Page 2 - REQUIRED CLEARANCE FOR OPERATION AND SERVICING
UNIT ELECTRICAL CHARACTERISTICS UNIT WEIGHT UNIT HEIGHT IN. [MM] "A" CENTER OF GRAVITY IN. [MM] lb kg X Y Z 50JS018 208/230-1-60 283 128.4 37.02 [940.3] 19.5 [495.3] 16.8 [425.5] 15.0 [381.0] 50JS024 208/230-1-60 289 131.1 39.02 [991.1] 18.5 [469.9] 16.8 [425.5] 15.0 [381.0] 50JS030 208/230-...
Page 4 - END VIEW; Fig. 4—Roof Curb Dimensions
Before performing service or maintenance operations onsystem, turn off main power to unit. Turn off accessory heaterpower switch if applicable. Electrical shock could causesevere injury or death. Step 1—General The 50JS and 50JX heat pumps are fully self-contained anddesigned for outdoor installatio...
Page 5 - Fig. 5—Unit Leveling Tolerances; Fig. 6—Slab Mounting Detail
INSPECT SHIPMENT — Inspect for shipping damage while unitis still on shipping pallet. If unit appears to be damaged or is tornloose from its anchorage, have it examined by transportationinspectors before removal. Forward claim papers directly totransportation company. Manufacturer is not responsible...
Page 6 - Fig. 8—Suggested Rigging
5. Tighten the tension buckle until it is taut. Lifting brackets must be secure in the handholds. 6. Attach field-supplied clevis or hook of sufficient strength to hole in the lifting bracket (See Fig. 8). 7. Attach the 2 safety straps directly to the clevis or hook at the 4 rigging brackets. DO NOT...
Page 7 - Table 1A—Physical Data; Table 1B—Physical Data
Table 1A—Physical Data UNIT SIZE 50JS018 50JS024 50JS030 50JS036 50JS042 50JS048 50JS060 NOMINAL CAPACITY (ton) 1-1/2 2 2-1/2 2-1/2 3-1/2 4 5 OPERATING WEIGHT (lb) 283 289 287 291 323 353 418 COMPRESSOR QUANTITY 1 TYPE RECIPROCATING COMPRESSOR SCROLL COMPRESSOR REFRIGERANT R-22 REFRIGERANT METERING ...
Page 8 - Step 7—Install Electrical Connections; Use only copper conductor for connections between; Fig. 9—Typical Installation; Fig. 10—50JX with Duct Covers On; Accessory Duct Covers; Fig. 11—Condensate Trap
The units dispose of condensate through a 3/4 in. NPT femalefitting that exits on the compressor end of the unit. Condensatewater can be drained directly onto the roof in rooftop installations(where permitted) or onto a gravel apron in ground level installa-tions. Install a field-supplied condensate...
Page 9 - Fig. 12—Wiring Schematics; LEGEND
Fig. 12—Wiring Schematics A00073 FIELD SPLICETERMINAL (MARKED)TERMINAL (UNMARKED)SPLICESPLICE (MARKED)FACTORY WIRINGFIELD CONTROL WIRINGFIELD POWER WIRINGACCESSORY OR OPTIONALWIRINGTO INDICATE COMMONPOTENTIAL ONLY:NOT TO REPRESENT WIRING AHA ADJUSTABLE HEAT ANTICIPATOR C CONTACTOR CAP CAPACITOR CB C...
Page 10 - Fig. 13—Wiring Schematics
Page 11 - Fig. 14—Wiring Schematics
Fig. 14—Wiring Schematics A00075 FIELD SPLICETERMINAL (MARKED)TERMINAL (UNMARKED)SPLICESPLICE (MARKED)FACTORY WIRINGFIELD CONTROL WIRINGFIELD POWER WIRINGACCESSORY OR OPTIONALWIRINGTO INDICATE COMMONPOTENTIAL ONLY:NOT TO REPRESENT WIRING AHA ADJUSTABLE HEAT ANTICIPATOR C CONTACTOR CAP CAPACITOR CB C...
Page 12 - Table 3A—Electrical Data—50JS
Table 3A—Electrical Data—50JS UNIT 50JS SIZE V-PH-HZ VOLTAGE RANGE COMPRESSOR ODFM IDFM ELECTRIC HEAT POWER SUPPLY Min Max RLA LRA FLA FLA Nominal KW* FLA MCA Max Fuse or CRCT Breaker MOCP 018 208/230-1-60 187 253 9 48 0.9 1.8 -/- 3.8/5 7.5/10 -/- 18.1/20.836.1/41.7 14.0/14.024.8/28.347.4/54.3 20/20...
