Page 2 - Instructions continued on page 12.
ALTERNATE UNIT SUPPORT — When the preferred curbor slab mount cannot be used, support unit with sleepers onperimeter, using unit curb support area. If sleepers cannot beused, support long sides of unit (refer to Fig. 3-6) with aminimum number of 4-in. x 4-in. pads spaced as follows:48EJ,EK,EW,EY024-...
Page 10 - Table 1 — Physical Data
Table 1 — Physical Data UNIT 48EJ,EK,EW,EY 024D/E 028D/E 030D/E 034D/E NOMINAL CAPACITY (tons) 20 25 27 30 OPERATING WEIGHT (lb)* Unit Al/Al† (Lo Heat/Hi Heat) 4176/4256 4262/4342 4262/4342 4262/4342 Al/Cu† (Lo Heat/Hi Heat) 4396/4476 4482/4562 4482/4562 4482/4562 Roof Curb (14-in. curb) 365 365 365...
Page 12 - Step 4 — Install Flue Hood —; Flue hood is shipped; Fig. 10 — Flue Hood Location
Table 2 — Evaporator Fan Motor Data (Units with Starting Serial Numbers 4197 and Later) UNIT SIZE 48E MOTOR HP MOTOR SHAFT DIA. (in.) FAN SHAFTSPEED (rpm) MOTOR SHEAVE MOTOR SHEAVE PITCH DIAMETER (in.) BUSHING DIAMETER (in.) FAN SHEAVE FAN SHEAVE PITCH DIAMETER (in.) BUSHING DIAMETER (in.) BELT (QUA...
Page 13 - Fig. 11 — Combustion Fan Housing Location
Step 5 — Trap Condensate Drain — See Fig. 3-6 for drain location. Condensate drain is open to atmosphereand must be trapped. Install a trapped drain at the drain lo-cation. A trap at least 4-in. deep must be used. See Fig. 12.Trap must be installed to prevent freeze-up. Condensate pans are sloped so...
Page 15 - Fig. 14 — Field Control Remote Start/Stop
Features with Sensor Control of Unit (Network Applica-tions) — The base control board provides, as standard, a con-nection for use with a Carrier VVT system and can also beintegrated into a Carrier Comfort Network. When the unit is accessed via a PC equipped with Com- fortWorks™, Building Supervisor...
Page 16 - Step 8 — Make Electrical Connections
When a VAV unit with a space temperature sensor is ac- cessed via a computer, the following additional features areavailable:• ability to initiate timed override from T-55 sensors• temperature compensated start to calculate early start time before occupancy • provide space temperature reset to reset...
Page 17 - Fig. 16 — Control Board Diagram
LEGEND CCN — Carrier Comfort NetworkCOM — CommonD — Diode LED — Light-Emitting Diode N.C. — Normally Closed N.O. — Normally OpenR — Relay SIO — Serial Input/Output SW — Switch T — Terminal Fig. 16 — Control Board Diagram *Where X is the unit control software version number. 17
Page 18 - Table 4 — Electrical Data
Table 4 — Electrical Data UNIT SIZE 48E NOMNAL VOLTAGE (3 Ph 60 Hz) VOLTAGE RANGE COMPRESSOR OFM IFM POWER EXHAUST COMBUSTION FAN MOTOR POWER SUPPLY No. 1 No. 2 Min Max RLA LRA RLA LRA Qty Hp FLA (ea) Hp FLA FLA LRA FLA MCA MOCP* 024 208/230 187 254 39.1 228 25.6 160 2 1 5.3 5 16.7/15.2 — — 0.96 101...
Page 21 - Fig. 17 — Field Power Wiring Connections
IMPORTANT: THE VAV (variable air volume) unitsuse variable frequency drives, which generate, use andcan radiate radio frequency energy. If units are not in-stalled and used in accordance with these instructions,they may cause radio interference. They have been testedand found to comply with limits o...
Page 22 - Fig. 20 — Field Control Thermostat Wiring; Fig. 21 — Field Control Temperature Sensor Wiring
LEGEND Fig. 20 — Field Control Thermostat Wiring NOTE: Sensor part numbers are as follows: T-55 — CEC0121448-01T-56 — CEC0121503-01 Fig. 21 — Field Control Temperature Sensor Wiring (CV or VAV Units) C — Contactor/Compressor CB — Circuit Breaker DIP — Dual In-Line PackageFU — Fuse HR — Heater Relay ...
