Page 3 - MAXIMUM ALLOWABLE; Fig. 2 — Unit Leveling Tolerances; Fig. 3 — Condensate Drain Pan
3 Step 2 — Field Fabricate Ductwork — Secure all ducts to roof curb and building structure on vertical dischargeunits. Do not connect ductwork to unit. For horizontal applica-tions, field-supplied isolation flanges should be attached to hor-izontal discharge openings and all ductwork should be secur...
Page 4 - Fig. 4 — Rigging Details
4 Step 5 — Install Flue Hood — Flue hood is shipped screwed to the burner compartment access panel. Removefrom shipping location and, using screws provided, install fluehood in location shown in Fig. 5 and 6. For units being installed in California Air Quality Manage- ment Districts which require NO...
Page 5 - Table 1 — Physical Data
5 Table 1 — Physical Data LEGEND *Single phase/three phase. †Indicates automatic reset. **48HJD005-007 and 48HJE004 (72,000 Btuh heat input) units have 2 burners. 48HJE005-007 and 48HJF004 (115,000 Btuh heat input) units and 48HJF005-007 (150,000 Btuh Heat input) units have 3 burners. ††An LP kit is...
Page 6 - Table 1 — Physical Data (cont)
6 Table 1 — Physical Data (cont) LEGEND *Single phase/three phase. †Indicates automatic reset. **48HJD005-007 and 48HJE004 (72,000 Btuh heat input) units have 2 burners. 48HJE005-007 and 48HJF004 (115,000 Btuh heat input) units and 48HJF005-007 (150,000 Btuh Heat input) units have 3 burners. ††An LP...
Page 8 - Step 8 — Adjust Factory-Installed Options; Fig. 7 — Gas Piping Guide (With Accessory; SPACING OF SUPPORTS; NFGC —; STEEL PIPE; Fig. 6 — Flue Hood Details
8 Install conduit through side panel openings indicated in Fig. 5. Route power lines through connector to terminal con-nections as shown in Fig. 8. Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate (also seeTables 2A-2D). On 3-phase units, volt...
Page 9 - Fig. 8 — Power Wiring Connections
9 RACEWAY LOW VOLTAGECONNECTIONS INTEGRATED GAS UNITCONTROLLER (IGC) HOLE IN END PANEL (HIDDEN) Fig. 8 — Power Wiring Connections LEGEND C — Contactor COMPS — Compressors EQUIP — Equipment GND — Ground IFC — Indoor (Evaporator) Fan Contactor NEC — National Electrical Code TB — Terminal Block Fig. 9 ...
Page 12 - Fig. 11 — Accessory Field-Installed Humidistat
12 OPTIONAL DURABLADE ECONOMIZER — The option-al economizer hood assembly is packaged and shipped in thefilter section. Damper blades and control boards are installed atthe factory and the economizer is shipped in the vertical dis-charge position.NOTE: Horizontal discharge block-off plate is shipped...
Page 13 - Fig. 15 — Durablade Economizer Installed in Unit
13 9. Replace outdoor-air opening panel using screws from Step 2. Replace filter access panel. Ensure the filter ac-cess panel slides along the tracks and is securely engaged. 10. Fasten hood top and side plate assembly (Fig. 14) to outdoor-air opening panel with screws provided. 11. Place knob supp...
Page 15 - Fig. 22 — Durablade Economizer Barometric; Fig. 23 — Economizer Component Locations
15 OPTIONAL ECONOMI$ER — See Fig. 23 for EconoMi$ercomponent locations. 1. To remove the existing unit filter access panel, raise the panel and swing the bottom outward. The panel is nowdisengaged from the track and can be removed. Removethe indoor coil access panel and discard. See Fig. 24.If insta...
Page 16 - Fig. 27 — Completed Hood Assembly; OAT
16 SEAL STRIP SEAL STRIP OUTDOOR AIRHOOD TOP SCREENRETAINER OUTDOOR AIRINLETSCREENS OUTDOOR AIRHOOD SIDES ASSEMBLEDEXHAUST HOOD OUTDOOR AIROPENINGPANEL ECONOMIZER ECONOMIZER REARFLANGE UNIT BASE UNIT FILTERRACK ECONOMIZER CLIPHVAC UNIT WIRINGHARNESS OUTDOORAIRBLOCK-OFFPLATE Fig. 26 — Outdoor-Air Hoo...
Page 17 - OR; Fig. 33 — Typical Access Panel Locations
17 OUTDOORAIRSENSOR TEMP TEMP COM OUTPWR BROWN VIOLET WHITE RED BROWN TEMPTEMPCOMOUTPWR RETURNAIRSENSOR VIOLET WHITE RED OAT COM OAH -15 V RAT COM RAH +15 V ECONOMI$ERCONTROLLER PINK TEMP TEMP VIOLET SUPPLY AIR TEMPERATURE SENSOR V+ 24 COM VAC SENSOR CO 2 (+) COM DAT COM REM POT COM LED COM CO 2 CO ...
