Page 2 - INTRODUCTION; Step 1 — Check Equipment; CAUTION; except; Step 3 — Field Fabricate Ductwork
2 words are used with the safety--alert symbol. DANGER identifiesthe most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in per- sonal injury or death. CAUTION is used to identify unsafe practic- es which may result in minor persona...
Page 5 - LARGE CURB; SMALL CURB; IMPORTANT; : Do not install large base pan HYBRID HEAT
5 LARGE CURB SMALL CURB ROOF CURB DETAIL Wood nailer* Roofcurb* Insulation(field supplied) *Provided with roofcurb Cant stripfield supplied Roofing materialfield supplied Flashing fieldsupplied HVAC unitbase rails Roofcurb SealingGasket HVAC unitbasepan Anchor screw A09090 A09415 A09418 C B A F D E ...
Page 6 - Step 4 — Provide Clearances; Step 5 — Rig and Place Unit; PERSONAL INJURY OR PROPERTY DAMAGE; WARNING
6 ACCESS PANELS MUST BE IN PLACE WHEN RIGGING. PANNEAUX D'ACCES DOIT ÊTRE EN PLACE POUR MANIPULATION. 50CY502286 2.0 CAUTION - NOTICE TO RIGGERSPRUDENCE - AVIS AUX MANIPULATEUR Use top skid as spreader bar. / Utiliser la palette du haut comme barre de répartition SEAL STRIP MUST BE INPLACE BEFORE PL...
Page 7 - Inspection; Step 6 — Connect Condensate Drain; Step 8 — Install Gas Piping
7 Inspection Prior to initial use, and at monthly intervals, all rigging shackles, clevis pins, and straps should be visually inspected for anydamage, evidence of wear, structural deformation, or cracks. Particular attention should be paid to excessive wear at hoisthooking points and load support ar...
Page 8 - OUT
8 A 1/8--in. (3.2 mm) NPT plugged tapping, accessible for test gaugeconnection, must be installed immediately upstream of the gas supply connection to the gas valve.When installing the gas supply line, observe local codes pertaining to gas pipe installations. Refer to the NFGC NFPA 54/ANSI Z223.1 la...
Page 10 - Table 2 – Maximum Gas Flow Capacity*; Table 3 – Heating Inputs
10 Table 1 -- Physical Data -- Unit 48EZ--A (Cont’d) UNIT SIZE 48EZ --- A 48090 48115 48130 60090 60115 60130 NOMINAL CAPACITY --- ton 4 4 4 5 5 5 OPERATING WEIGHT --- lb (kg) 482 219 482 219 482 219 507 230 507 230 507 230 COMPRESSORS Scroll Quantity 1 REFRIGERANT (R --- 410A) Quantity --- lb (kg )...
Page 11 - Step 9 — Install Duct Connections; Configuring Units for Downflow (Vertical) Discharge
11 Step 9 — Install Duct Connections The unit has duct flanges on the supply-- and return--air openingson the side and bottom of the unit. For downshot applications, the ductwork connects to the roof curb (See Fig. 2 and 3 for connection sizes and locations). Configuring Units for Downflow (Vertical...
Page 12 - Return Duct Panels; Supply Duct Panels
12 Horizontal Duct Covers A09061 BasepanDownflow(Vertical)SupplyKnockout BasepanDownflow (Vertical)ReturnKnockout A09060 Fig. 8 -- Supply and Return Duct Opening Return Duct Panels Return & Supply Duct Panels fromUnderside of Base (Alternate Method) Supply Duct Panels A09420 Fig. 9 -- Vertical (...
Page 13 - Step 10 — Install Electrical Connections; UNIT COMPONENT DAMAGE HAZARD; ELECTRICAL SHOCK HAZARD; ELECTRICAL SHOCK AND EXPLOSION HAZARD; Then; Control Voltage Connections
13 Step 10 — Install Electrical Connections ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death.The unit cabinet must have an uninterrupted, unbroken electrical ground. This ground may consist of an electrical wire connected to the unit ground screw in the...
Page 14 - Balance Point Setting--Thermidistat or Hybrid; FIRE, EXPLOSION HAZARD
14 POWERSUPPLY FIELD-SUPPLIEDFUSED DISCONNECT HIGH VOLTAGEPOWER LEADS(SEE UNIT WIRINGLABEL) EQUIP GR CONTROL BOX SPLICE BOX LOW-VOLTAGEPOWER LEADS(SEE UNITWIRING LABEL) W Y G R C WHT(W1) YEL(Y) GRN(G) RED(R) BRN(C) THERMOSTAT(TYPICAL) O ORN(O) GRA (Y2) BLU (DH) DH 3-PhaseOnly A09067 Fig. 10 -- High ...