Page 23 - Table 5 — CCN Connection Approved Shielded Cables
Remote Field Control — A switch closure across terminalsR and W1 on TB-3 will initiate the Occupied mode. Thiscan be done manually as well as through a field-suppliedtimeclock.Service Tool, Building Supervisor, and ComfortWorks™Software — Access to the control board can be achieved throughthe termin...
Page 24 - Table 6 — Color Code Recommendations; Step 9 — Make Outdoor-Air Inlet Adjustments
IMPORTANT: When connecting the CCN communi-cation bus to a system element, use a color coding sys-tem for the entire network to simplify installation andcheckout. See Table 6. Table 6 — Color Code Recommendations SIGNAL TYPE CCN BUS CONDUCTOR INSULATION COLOR CCN PLUG PIN NO. Positive (+) RED 1 Grou...
Page 26 - Fig. 28 — Adding Foam Strip to Hood Side; Fig. 29 — Adding Foam Strip to Blockoff Baffle
The outdoor-air damper closes. The control allows 90 sec- onds for the damper to close in case it is in the full openposition. Next, the indoor-fan contactor will energize. Theoutdoor-air damper will remain at 0% for 30 seconds. It willthen move to the 10% position for another 30 seconds. Thiswill b...
Page 27 - Filter Track Assembly; Fig. 32 — Attaching Seal Strip to Filter Cover; Fig. 33 — Differential Enthalpy Control and Sensor
Differential Enthalpy Sensor Installation — To install the con-trol, perform the following procedure: 1. Turn off all power. Ensure disconnect is locked out.2. Remove the economizer inlet filters from the bottom of the right hand economizer hood. See Fig. 24. 3. Remove the factory-installed, 620-ohm...
Page 28 - Fig. 34 — Wiring Connections for Solid-State; Fig. 35 — Psychrometric Chart for
NOTE: Switches shown in high enthalpy state. Terminals 2 and 3 closeon enthalpy decrease. Fig. 34 — Wiring Connections for Solid-State Enthalpy Control (HH57AC077) CONTROL CURVE CONTROL POINT (APPROX. DEG.) AT 50% RH A 73 (23) B 70 (21) C 67 (19) D 63 (17) RH — Relative Humidity Fig. 35 — Psychromet...
Page 30 - Step 11 — Install All Accessories —; Fig. 38 — Pressure Transducer Locations; Fig. 39 — Motormaster III Baffle Details
Step 11 — Install All Accessories — After all the factory-installed options have been adjusted, install all field-installed accessories. Refer to the accessory installation in-structions included with each accessory. MOTORMASTER t III INSTALLATION Install Field-Fabricated Wind Baffles — Wind baffles...
Page 32 - Power Exhaust —; Table 7 — VFD Supply Air Pressure Set Point; JUMPERS
To set the VFD, the VFD must be powered up; however, since it is located near the indoor air fan, operation of thefan is not desirable. To disable the fan, perform the follow-ing procedure: 1. Open the indoor fan circuit breaker.2. Remove the jumper between CC and ST on the terminal strip of the VFD...
Page 33 - Table 8 — Potentiometer Signal Levels; Crankcase Heater —
At the upper right corner of the board is a set of 5 pins and jumper, which determines the time constant for the control.The time constant is the delay in response built into the con-trols. The jumper should be on the middle or bottom twopins, for the maximum time constant. The delay can bedecreased...
Page 35 - Table 12 — Fan Performance, 48EJ/EK024-034 — Vertical Discharge Units
Table 12 — Fan Performance, 48EJ/EK024-034 — Vertical Discharge Units (For EW/EY units, reduce net available external static pressure by 0.3 in. wg) AIRFLOW (Cfm) AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm B...
Page 36 - Table 13 — Fan Performance, 48EJ,EK038,044 — Vertical Discharge Units
Table 13 — Fan Performance, 48EJ,EK038,044 — Vertical Discharge Units (For EW/EY units, reduce net available external static pressure by 0.5 in. wg) AIRFLOW (Cfm) AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm B...