Page 18 - Fig. 36 — Barometric Relief Capacity
18 CO 2 Control Setup — If a CO 2 sensor is not being used, pro- ceed to the next section. If a CO 2 sensor is being used, perform the following: 1. Determine the value at which you want the minimum po- sition of the dampers to begin opening to allow a greateramount of outdoor air to enter. The rang...
Page 19 - Step 9 — Adjust Evaporator-Fan Speed —; Fig. 38 — Evaporator-Fan Pulley Adjustment
19 Step 9 — Adjust Evaporator-Fan Speed — Ad- just evaporator-fan speed to meet jobsite conditions. Tables 5A and 5B show fan rpm at motor pulley settings. Tables 6 and 7 show maximum amp draw of belt-drive motor.Table 8 shows motor nominal horsepower for evaporator-fanmotors. Refer to Tables 8-25 f...
Page 30 - Table 28 — Altitude Compensation*; Heating
30 NOTE: When the compressor is rotating in the wrong direc-tion, the unit will make an elevated level of noise and will notprovide cooling. Cooling — Set space thermostat to OFF position. To start unit, turn on main power supply. Set system selector switch atCOOL position and fan switch at AUTO. po...
Page 32 - Fig. 39 — MoistureMiser Option Operation
Page 33 - Fig. 40 — Cleaning Condenser Coil
33 SERVICE Cleaning — Inspect unit interior at the beginning of heat- ing and cooling season and as operating conditions require.EVAPORATOR COIL 1. Turn unit power off, tag disconnect. Remove evaporator coil access panel. 2. If economizer or two-position damper is installed, re- move economizer by d...
Page 37 - Burner Ignition —; Table 29 — LED Error Code Description*; Main Burners —; Fig. 52 — Burner Section Details
37 Burner Ignition — Unit is equipped with a direct spark ignition 100% lockout system. Integrated Gas Unit Controller(IGC) is located in the control box (Fig. 10). A single LED onthe IGC provides a visual display of operational or sequentialproblems when the power supply is uninterrupted. The LEDca...
Page 38 - Fig. 54 — Spark Gap Adjustment; LOW HEAT
38 Fig. 54 — Spark Gap Adjustment LOW HEAT 48HJE004, 48HJD005-007 — 72,000 BTUH INPUT MEDIUM AND HIGH HEAT 48HJE005-007, 48HJF004 — 115,000 BTUH INPUT 48HJF005-007 — 150,000 BTUH INPUT
Page 39 - TROUBLESHOOTING; Refer to Tables 30-36 for troubleshooting details.; Table 30 — LED Error Code Service Analysis; SYMPTOM
39 TROUBLESHOOTING Refer to Tables 30-36 for troubleshooting details. Table 30 — LED Error Code Service Analysis LEGEND SYMPTOM CAUSE REMEDY Hardware failure.(LED OFF) Loss of power to control module (IGC). Check 5 amp fuse on IGC, power to unit, 24-v circuit breaker, and transformer. Units without ...
Page 42 - Subcooler will not deenergize.
42 Table 35 — MoistureMiser Dehumidification Subcooler Service Analysis PROBLEM CAUSE REMEDY Subcooler will not energize. No power to control transformer fromevaporator-fan motor. Check power source and evaporator-fan relay. Ensure all wire connections are tight. No power from control transformer to...
Page 43 - Table 36 — Cooling Service Analysis
43 Table 36 — Cooling Service Analysis PROBLEM CAUSE REMEDY Compressor and condenser fanwill not start. Power failure. Call power company. Fuse blown or circuit breaker tripped. Replace fuse or reset circuit breaker. Defective thermostat, contactor, transformer, or control relay. Replace component. ...
Page 45 - LEGEND AND NOTES FOR FIG. 55
45 LEGEND AND NOTES FOR FIG. 55 AHA — Adjustable Heat Anticipator C — Contactor, Compressor CAP — Capacitor CC — Cooling Compensator CLO — Compressor Lockout COMP — Compressor Motor D — Diode EC — Enthalpy Control ECON — Economizer EPS — Emergency Power Supply EQUIP — Equipment ER — Economizer Relay...
Page 48 - I. PRELIMINARY INFORMATION; ELECTRICAL
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. PC 111 Catalog No. 534-767 Printed in U.S.A. Form 48HJ-18SI Pg CL-1 9-00 Replaces: 48HJ-17SI Book 1 4 Tab 1a 6a Copyright 2000 Carrier Cor poration - - -...