Page 4 - VVu
- Unit Physical Data BK BJ BK BJ BK BJ BK ^ BJ_______ BK 028 034 044 054 064 2335 2610 2440 3660 3155 2888 3298 4030 3305 15 Refrigerant 22 24 1 15 30 18 45 18 40 18 12 24 15 30 18 35 18 40 18 c DC537 lerviceable Hermetic, 1750 Rpn DC337 1 DC537 1 E2150 Е2250 E7265 Е7265 E7175 Е7275 DA824 DA337 DA53...
Page 5 - OPTIONAL TOP HORIZONTAL DISCHARGE; UNIT; IM j; Fig. 1 — Unit Dimensions; ve
OPTIONAL TOP HORIZONTAL DISCHARGE *For optional top-mounted horizontal discharge, use accessory filler panel package as shown DIMENSIONS (ft-in.) UNIT 50BJ.BK 016 024 028 j 034 A 6-8 7- 9V4 B 2-4 2-11V4 C 6-10'/2 8- OVe D 2-0 2-0 E 3-0 3-0 F 1- 3% 1- 8V b G 1- 2% 1- 8% H 1- 4V4 1- 7Vs NOTES: 1 Certi...
Page 6 - Step 6 — Install Fan Motor.
To set up sizes 50BJ,BK028 and 034 units for vertical discharge (Fig. 2): 1. Remove: a. Front, rear and end panels of fan section. b. Upper-rear and end panels of coil section.c. Filters from coil section.d. Fasteners holding filter frame top. Push out frame away from coil section frame. 2. Lift up ...
Page 7 - Proper wire rout; before cot-ttiag mriog to few; not; zm; moviiig parts or sharp
FAN MOTOR POSITION VERTICAL DISCH TOP MOUNTED AIRFLOWFRONT ■ FILTER RACK NOTE.Motor pulley on left side of unit — vertical discharge Motor pulley on right side of unit — horizontal discharge Fig. 3 — Fan and Motor Arrangements 50BJ.BK028.034 Fig. 4 — 50BJ,BK028 and 034 Horizontal Fan Motor Mounting ...
Page 9 - Table 2 — Setscrew Torque Requirements; BOLT SIZE; Fig. 9 — Wire Tie Locations; Fig. 10 — Horizontal Wheel Centering
Table 2 — Setscrew Torque Requirements A VsfmCAL DfSC^íARS£ BOLT SIZE 1 RECOMMENDED (in.) TORQUE (Ib-ft) % 1 15-18 Vs 1 22-25 Fig. 9 — Wire Tie Locations W H E E L # VENTURI 7 SCROLL DIMENSION " d " MUST BE EQUAL ALL AROUND Fig. 10 — Horizontal Wheel Centering Adjust as follows: Units 50BJ,B...
Page 10 - FLOOR 1; Water and Refrigerant Connections
Weatherproof external ductwork, joints and openings with flashing and mastic in accordance with applicable codes. Ducts passing thru an unconditioned space must be insulated and covered with a vapor barrier. Step 10 — Check Return Air Filters Unit 50BJ.BK (016-034 only) Be sure that the filters are ...
Page 11 - Piping Conversion; HXh; Condenser Water Piping; MAXIMUM WORKING
Fig. 13 50BJ024 City Water Condenser Piping Conversion 1X1- i|HXl-RETURN CONNECT TO»rn COMPRESSOR y {X1-— d J o — CONNECT WATER REGULATING VALVE TO COMPRESSOR ^^STRAINER ------l||-C]— SUPPLY D istrainer -Cxi- HXh Nominal supply and return lines must be sized to provide required gallons per minute at...
Page 12 - Step 13 — Install Unit Drain Line; Fig. 18 — Condensate Drain
Table 4 — Recommended Line Sizes (in.) (50BK Condenserless Models) HG — Hot Gas Line (OD in ] L — Liquid Line (OD in ) ‘Sweat connections UNIT 50BK CONN. LENGTH OF LINE (ft) SYSTEM SIZES* 20 40 60-80 L HG L HG L HG L HG 016 — % ^Ve Ve 1'/s ys P/s . ys P/s 024 1 & 2 % Vs Y b ys Ye P/s ys P/s 028 ...
Page 13 - IMPORTANT: ff supply voRage phase «a-; Compressor operation on improper line voltage
Do not use drain line smaller than size listed in Table 5. If required, cut hole in panel for drain line. Piteh drain downward toward an open drain sump. Provide a trap at least 3 in. high with plugged tee for cleaning. Fill trap with water to make an air seal. Observe all sanitary codes. Step 14 — ...
Page 14 - Table 7 — Unit Electrical Data
Table 6 — Maximum Wire Size for Power Terminal Block* VOLTS/PHASE UNIT 50BJ.BK 016 024 028,034 044t 054,064t 208-230/3 2/0 2/0 350 350 500 460/3 2/0 2/0 2/0 350 350 575/3 2/0 2/0 2/0 350 350 *Select wire size per NEC and connect supply wires to factory- supplied pigtail wire connectors tMaximum wire...
Page 16 - Fig. 23 — Fan Belt Alignment
(LEDs) should glow as corresponding cooling stages come on. In addition, indicating lights on cover of aecessory timer eontrol panel should light. ^ NOTE: Depending on job eonditions and dif ferential between setpoint and discharge tem peratures, minimum time for all stages to eome on is 22 minute...
Page 17 - Fig. 24 — Fan Belt Adjustment; Shut off unit power; Fig. 25 — Indoor Air Fan Pulley; tt; Lubrication; Shut off power; Condensate Drains
Step 3 — Matched Set of Belts — Always usematched set of belts. NEVER mix new and used belts andjor mix belts from different manufacturers. Step 4 — Belt Installation: a. Move pulleys together to facilitate belt installa tion. NEVER pry or roll belt on to pulleys as this may cause serious damage to...
Page 18 - Evaporator; Sim oif artd lockout ouit power swply.; A CAUTION
Evaporator Coil — Protect coil when working inside unit. (See screened CAUTION note, page 15.) Remove dirt and debris from evaporator coil as required. Clean with a stiff brush, vacuum cleaner or compressed air. Straighten mashed or bent coil fins with a fin comb of the correct spacing. Table 1 list...
Page 19 - MODEL
CONTROL SEQUENCE All 50BJ,BK Units — The indoor fan circuit breaker (IFCB) must be closed for the control circuit to be energized. When breaker is closed, the SYSTEM light will be on. The 044-064 units are equipped with a switch labeled STANDBY. When switch is closed, the indoor fan contactor (IFC) ...
Page 20 - Tab
For replacement items use Carrier Specified Parts Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations Form 50BJ,BK-4SI Supersedes 50BJ,BK-2SI Printed in U S A 6-83 PC 111 Book 1 Tab 2a Catalog No 535-031