Page 37 - Table 14 — Fan Performance, 48EJ,EK048 — Vertical Discharge Units
Table 14 — Fan Performance, 48EJ,EK048 — Vertical Discharge Units (For EW/EY units, reduce net available external static pressure by 0.5 in. wg) AIRFLOW (Cfm) AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 9...
Page 38 - Table 15 — Fan Performance — Power Exhaust; Table 16 — Motor Limitations
Table 15 — Fan Performance — Power Exhaust 48EJ,EK,EW,EY024-048 (20 THRU 45 TONS) Airflow (Cfm) Low Speed Medium Speed High Speed 208 v 230, 460, 575 v 208 v 230, 460, 575 v 208 v 230, 460, 575 v ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts 6,500 0.32 2.82 3160...
Page 39 - Table 17 — Air Quantity Limits; Filter Replacement —
Table 17 — Air Quantity Limits UNIT 48EJ,EK,EW,EY MINIMUM HEATING AIRFLOW (Low Heat) MINIMUM HEATING AIRFLOW (High Heat) MINIMUM COOLING AIRFLOW (VAV) AT FULL LOAD OPERATION MINIMUM COOLING AIRFLOW (CV) MAXIMUM AIRFLOW 024 5730 5950 2000 6,000 10,000 028 5730 5950 2500 7,500 12,500 030 5730 5950 275...
Page 40 - Table 18 — User Defined Set Points
Table 18 — User Defined Set Points SET POINT NAME FORMAT DESCRIPTION LIMITS DEFAULT OHSP xx.xF Occupied Heat Set Point 55 to 80 F 68 F OCSP xx.xF Occupied Cool Set Point 55 to 80 F 78 F UHSP xx.xF Unoccupied Heat Set Point 40 to 80 F 55 F UCSP xx.xF Unoccupied Cool Set Point 75 to 95 F 90 F SASP xx....
Page 42 - Fig. 42 — Heat Interlock Relay Wiring; Fig. 43 — Space Temperature Reset Wiring
MORNING WARM-UP (VAV Only) (Stand-Alone Opera-tion) — When the unit operates in stand-alone mode, morn-ing warm-up occurs when the unit is energized in Occupiedmode and return-air temperature (RAT) is below 68 F. Warm-upwill not terminate until the RAT reaches 68 F. The heat in-terlock relay output ...
Page 44 - SERVICE
• When the outdoor air quality is greater than the outdoor air quality set point (ppm) High priority — When the priority is set to high, the IAQset point controls the outside air damper exclusively, withno regard to comfort conditioning. TIME GUARD t CIRCUIT — The Time Guard function (built into the...
Page 45 - Fig. 46 — Spark Gap Adjustment
To open, loosen the latch bolt using a 7 ⁄ 16 -in. wrench. Pivot the latch so it is not in contact with the door. Open the door.To shut, reverse the above procedure.NOTE: Disassembly of the top cover may be required underspecial service circumstances. It is very important that theorientation and pos...
Page 46 - Fig. 47 — Typical Gas Heating Section
Evaporator Fan Performance Adjustment (Fig. 49) — Fan motor pulleys are designed for speed shown in Table 1 (factory speed setting). IMPORTANT: Check to ensure that the unit drivematches the duct static pressure using Tables 12-14. To change fan speeds, change pulleys.To align fan and motor pulleys:...
Page 47 - Adjustment
Evaporator-Fan Motor Replacement 1. Shut off unit power supply.2. Remove upper outside panel and open hinged door to gain access to motor. 3. Fully retract motor plate adjusting bolts.4. Loosen the two rear (nearest the evaporator coil) motor plate nuts. 5. Remove the two front motor plate nuts and ...
Page 48 - Main Burners —; For all applications, main burners are; Filter Drier —; Replace whenever refrigerant system is; Protective Devices; COMPRESSOR PROTECTION; Fig. 50 — Belt Tension Adjustment
Main Burners — For all applications, main burners are factory set and should require no adjustment.MAIN BURNER REMOVAL (Fig. 55) 1. Shut off (field-supplied) manual main gas valve.2. Shut off power to unit.3. Remove heating access panel.4. Disconnect gas piping from gas valve inlet.5. Remove wires f...
