Page 2 - Table 1 — Model Number Reference By Application Type; WARNING
2 equipment. Follow all safety codes. Wear safety glasses and work gloves. GENERAL Omnizone™ 50BV indoor packaged units are very flexible for a variety of applications. These self-contained units are available as water-cooled or remote air-cooled air conditioning units. The 50BV units are available ...
Page 3 - Table 2 — Modular Unit Shipping Table; Step 2 — Rig and Place Unit —; SECTIONS; Fig. 1 — Modular Unit Rigging
3 INSTALLATION Omnizone™ 50BV units are intended for indoor installa- tion only. Determine building alterations required to run piping, wiring, and ductwork. Read all installation instructions before installing the unit. Step 1 — Complete Pre-Installation Checks EXAMINE THE UNIT — Examine the unit f...
Page 19 - Fig. 15 — Typical Fan Discharge Connections for
19 ACOUSTICAL CONSIDERATIONS — Proper acoustical considerations are a critical part of every system’s design and operation. Each system design and installation should be reviewed for its own unique requirements. For job specific requirements, contact an acoustical consultant for guidance and recomme...
Page 20 - Fig. 16 — Duct Static Pressure Probe; Fig. 17 — Display Panel Location on Unit Front Panel
20 acceptable system static pressure. If the existing duct system is too small, larger ductwork must be installed. The duct system and diffusers should be sized to handle the design airflow volumes quietly. To maximize sound attenuation of the unit's blower(s), the supply and return air plenums shou...
Page 21 - Step 4 — Make Piping Connections; Table 4 — Glycol Freezing Points; CAUTION; Ethylene Glycol; Fig. 18 — DHS Pressure Limit Location
21 Step 4 — Make Piping Connections CONDENSER WATER PIPING (Water-Cooled Only) — Always follow national and local codes when installing water piping to ensure a safe and proper installation. Connections to the unit should incorporate vibration eliminators to reduce noise and vibration to the buildin...
Page 22 - Table 5A — Condenser Pressure Drop; Table 5B — Condenser Pressure Drop; LEGEND; VPACBuilder; FLOW RATE; Flow Rate; FLOW RATE; Flow Rate; Fig. 20 — Condensate Drain Layout
22 Table 5A — Condenser Pressure Drop 50BVC,J,Q Units LEGEND Table 5B — Condenser Pressure Drop 50BVT,V,W Units LEGEND Pressure and temperature ports are recommended in both the supply and return lines for system flow balancing. These openings should be 5 to 10 pipe diameters from the unit water con...
Page 23 - motor; Fig. 21 — Optional Water Economizer
23 Table 6A — Hot Water Pressure Drop 50BVC,E,J,K,Q Units LEGEND Table 6B — Hot Water Pressure Drop 50BVT,U,V,W,X Units LEGEND Pipe sizes should be selected based on the head pressure available from the pump. Water velocity should not exceed 8 fps. Design the piping system for approximately 3 ft of ...
Page 24 - Step 5 — Complete Electrical Connections —
24 Table 7B — Economizer Pressure Drop Curve (ft wg), 50BVT,U,V,W,X Units LEGEND REMOTE REFRIGERANT PIPING (Remote Air-Cooled Only) — Carrier 50BVE,K,U,X units are supplied without condensers. To complete the installation, these units must be field connected to a suitable remote condenser. The 50BV ...
Page 27 - FAN RELAY; Fig. 24 — Typical Wiring 18 to 30 Ton Units
27 Modular Units — For units with multiple main air- conditioning sections, connect the high voltage compressor power wiring to the line side of the high voltage terminal block in the second section’s high voltage electrical box. This wiring is located in the upper portion of the compressor compartm...
Page 28 - Table 10 — Recommended Cables; MANUFACTURER; Fig. 26 — Field Terminal Block; FIELD-SUPPLIED THERMOSTAT; Remote Condenser Units Only; FC —
28 Table 10 — Recommended Cables NOTE: Conductors and drain wire must be at least 20 AWG (American Wire Gage), stranded, and tinned copper. Individual conductors must be insulated with PVC, PVC/nylon, vinyl, Teflon ® *, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of P...
Page 29 - CSMUX; Fig. 27 — Modular Unit VAV Control Panel
29 TRANS-1 PCB1 TB2 CSMUX PCB1 TB2 TRANS-1 Fig. 27 — Modular Unit VAV Control Panel Fig. 28 — Single-Piece Unit VAV Control Panel Fig. 29 — Supply/Return Air Temperature Sensor (P/N HH79NZ043) Fig. 30 — Supply-Air Temperature Sensor Installation (Unit Discharge Location) a50-7275ef a50-7276ef a39-18...
Page 30 - General —; Wait 24 hours before starting the compressors to permit; Fig. 31 — Return Air Temperature Sensor
30 Table 11 — Thermistor Resistance vs Temperature Values for Supply-Air Temperature Sensor (10 Kilo- ohm) SMOKE DETECTOR/FIRE ALARM SHUTDOWN (FSD) — To allow a smoke detector to shut the 50BV down, remove the jumper from FSD to C and wire these terminals to a set of normally closed contacts on the ...
