperature vs resistance and voltage drop performance. Thermistor T10 is a 10 k Ω in- put channel and has a different set of temperature vs r...
60 Table 32A — 5K Thermistor Temperature (F) vs Resistance/Voltage VOLTAGE DROP A FOR THERMISTORS T1, T2, T7-T9 VOLTAGE DROP B FOR THERMISTORS T3-T6 TEMP (F) VOLTAGE DROP A (V) VOLTAGE DROP B (V) RESISTANCE (Ohms) –25 3.699 4.538 98,010 –24 3.689 4.523 94,707 –23 3.679 4.508 91,522 –22 3.668 4.493 8...
64 Safety Devices — Chillers contain many safety devices and protection logic built into electronic control. Following is abrief summary of major safeties.COMPRESSOR PROTECTIONCircuit Breaker — One manual-reset, calibrated-trip magneticcircuit breaker for each compressor protects against overcur-ren...
65 Relief Devices — Fusible plugs are located in each cir- cuit to protect against damage from excessive pressures.HIGH-SIDE PROTECTION — One device is located between condenser and filter drier; a second is on filter drier.These are both designed to relieve pressure on a temperaturerise to approxim...
66 START-UP AND OPERATION NOTE: Refer to Start-Up Checklist on pages CL-1 to CL-8. Actual Start-Up — Actual start-up should be done only under supervision of a qualified refrigeration mechanic. 1. Be sure all service valves are open. Units are shipped from factory with suction, discharge, and liquid...
67 Consult application data section in the Product Data litera- ture and job design requirements to determine flow rate re-quirements for a particular installation. Table 36 — Nominal and Minimum Cooler Fluid Flow Rates LEGEND *Nominal flow rates required at ARI conditions are 44 F (6.7 C) leaving-f...
68 LEGEND FOR FIG. 36-41 ALM — Alarm CWFS — Chilled Water Flow Switch CWP — Chilled Water Pump CWPI — Chilled Water Pump Interlock CXB — Compressor Expansion Board HGBPS — Hot Gas Bypass Switch LWT — Leaving Fluid Temperature MBB — Main Base Board OAT — Outdoor-Air Temperature Sensor SPT — Remote Sp...
71 APPENDIX A — CCN TABLES UNIT (Configuration Settings) OPTIONS1 (Options Configuration) *Unit size dependent. DESCRIPTION STATUS DEFAULT UNITS POINT 1 Unit Type 1 = Air Cooled2 = Water Cooled3 = Split System4 = Heat Machine5 = Air Cooled Heat Reclaim 1 UNIT_TYP 2 Unit Size 20 to 300 * TONS SIZE 3 ...
73 APPENDIX A — CCN TABLES (cont) RESETCON (Temperature Reset and Demand Limit) BRODEFS (Broadcast POC Definition Table) DESCRIPTION STATUS DEFAULT UNITS POINT 1 COOLING RESET 2 Cooling Reset Type 0 = No Reset1 = 4-20 ma input2 = External temp-OAT3 = Return fluid4 = External temp-SPT 0 CRST_TYP 3 No...
79 APPENDIX A — CCN TABLES (cont) CSM/FSM EQUIPMENT TABLE (Type 621H, Block 2) WSM EQUIPMENT PART COOL SOURCE MAINTENANCE TABLE SUPERVISOR MAINTENANCE TABLE OCCUPANCY MAINTENANCE TABLE OCCUPANCY SUPERVISORY LINE DESCRIPTION POINT 1 Chiller Status0 = Chiller is off1 = Valid run state in CCN mode 2 = ...
80 APPENDIX B — FLUID DROP PRESSURE CURVES Cooler Fluid Pressure Drop Curves — 30GUN,GUR040-110 ENGLISH AND SI LEGEND NOTE: Ft of water = 2.31 x change in psig. — 040 — 045,050
81 APPENDIX B — FLUID DROP PRESSURE CURVES (cont) Cooler Fluid Pressure Drop Curves — 30GUN,GUR130-210 ENGLISH SI COOLER PRESSURE DROP KEY 1 — 30GUN,GUR130,150 2 — 30GUN,GUR170,190 3 — 30GUN,GUR210 NOTE: Ft of water = 2.31 x change in psig.
83 APPENDIX B — FLUID DROP PRESSURE CURVES (cont) Cooler Fluid Pressure Drop Curves — 30GUN,GUR230B-315B ENGLISH AND SI COOLER PRESSURE DROP KEY 1 Module B — 30GUN,GUR230,245 2 Module B — 30GUN,GUR255,290,315 NOTE: Ft of water = 2.31 x change in psig.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. PC 903 Catalog No. 563-025 Printed in U.S.A. Form 30GTN-3T Pg 88 3-00 Replaces: 30GTN-2T Book 2 Tab 5c Copyright 2000 Carrier Cor poration SERVICE TRAINI...
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. PC 903 Catalog No. 563-025 Printed in U.S.A. Form 30GTN-3T Pg CL-1 3-00 Replaces: 30GTN-2T Book 2 Tab 5c C U T A L ONG DO TT ED L INE CUT A L ONG D O T T...
CL-2 B. Preliminary Equipment Check (Check box if complete) IS THERE ANY SHIPPING DAMAGE? IF SO, WHERE _________________________________________________________________________________________ WILL THIS DAMAGE PREVENT UNIT START-UP? HAVE COMPRESSOR BASE RAIL ISOLATORS ALL BEEN PROPERLY ADJUSTED? CHE...
CL-6 C. Unit Start-Up (cont) PRESS ESCAPE KEY TO DISPLAY ‘RSET’. PRESS DOWN ARROW KEY TO DISPLAY ‘SLCT’.PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW: SLCT (Heating Cooling Setpoint Select) PRESS ESCAPE KEY SEVERAL TIMES TO GET TO THE MODE LEVEL (BLANK DISPLAY). USE THEARROW KEYS TO SCROLL...
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. PC 903 Catalog No. 563-025 Printed in U.S.A. Form 30GTN-3T Pg CL-8 3-00 Replaces: 30GTN-2T Book 2 Tab 5c Copyright 2000 Carrier Cor poration All Units: M...
Carrier Manuals
-
Carrier 58CTA09010016
User Manual
-
Carrier 58CTA09010016
Installation Manual
-
Carrier 58STX07010016
User Manual
-
Carrier 58STX07010016
Installation Manual
-
Carrier 58DLA09010016
User Manual
-
Carrier 58DLA09010016
Installation Manual
-
Carrier 58CVX10010020
User Manual
-
Carrier 58CVX10010020
Installation Manual
-
Carrier 58CTA04510008
User Manual
-
Carrier 58CTA04510008
Installation Manual
-
Carrier 58CTX13510016
User Manual
-
Carrier 58CTX13510016
Installation Manual
-
Carrier 58STX09010014
User Manual
-
Carrier 58STX09010014
Installation Manual
-
Carrier 58CVA090---11116
User Manual
-
Carrier 58CVA090---11116
Installation Manual
-
Carrier 58CVA070---15112
User Manual
-
Carrier 58CVA070---15112
Installation Manual
-
Carrier 58DLX09010016
User Manual
-
Carrier 58DLX09010016
Installation Manual