Page 2 - Connections
Approved for outdoor installation on wood flooring or on class A,B or C roof covering materials. Before performing service or maintenance operations onsystem, turn off main power to unit and install lock-out tag.Turn off accessory heater power switch if applicable. Elec-trical shock could cause seve...
Page 4 - Fig. 7—Humidistat Wiring for
(2.) AC/HP Size-Factory selected to match system size, please verify. (3.) SYSTEM TYPE-Factory selected on 48GP system AC- AIR CONDITIONER. (4.) AC/HP CFM ADJUST-Select HIGH for 042 & 048, NOM for 036 & 060, and LO for 024 & 030.. (5.) ON/OFF DELAY-Factory selected 0/90 profile. (6.) CON...
Page 5 - Fig. 8—Detail of SPP Printed-Circuit Board; EASY SELECT; PIN CONNECTOR
b. COOLING MODE (1.) If indoor temperature is above temperature set point and humidity is below humidity set point, thermostat closescircuits R to G, R to Y/Y2 and R to O—The unit deliverssingle speed cooling airflow. c. COOLING MODE-DEHUMIDIFICATION (1.) If indoor temperature is above temperature s...
Page 6 - Fig. 10—ThermidistatTM Wiring for
(4.) ENH (enhanced) selection provides a 30 sec. cooling & heat pump on delay with no airflow, plus 150 seconds at 70 percent airflow and no off delay for added comfort. This will minimize cold blow in heat pump operation and could enhance system efficiency. f. CONTINUOUS FAN—SELECT DESIRED FAN ...
Page 7 - Fig. 11—Detail of SPP Printed-Circuit Board
to a level which causes the Thermidistat™ to close its contacts.When the contacts close, the airflow will return to 100 percentof selected cooling airflow. To activate this mode wire inThermidistat™ see jumper in Fig. 10. e. DEHUMIDIFY AND SUPER DEHUMIDIFY CAPABILITIES This model unit is capable of ...
Page 8 - This BASIC
and continuous operation. (See Tables 16, 17 & 18 for airflowdelivery and minimum CFM.) Note that airflow marked is theairflow which will be supplied in emergency heat mode andheating mode on air conditioners when electric heat is theprimary heating source. In heat pump heating mode whenelectric...
Page 9 - Fig. 12—Humidifier Wiring for 50GL & 50JZ
This configuration provides the following comfort enhance-ments: (a.) A 30 sec blower on delay with 150 sec at 70 percent airflow to allow the indoor coil to warm up or cooldown before the blower is asked to deliver 100 percentairflow reducing the cold blow sensation at start up inheating and allowi...
Page 10 - AUTO and ON
value. If circuit R to G is open (0–v.) for super dehumidifymode, the motor delivers reduced airflow to maximize thehumidity removal of the system while minimizing overcooling. e. ELECTRIC HEATING MODE (1.) Thermostat closes circuit R to W/W1, or W2—The unit delivers the selected electric heat airfl...
Page 12 - Indoor Blower and Motor; Table 1—ICM FIOP Physical Data—Unit 48GP
cooling cycle remains ‘‘on’’ until the room temperature drops topoint that is slightly below the cooling control setting of the roomthermostat. At this point, the thermostat ‘‘breaks’’ the circuitbetween thermostat terminal R to terminals Y and G. These opencircuits de-energize contactor coil C and ...
Page 13 - TROUBLESHOOTING; Table 2—ICM FIOP Physical Data—Unit 48GP (Continued)
f. Loosen set-screw that secures wheel to motor shaft, remove screws that secure motor mount brackets to blower housing,and slide motor and motor mount out of blower housing. 2. Remove and clean blower wheel as follows: a. Ensure proper reassembly by marking wheel orientation. b. Lift wheel from hou...
Page 14 - Fig. 14—ICM FIOP Electric Schematic—Unit 48GP
Fig. 14—ICM FIOP Electric Schematic—Unit 48GP C01035 14
Page 15 - Table 4—ICM FIOP Physical Data—Unit 48JZ
Table 4—ICM FIOP Physical Data—Unit 48JZ THIS DATA APPLIES TO 48JZ UNITS WITH THE ICM INDOOR MOTOR FIOP UNIT SIZE 48JZ 024040 030040 030060 036060 036090 042060 042090 NOMINAL CAPACITY (ton) 2 2-1/2 2-1/2 3 3 3-1/2 3-1/2 OPERATING WEIGHT (lb.) 310 324 324 321 321 380 380 COMPRESSORS Quantity Scroll ...
Page 17 - Fig. 15—ICM FIOP Electric Schematic—Unit 48JZ
Fig. 15—ICM FIOP Electric Schematic—Unit 48JZ C01101 17
Page 18 - Table 7—ICM FIOP Physical Data—Unit 50GL
Table 7—ICM FIOP Physical Data—Unit 50GL THIS DATA APPLIES TO 50GL UNITS WITH THE ICM INDOOR MOTOR FIOP UNIT SIZE 024 030 036 042 048 060 NOMINAL CAPACITY (ton) 2 2-1/2 3 3-1/2 4 5 OPERATING WEIGHT (lb) 270 291 299 321 326 399 COMPRESSOR Scroll REFRIGERANT (R-410A) Quantity (lb) 5.0 5.5 6.9 9.0 9.5 ...
