Page 2 - SPECIFICATIONS; Heating Capacity and Efficiency
2 SPECIFICATIONS Heating Capacity and Efficiency 060-14 080-14 100-20 120-22 Input Maximum Heat (BTUH) 60,000 80,000 100,000 120,000 Intermediate Heat (BTUH) 39,000 52,000 65,000 78,000 Minimum Heat (BTUH) 24,000 32,000 40,000 48,000 Output Maximum Heat (BTUH) 59,000 78,000 97,000 117,000 Intermedia...
Page 3 - MODEL NUMBER NOMENCLATURE; FURNACE COMPONENTS
3 MODEL NUMBER NOMENCLATURE 59 M N 7 A 060 V 17 -- -- 14 S - Single StageT - Two StageM - Modulating C - ComfortP - PerformanceN - Infinity 0 --- 90 AFUE3 --- 93 AFUE5 --- 95 AFUE6 --- 96 AFUE7 --- 97 AFUE S - StandardE - Energy EfficientV - Variable Speed 14 - 14.2”17 - 17.5”21 - 21.0”24 - 24.5” 08...
Page 4 - ACCESSORIES
4 ACCESSORIES DESCRIPTION PART NUMBER 060-14 080-14 100-20 120-22 Venting, Drainage and Installation Vent Kit - Through the Cabinet KGADC0101BVC X X X X Vent Terminal - Concentric - 2” (51 mm) KGAVT0701CVT X X X N/A Vent Terminal - Concentric - 3” (76 mm) KGAVT0801CVT X X X X Vent Terminal Bracket -...
Page 7 - FOR EACH; long radius elbows and a concentric vent kit.; EACH
7 MAXIMUM EQUIVALENT VENT LENGTH -- FT. (M) NOTE: Maximum Equivalent Vent Length (MEVL) does NOT include elbows or terminations. Use Table 2 - Deductions from Maximum Equivalent Vent Length to determine allowable vent length for each application. Table 1 – Maximum Equivalent Vent Length -- Ft. (M) 0...
Page 10 - RETURN AIR TEMPERATURE; C) db or intermittent operation down to 55; SUPPLY AIR; MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS; ELBOW; NOTE
10 RETURN AIR TEMPERATURE This furnace is designed for continuous return--air minimum temperature of 60 _ F (15 _ C) db or intermittent operation down to 55 _ F (13 _ C) db such as when used with a night setback thermometer. Return--air temperature must not exceed 80 _ F (27 _ C) db. Failure to foll...
Page 11 - DOWNFLOW SUBBASE; Assembled; Concentric Vent Kit
11 DOWNFLOW SUBBASE A97427 Assembled A88207 Disassembled LOCATING TAB LOCATING TAB 1 2 3 4 4 3 2 1 B D C A 1 1 / 4 " TYP PLENUM OPENING FACTORY-SUPPLIED FIELD-INSTALLED INSULATION DIMENSIONS (IN. / MM) FURNACE CASING WIDTH FURNACE IN DOWNFLOW APPLICATION PLENUM OPENING* FLOOR OPENING HOLE NO. FO...
Page 12 - MEDIA FILTER CABINET; Furnace Side; TYPICAL WIRING SCHEMATIC
12 MEDIA FILTER CABINET Furnace Side Centerline Screw Slots 23-3/4” 23-3/8” 23-5/8" 5 3 4 Duct Side Opening Opening with Flanges Bent 24-1/4” 25-5/8" B Opening A " (600mm) (594mm) (603mm) (146mm) (651mm) (616mm) 23-1/8” (588mm) A11456A DIMENSIONS (IN. / MM) MEDIA FILTER CABINET A B SHIPP...
Page 13 - DIMENSIONAL DRAWING; NOT
13 DIMENSIONAL DRAWING 6 15/16 [176.1] 3 [76.2] 3 [76.2] 6 11/16 [170.1] 23 5/16 [592.9] 25 1/8 [638.7] 26 3/8 [670.0] 26 11/16 [678.1] 21 [534.0] 26 5/16 [668.8] 17 5/16 [439.2] 16 9/16 [420.9] 20 1/4 [513.9] 25 3/16 [639.1] 28 3/16 [715.9] 28 5/8 [726.4] 32 5/8 [829.5] 28 3/4 [730.5] 26 3/8 [370.0...
Page 14 - GUIDE SPECIFICATIONS; General
14 GUIDE SPECIFICATIONS General System Description Furnish a ______________________ 4--way multipoise gas--fired condensing furnace for use with natural gas or propane (factory--authorized conversion kit required for propane); furnish cold air return plenum; furnish external media cabinet for use wi...