Page 2 - Table 2 — Dimensions; апЭ; Physical Data
Table 2 — Dimensions апЭ Physical Data MODEL NO. 58GS 125 SERIES 100 200 300 400 100 200 300 300 DIMENSIONS* (in.) Width A 2 1 2 1 2 1 2 4 - 1 / 2 2 4 - 1 / 2 2 4 - 1 / 2 2 4 - 1 / 2 3 1 - 1 / 2 Depth B 2 8 - 1 / 2 2 8 - 1 / 2 2 8 - 1 / 2 2 8 - 1 / 2 2 8 - 1 / 2 2 8 - 1 / 2 2 8 - 1 / 2 2 8 - 1 / 2 H...
Page 3 - NOTES FOR LABEL WIRING DIAGRAMS; ©Cp; JL; Jl; Fig. 2 — Heating and Cooljng Application Wiring Diagram
CAUTION: Use copper or copper-dad aluiai- num conductors only. Use a separate branch electrical circuit for this furnace. A disconnect ing means must be located within sight of, and readily accessible to, the furnace. See Fig. 2 for wiring diagram showing the proper field high- and low-voltage wiri...
Page 7 - Fig. 6 — Printed Circuit Control Center; Fig. 7 — Filter Installed for Bottom Inlet; when bottom inlet is used.; Fig. 8 — Filter Installed for Side Inlet
PRINTED-CIRCUIT CONTROL CENTER — Each furnace features a printed-circuit control center to aid the installer and serviceman when installing and servicing the unit. See Fig. 6. A low-voltage terminal board is marked for easy con nection of field wiring and accessories. w c ^ ^ ^ ^ Fig. 6 — Printed C...
Page 8 - igniter ceases to spark
BOTTOM CLOSURE PANEL — When the side inlet is used, the bottom opening must be properly sealed by installing a bottom closure panel shipped under the filter in each furnace. To install the bottom closure panel, perform the following steps: 1 . After filter has been installed for side return, remove...
Page 9 - rtot; bjpass tììc fusible element; etemeut vwth au idejRîicaîpari; Starting Procedure
# m OVERHEAT FUSE LINK — The furnace is equipped with a fusible element to protect against overtemperature conditions in the vestibule that can result from inadequate combustion air supply. WARNÌNG: 0o rtot bjpass tììc fusible element 4ÏÎÉ: ob&îÏÊCtéd betwëèù tbe ÌKmti;|ÌIIÌ l ì ii;i©pe}3Sÿi)Sîa...
Page 10 - Limit Control Safety Check
d. Multiply cu ft per hour times heating value of gas (Btu/cu ft). Obtain heating value of gas from local utility. X heat value of gas = gas input, Btuh Example: Time for one revolution of 2 eu ft dial = 72 seconds. Heat value of gas = 1070 Btu/cu ft 3600 72 X 2 = 100 cu ft/hr 100 X 1070 = 107,000 B...
Page 11 - SERVICE; oft; Air Filter
SERVICE CAUTION: Tixe abüîty to properly perform maintenance on this equipment requires certain mechanical skills and tools. If yott are at all uncertain, contact your Carrier deaier lor qualified maintenance and .service.. Regular maintenance, exercised with care, results in more efficient operatin...
Page 12 - Cleaning Heat Exchanger; Fig. 13 — Removing Baffles; NOTE: There may be more than one electrical
8. Remove bolts holding motor mount to blower housing and slide motor and mount out of housing. Some motors have a ground wire attached to blower housing: disconnect it also. 9. Lubricate motor. a. Remove dust caps or plugs from oil ports located at each end of motor. b. Use a good grade of SAE 20 n...
Page 14 - Table 4 — Trouble Analysis Chart; WARNING: Turn off gas and power supply to ur»it before servicing.; test
Table 4 — Trouble Analysis Chart WARNING: Turn off gas and power supply to ur»it before servicing. (Unless specific test requires gas and electrical supplies.} CAUSE No spark at electrode Blower operates continuously Inadequate heating Aldehyde odors, (CO), sooting flame — floating flame Spark short...