Page 19 - Table 8—50GL with ICM FIOP Electrical Data
Table 8—50GL with ICM FIOP Electrical Data UNIT SIZE 50GL V-PH-HZ VOLTAGE RANGE COMPRESSOR OUTDOOR FAN MOTOR INDOOR FAN MOTOR ELECTRIC HEAT SINGLE POINT POWER SUPPLY MIN MAX RLA LRA FLA FLA Nominal kW* FLA MCA MAX FUSE OR CKT. BKR. MOCP 024 208/230–1–60 187 253 13.5 61.0 0.9 4.3 -/- 3.8/5.05.4/7.2 7...
Page 20 - Fig. 16—ICM FIOP Electrical Schematic—50GL
Fig. 16—ICM FIOP Electrical Schematic—50GL C01037 20
Page 21 - Table 9—ICM FIOP Physical Data—Unit 50JZ
Table 9—ICM FIOP Physical Data—Unit 50JZ THIS DATA APPLIES TO 50JZ UNITS WITH THE ICM INDOOR MOTOR FIOP UNIT SIZE 50JZ024 50JZ030 50JZ036 50JZ042 50JZ048 50JZ060 NOMINAL CAPACITY (ton) 2 2-1/2 3 3-1/2 4 5 OPERATING WEIGHT (lb.) 299 320 328 350 355 428 COMPRESSOR QUANTITY 1 TYPE SCROLL COMPRESSOR REF...
Page 22 - Table 10—50JZ with ICM FIOP Electrical Data
Table 10—50JZ with ICM FIOP Electrical Data UNIT SIZE 50JZ V-PH-HZ VOLTAGE RANGE COMPRESSOR OUTDOOR FAN MOTOR INDOOR FAN MOTOR ELECTRIC HEAT SINGLE POINT POWER SUPPLY MIN MAX RLA LRA FLA FLA Nominal kW* FLA MCA MAX FUSE OR CKT. BKR. MOCP 024 208/230–1–60 187 253 13.5 61.0 0.9 4.3 -/- 3.8/5.05.4/7.2 ...
Page 23 - Fig. 17—ICM FIOP Electrical Schematic—50JZ
Fig. 17—ICM FIOP Electrical Schematic—50JZ c01036 23
Page 24 - Dry Coil ICM Airflow
Table 11–48GP & 48JZ Cooling (and Heat Pump Heating-48JZ only) Dry Coil ICM Airflow Small Cabinet UNIT SIZE CFM ADJUST PIN SELECT LO PIN NOM PIN HI PIN EXTERNAL STATIC PRESSURE RANGE 0.0–0.4 0.4–0.7 0.7–1.0 0.0–0.4 0.4–0.7 0.7–1.0 0.0–0.4 0.4–0.7 0.7–1.0 024 COOLING † 745 675 – 835 750 690 940 8...
Page 26 - Table 17—50GL/50JZ Cooling & Heating Dry Coil ICM Airflow
Table 16—50GL/50JZ Cooling & Heating Dry Coil ICM Airflow Small Cabinet UNIT SIZE CFM ADJUST PIN SELECT LO PIN NOM PIN HI PIN EXTERNAL STATIC PRESSURE RANGE 0.0–0.4 0.4–0.7 0.7–1.0 0.0–0.4 0.4–0.7 0.7–1.0 0.0–0.4 0.4–0.7 0.7–1.0 024 COOLING † 800 725 – 885 805 730 990 930 855 COOLING DEHUMIDIFY ...
Page 28 - ICM QUICK REFERENCE GUIDE; QUICK REFERENCE GUIDE; SET-UP INSTRUCTIONS FOR WARMER HEATING TEMPERATURES; according to Installation Instructions.; EASY SELECT BOARD; Table 24—Troubleshooting Chart; SYSTEM
ICM QUICK REFERENCE GUIDE c01034 EASY SELECT HEATER/MOTOR AUX HEAT KW/CFM 0-30 1075 SEC1 SEC2 J1 AC/HP SIZE 036 030 024 018 AC HP-COMFORT HP-EFF NOM HI ENH LO SYSTEM TYPE AC/HP CFM ADJUST ON/OFF DELAY CONTINUOUS FAN MED HI YEL LO AUX1 HUM1 AUX2 24VAC GRY HUM2 YEL WHT BLK ORN BLU VIO 0-20 875 0-10 72...
Page 29 - GAS INLET PRESSURE; IV. EASY SELECT SETTINGS
c01999 START-UP CHECKLIST (Remove and Store in Job File) I. Preliminary Information MODEL NO.:_________________________________SERIAL NO.:__________________________________DATE:_______________________________________TECHNICIAN:_________________________________ II. PRE-START-UP (Insert checkmark in b...