Page 13 - Table 3B—Electrical Data—50JX
→ Table 3B—Electrical Data—50JX UNIT 50JX SIZE V-PH-HZ VOLTAGE RANGE COMPRESSOR ODFM IDFM ELECTRIC HEAT POWER SUPPLY Min Max RLA LRA FLA FLA Nominal KW* FLA MCA Max Fuse or CRCT Breaker MOCP 024 208/230-1-60 187 253.00 10.8 56 0.90 2 -/- 3.75/5.0 7.5/10 -/- 18.1/20.836.1/41.7 16.4/16.425.1/28.547.6/...
Page 14 - GROUND LUG; Fig. 18—Control Wiring Plate
be in a conduit until they enter the duct panel; conduit terminationat the duct panel must be watertight. Run the high-voltage leadsthrough the power entry knockout on the power entry side panel(See Fig. 2 and 3 for location and size). When the leads are insidethe unit, run leads up the high-voltage...
Page 15 - Fig. 19—Transformer Label; Fig. 20—Fan Blade Clearance
SPECIAL PROCEDURES FOR 208-V OPERATION 1. Disconnect the yellow primary lead (w110) from the trans- former. See unit wiring label (See Fig. 12 through 14). 2. Connect the yellow primary lead (w110) to the transformer terminal labeled 200v. Indoor blower-motor speeds may need to be changed for 208-vo...
Page 16 - Fig. 22—Typical Heat Pump Operation, Cooling Mode; Fig. 21—Typical Heat Pump Operation, Heating Mode
Fig. 22—Typical Heat Pump Operation, Cooling Mode 1. Hot gas from compressor flows through the 4-way valve and is directed to the outdoor coil. It is then condensed and subcooled through the coil circuits. Refrigerant leaves the outdoor coil by way of the OD Accurater in the bypass position to the l...
Page 17 - Table 4A—Wet Coil Air Delivery
2. Place SYSTEM switch in COOL position and FAN switch in AUTO position. Set control below room temperature. Observethat cooling cycle shuts down when control setting is satisfied. 3. Place system switch in HEAT position. Set control above room temperature. Observe that compressor, outdoor fan, andi...
Page 18 - When evaluating the refrigerant charge, an indi-; Table 4B—Wet Coil Air Delivery
The charging label and the tables shown refer to system tempera-tures and pressures in cooling mode only. A refrigerant charginglabel is attached to the outside of the service access door. If chargelevel is suspect in Heating mode, reclaim all refrigerant and chargeto nameplate amount. (This informa...
Page 20 - MAINTENANCE
To change the speed of the blower motor (BM), remove the fanmotor speed leg lead from the blower relay (BR). This wire isattached to IGC terminal BM for single-phase and 3-phase units.To change the speed, remove and replace with lead for desiredblower motor speed. Insulate the removed lead to avoid ...
Page 23 - SYSTEM INFORMATION; Because these switches are attached to refrigeration; Fig. 36—Refrigerant Circuit; FEEDER TUBE
exists, be sure that all supply- and return-air grilles are open andfree from obstructions, and that the air filter is clean. Whennecessary, refer to Indoor Airflow and Airflow Adjustmentssection to check the system airflow. METERING DEVICES — Refrigerant metering devices are fixedorifices and are l...
Page 24 - Table 5—Cooling and Heating Troubleshooting Chart
Table 5—Cooling and Heating Troubleshooting Chart SYMPTOM CAUSE REMEDY Compressor and outdoor fan will not start Power failure Call power company Fuse blown or circuit breaker tripped Replace fuse or reset circuit breaker Defective thermostat, contactor, transformer, con-trol relay or defrost board ...
Page 25 - Cooling and Heating Troubleshooting Chart (cont’d); I. PRELIMINARY INFORMATION
Cooling and Heating Troubleshooting Chart (cont’d) SYMPTOM CAUSE REMEDY Suction pressure too low (Cool) Dirty air filter Replace filter (Heat) Outdoor coil frosted Move timer on control board to 30 min. betweendefrost cycles Low refrigerant charge Check for leaks, repair and recharge Metering device...