Page 15 - Step 1 — Check for Refrigerant Leaks; NOTE; Step 2 — Unit Sequence of Operation; Heating Sequence of Operation; NOTE; ments; NOTE
15 4. Verify the following conditions: a. Make sure gas line is free of air. Before lighting the unit for the first time, perform the following with the gasvalve in the “OFF” position: NOTE : If the gas supply pipe was not purged before connecting the unit, it will be full of air. It is recommended ...
Page 16 - Check Heating Control; UNIT DAMAGE HAZARD; Adjust Gas Input
16 MANIFOLD BURNER BURNER FLAME C99021 Fig. 12 -- Monoport Burner Check Heating Control Start and check the unit for proper heating control operation asfollows (see furnace lighting instructions located on the inside of the control access panel): 1. Place room thermostat SYSTEM switch in the HEAT po...
Page 17 - FIRE AND UNIT DAMAGE HAZARD; Measure Manifold Pressure (Propane Units); Check Burner Flame; Table 5 – LED Indications; Rollout Switch
17 4. Divide number of seconds in Step 3 into 3600 (number of seconds in one hr). 5. Multiply result of Step 4 by the number of cubic feet (cu ft) shown for one revolution of test dial to obtain cubic feet (cuft) of gas flow per hour. 6. Multiply result of Step 5 by Btu heating value of gas to obtai...
Page 18 - Checking Cooling Control Operation; Indoor Airflow and Airflow Adjustments
18 Step 4 — Start--up Cooling and Make Adjust- ments Complete the required procedures given in the Pre--Start--Upsection before starting the unit. Do not jumper any safety devices when operating the unit. Do not operate the compressor when the outdoor temperature is below 40 ° F (4.4 ° C) (unless ac...
Page 19 - Continuous Fan Operation
19 Gas Heating Fan Speed Set-up To change the gas heating speed: 1. Remove the vinyl cap off of the desired speed tap wire (Refer to Table 6 for color coding). Table 10 shows thetemperature rise associated with each fan speed for a given static pressure. Make sure that the speed chosen delivers atem...
Page 28 - MAINTENANCE; Air Filter
28 MAINTENANCE To ensure continuing high performance and to minimize the possibility of premature equipment failure, periodic maintenancemust be performed on this equipment. This combination heating/cooling unit should be inspected at least once each year bya qualified service person. To troubleshoo...
Page 30 - FEEDER TUBE; Outdoor Fan; UNIT OPERATION HAZARD; Electrical Controls and Wiring; Refrigerant Circuit
30 BLOWER HOUSING 2 SETSCREWS (HIDDEN) C99085 Fig. 20 -- Removal of Motor and Blower Wheel A07680 Fig. 21 -- Burner Rack Removed FEEDER TUBE STUB TUBE DEFROST THERMOSTAT C99029 Fig. 22 -- Defrost Thermostat Location A07680 Fig. 23 -- Burner Rack Removed Outdoor Fan UNIT OPERATION HAZARD Failure to f...
Page 31 - Gas Input
31 OF2 OF1 ON QUIET SHIFT 120 30 60 60 30 90 INTER V AL TIMER OFF P3 DFT O R W 2 Y C T2 C C O DFT T1 Y P1 J1 SPEEDUP SpeedupPins Defrost intervalDIP switches QuietShift A08020 Fig. 24 -- Defrost Control EXPLOSION, PERSONAL INJURY AND ENVIRONMENTAL HAZARD Failure to follow this warning could result i...
Page 33 - Accurater; LEGEND; Accurater; Refrigerant System
33 COMPRESSOR ACCUMULATOR OUTDOOR COIL INDOOR COIL LCS LEGEND HPS – High Pressure SwitchLCS – Loss of Charge Switch Accurater ® Metering De vice Arrow indicates direction of flo w TXV in Metering Position Bypass Position HP S C03011 Fig. 26 -- Typical Heat Pump Operation, Cooling Mode COMPRESSOR ACC...
Page 34 - TROUBLESHOOTING
34 Servicing Systems on Roofs and with Synthetic materials POE (polyolester) compressor lubricants are known to cause long term damage to some synthetic roofing materials.Exposure, even if immediately cleaned up, may cause embrittlement (leading to cracking) to occur in one year or more.When perform...
Page 35 - Table 11 – Troubleshooting Guide -- Cooling or Heat Pump Heating Mode
35 Table 11 – Troubleshooting Guide -- Cooling or Heat Pump Heating Mode SYMPTOM CAUSE REMEDY Compressor and Outdoor fan will not start. Power Failure Call power company. Fuse blown or circuit breaker tripped Replace fuse or reset circuit breaker. Defective thermostat, contactor, transformer, or con...