Page 2 - INSTALLATION; Check Package Contents; CR
2 Understand the signal words DANGER, WARNING, andCAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used t...
Page 3 - Smoke Sensor; Smoke Control Module; Smoke Detector; Return Air Smoke Detector Location; WARNING; NOTE
3 Exhaust tube Rubbergasket Cover gasket (ordering option) Sensor housingand electronics Rubber gasket Sensor cover Plug Sampling tube Collar PowerDirty TroubleAlarm LEDs Smoke Sensor Fastener (2X) Controller cover Conduit nuts ( field supplied ) Conduit support plate Cover gasket (ordering option) ...
Page 4 - EQUIPMENT DAMAGE HAZARD; CAUTION; Comfort; Supply and Return Sensor Tube
4 10. