Carrier 58 Series- Manuals

Carrier 58 Series– User Manual in PDF format online.

Manuals:

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8

Summary

Page 2 - confined or unconfined space. An unconfined space; Furnaces in Confined Spaces (Typical Furnace

The draft hood relief air supply must be in the same atmospheric pressure zone as the combustion air inlet supply to the furnace. When a furnace is installed so that supply ducts carry air to areas outside the space containing the furnace, the return air must also be handled by duct(s) sealed to the...

Page 3 - only if it connects directly to outside air. The

RETURN OR SUPPLY AIR VENT TO ROOF I I I I I I I I i T D_L 12 IN MAX I -d ■= I so IN. ~ PER 1000 BTUH* INTERIOR HEATED SPACE -6IN MIN (FRONT) ISO IN # per 1000 HTBTUH* *-12 IN MAX RETURN OR SUPPLY AIR J *MINIMUM OPENING SIZE IS 100 SO IN MAKEUP AIR ISO IN -PER 5000 BTUH FROM OUTSIDE (RETURN AIR ONLY)...

Page 4 - Fig. 3 — Sediment Trap; size is permissible in pipe run.

GAS PIPING The gas supply line should be a separate line directly from the meter to the furnace, if possible. Refer to Table 1 for recommended gas pipe sizing. Do not use cast-iron or galvanized pipe. Table 1 — Maximum Capacity of Gas Pipe* NOMINAL I R O N PIPE SIZE (in.) Z ’ " 3 / 4 1 T 1 - 1 /...