Page 49 - Fig. 55 — Main Burner Removal
Crankcase Heater — Each compressor has a crankcase heaterto prevent absorption of liquid refrigerant by oil in the crank-case when the compressor is idle. Since power for the crank-case heaters is drawn from the unit incoming power, mainunit power must be on for the heaters to be energized. IMPORTAN...
Page 50 - LEGEND and NOTES for Fig. 56-60 — Typical Wiring Schematics
LEGEND and NOTES for Fig. 56-60 — Typical Wiring Schematics AHA — Adjustable Heat Anticipator BP — Building Pressure BR — Burner Relay C — Contactor, Compressor CAP — Capacitor CB — Circuit Breaker CC — Cooling Compensator CCB — Controller Circuit Breaker CCH — Crankcase Heater COM — Communication C...
Page 52 - Fig. 57 — Typical VAV 115-v Control Circuit
Page 53 - Fig. 58 — Typical CV 115-v Control Circuit
Page 54 - Fig. 59 — Typical VAV 24-v Control Circuit
Page 55 - Fig. 60 — Typical CV 24-v Control Circuit
Page 56 - TROUBLESHOOTING
TROUBLESHOOTING Typical refrigerant circuiting diagrams are shown in Fig. 61-63. An algorithm diagram of the IGC (Integrated Gas Unit Con-troller) control is shown in Fig. 64. LEGEND FPS — Freeze Protection SwitchHPS — High-Pressure SwitchLPS — Low-Pressure Switch Fig. 61 — Typical Refrigerant Circu...
Page 60 - The alarm codes for the IGC control board are shown in; Table 22 — IGC Control Board LED Alarms; Diagnostic LEDs —; Table 23 — Control Board LED Alarms
The alarm codes for the IGC control board are shown in Table 22. Table 22 — IGC Control Board LED Alarms INDICATION ERROR MODE ON Normal Operation OFF Hardware Failure 1 FLASH Fan ON/OFF Delay Modified 2 FLASHES Limit Switch Fault 3 FLASHES Flame Sense Fault 4 FLASHES 4 Consecutive Limit Switch Faul...
Page 61 - Tables 24-26 show the input and output channel; Table 24 — I/O Channel Designations Base Module — CV
Tables 24-26 show the input and output channel designations. Table 24 — I/O Channel Designations Base Module — CV TERMINAL NO. ASSIGNMENT TERMINAL NO. ASSIGNMENT T1-2 SPT (CCN) — 10K V Thermistor T23-25 Compressor 2 Safety — DI (24 vac) T3-4 STO (CCN) — 10K V Thermistor T24-25 Outside Air Enthalpy —...
Page 62 - PACKAGED SERVICE TRAINING; equipment discussed in this manual. Product programs cover:
PACKAGED SERVICE TRAINING Our packaged service training programs provide an excellent way to increase your knowledge of the equipment discussed in this manual. Product programs cover: • Unit Familiarization • Maintenance • Installation Overview • Operating Sequence A large selection of product, theo...
Page 63 - PRESSURES
START-UP CHECKLIST MODEL NO.: SOFTWARE VERSION (SEE FIG. 16) DATE: SERIAL NO.: TECHNICIAN: PRE-START-UP: M VERIFY THAT DIP SWITCH SETTINGS ARE CORRECT M VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT M REMOVE ALL SHIPPING HOLDDOWN BOLTS AND BRACKETS PER INSTRUCTIONS M VERIFY INSTALLAT...
Page 64 - GENERAL
GENERAL M SET ECONOMIZER MINIMUM VENT POSITION TO JOB REQUIREMENTS M ENSURE DRIVES OPERATE WITHIN LIMITS OF FAN PERFORMANCE TABLES HIGH PRESSURE SWITCH SETTING psig LOW PRESSURE SWITCH SETTING psig MOTOR PULLEY PART NUMBER FAN PULLEY PART NUMBER BELT PART NUMBER BELT SIZE in. FILTER QUANTITY FILTER ...