Page 3 - COOLING CAPACITIES AND EFFICIENCIES; Model number nomenclature
3 LEGEND AL — Aluminum CU — Copper *The 048 unit is 208-230/1/60. Minimum voltage of 197 at maximum load conditions. COOLING CAPACITIES AND EFFICIENCIES ARI* capacities UNIT 48GS NOMINAL TONS STANDARD CFM NET COOLING CAPACITIES (Btuh) SEER† SOUND RATINGS‡ (Bels) 018040 1-1/2 600 18,000 10.0 7.5 0240...
Page 4 - HEATING CAPACITIES AND EFFICIENCIES
4 ARI capacities (cont) LEGEND AFUE — Annual Fuel Utilization Efficiency NOTE: Before purchasing this appliance, read important energy costand efficiency information available from your retailer. UNIT 48GS HEATING INPUT (Btuh) OUTPUT CAPACITY (Btuh) TEMPERATURE RISE RANGE (°F) AFUE (%) 0180400240400...
Page 5 - Physical data
5 Physical data * Based on altitude of 0 to 2000 feet.† Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating air- flow velocity of 300 ft/min for throwaway type or 450 ft/min for high-capacity type. Air fil...
Page 6 - Options and accessories
6 Factory-installed optionsLouvered grille provides hail and vandalism protection. A wire grille is standard on all models. See model number nomenclaturefor louvered grille options. C o i l o p t i o n s i n c l u d e c o p p e r / c o p p e r a n d v i n y l - c o a t e d construction for refrigera...
Page 10 - FULL PERIMETER CURB; Accessory dimensions
10 UNIT SIZE A in. [mm] B in. [mm] C in. [mm] D in. [mm] FLAT CURB 018-042 CPRFCURB006A00 8 [203] 11 27 / 32 [301] 30 5 / 8 [ 778] 28 3 / 4 [ 730] CPRFCURB007A00 14 [356] 11 27 / 32 [301] 30 5 / 8 [ 778] 28 3 / 4 [ 730] 048,060 CPRFCURB008A00 8 [203] 15 27 / 32 [402] 42 1 / 8 [1070] 40 1 / 4 [1022] ...
Page 11 - Wet Coil; V Select unit that corresponds to power source available.
11 Selection procedure (with example) I Determine cooling and heating requirements at designconditions:Given: . . . Required Cooling Capacity (TC) ....................34,000 Btuh. . . Sensible Heat Capacity (SHC) ........................25,000 Btuh. . . Required Heating Capacity .......................
Page 12 - Performance data; NET COOLING CAPACITIES
12 Performance data NET COOLING CAPACITIES See Legend and Notes on page 14. 48GS018 Temp (F) Outdoor Air Entering Condenser Evaporator Air — CFM/BF 525/0.118 600/0.159 675/0.187 Evaporator Air — Ewb (F) 62 67 72 62 67 72 62 67 72 85 TC 15.7 18.5 20.9 16.5 19.2 21.5 17.2 19.8 21.9 SHC 13.5 11.6 9.5 1...
Page 15 - DRY COIL AIR DELIVERY* — HORIZONTAL AND DOWNFLOW DISCHARGE
15 DRY COIL AIR DELIVERY* — HORIZONTAL AND DOWNFLOW DISCHARGE (Deduct 10% for 208 v) *Air delivery values are without air filter and are for dry coil. (See Wet Coil Pressure Drop table.) NOTE: Deduct field-supplied air filter pressure drop or economizer and 1-in. filter pressure drop andwet coil pre...
Page 17 - HIGH ALTITUDE COMPENSATION
17 HIGH ALTITUDE COMPENSATION NATURAL GAS ONLY ORIFICE CONVERSION — 3.5 in. wg MANIFOLD PRESSURE* * As the height above sea level increases, there is less oxygen per cubic ft of air. Therefore heat input rate should be reduced at higher altitudes. † Orifices available through your Carrier distributo...
Page 18 - Typical piping and wiring
18 Typical piping and wiring VERTICAL DISCHARGE HORIZONTAL DISCHARGE NEC — National Electrical Code INDOORTHERMOSTAT DISCONNECTPER NEC* FROMPOWERSOURCE RETURNAIR TOP COVER FROMGAS LINE *NEC - NATIONAL ELECTRICAL CODE
Page 19 - Application data
19 Condensate trap — A 2-in. condensate trap must be fieldsupplied.Ductwork — Secure downflow discharge ductwork to roofcurb. For horizontal discharge applications, attach ductwork tounit with flanges.To convert a unit to downflow discharge — Units aree q u i p p e d w i t h factory-installed ins er...
Page 23 - Electrical data
23 452 = 5 v 457 = 7 v455 = 2 v LEGEND FLA — Full Load Amps LRA — Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent ProtectionRLA — Rated Load Amps NOTES:1. In compliance with NEC (National Electrical Code) requirements for multimotor and combination load equipment (refer to NE...
Page 24 - Controls; Operating sequence
24 Controls Operating sequence Heating — When the thermostat calls for heating, terminal“W” is energized, starting the induced draft motor. When thehall-effect sensor on the induced-draft motor senses that it hasreached the required speed, the burner ignition sequence begins.The indoor (evaporator) ...
Page 25 - Guide specifications
25 Packaged Heating/Cooling UnitsConstant Volume ApplicationHVAC Guide Specifications Size Range: 1-1/2 to 5 Tons, Nominal Cooling40,000 to 130,000 Btuh,Nominal Heating Input Carrier Model Number: 48GSPart 1 — GeneralSYSTEM DESCRIPTION Outdoor rooftop mounted, gas heating/electric cooling unitutiliz...