Page 31 - Italics
31 when it starts. Also, no cooling will be produced at the evaporator. If any of these conditions occurs, refer to the Service section to correct the compressor rotation before continuing.INTERNAL WIRING — Check all electrical connections in unit control boxes; tighten as required.RETURN-AIR FILTER...
Page 47 - Table 24 — Configuration Parameters
47 DISPLAY ALARM HISTORY — If the controller is indicat-ing there are alarms, the user can view the alarm history bypressing the button. The LID display will show “Alarm History.” Press . The LID display will show the date and type of alarm. As an example, if the LID display shows:ALARM — 10:55 02-1...
Page 48 - VAV Control and VFD Diagnostics —
48 Sequence of Operation (VAV Only) — The fol- lowing control sequence of operation for the VAV units de- scribes the various sequences that occur depending upon the way an operation is triggered and which software control points are involved.SUPPLY FAN — The supply fan can be activated in any of th...
Page 50 - Fig. 34 — Gravity Flow Method
50 GRAVITY FLOW METHOD (Fig. 34) — Do not add solu- tion faster than the vent can exhaust the generated gases. When condenser is full, allow the solution to remain over- night then drain the condenser and flush with clean water. Fol- low acid manufacturer’s instructions.FORCED CIRCULATION METHOD (Fi...
Page 51 - 0BVE,K Units Matched with 09DK Condensers; Compressor Oil —; Table 26 — Oil Recharge; TROUBLESHOOTING; UNIT SIZE; Fig. 37 — Fan Belt Tension
51 Evaporator Fan Performance Adjustment — To change fan speeds from factory settings: 1. Shut off unit power supply.2. Loosen nuts on the 4 carriage bolts in the mounting base. Using adjusting bolts and plate, slide the motor and remove the belt. 3. Loosen movable-pulley flange setscrew. 4. Screw t...
Page 52 - Table 27 — Run Test Troubleshooting (VAV Units Only); PROBLEM
52 Table 27 — Run Test Troubleshooting (VAV Units Only) NOTE: For more information on VAV controls, refer to the 50BV,XJ Controls Operation and Troubleshooting Manual. PROBLEM POSSIBLE CAUSE Control modules do not have lights when unit power is on. Transformer open. Circuit breaker open. Power wirin...
Page 53 - Table 28 — Unit Troubleshooting
53 Table 28 — Unit Troubleshooting LEGEND PROBLEM POSSIBLE CAUSE CORRECTION PROCEDURE Unit Will Not Start. Loss of unit power Check power source.Check fuses, circuit breakers, disconnect switch.Check electrical contacts. Unit voltage not correct Check and correct. Open fuse Check for short circuit i...
Page 54 - Table 29 — CV Units LED Diagnostic Codes; During unit operation and/or troubleshooting, it; Table 30 — Forcing an Input or Output; DESCRIPTION
54 Table 29 — CV Units LED Diagnostic Codes *Freeze protection and condensate overflow lockout require optionalsensors.NOTE: The main control board has a red LED (light-emitting diode)for fault indication and will blink a code as described above. Countthe number of blinks to determine the lockout co...
Page 59 - CMP; WIRE LEGEND; UNIT; FIELD WIRING
59 L1 L2 L3 T3 T2 COMPR2 CLO2 CURRENT LOOP CC2 T1 L3 L2 L1 COMPR 1 CC1 T2 T3 T1 CURRENT LOOP CLO1 TRANS-1 CBR PCB1 (J1-3) COMMON TBLK BM BM T2 L2 L3 T3 BR L1 T1 T2 L2 L3 T3 BR L1 T1 W VFD E U V R S T2 T3 T1 1 3 2 BYP ASS ) GND 4 5 6 L3 L1 L2 TRANFORMER PRIMAR Y LEAD CLR: - PUR OR YEL - BLK/RED 460 5...
Page 63 - DSP
63 TRANS-1 (24V AC) CBR 1 2 16 3 14 13 12 15 5 4 6 7 10 9 8 11 2 1 3 5 1 2 4 3 8 6 7 10 9 13 12 11 14 15 16 ALARM RED +- + W ARN - - IN OUT SPEED VIA CC P24 CC S1 R SF 5 3 BYP AS VFD1 SF + - CMP1 CLO1 LOGIC 1 2 3 + - CLO2 LOGIC 2 - 1 3 + CMP2 17 18 S 1 3 2 4 V C EWT DHS 5 3 ROCC 5 CDWF 3 5 3 FSD 4 6...
Page 68 - CHECK FAN SPEED AND RECORD.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53500001-01 Printed in U.S.A. Form 50BV-3SI Pg CL-2 10-08 Replaces: 50BV-2SI Copyright 2008 Carrier Corporation - - - - - - - - - - - - - ...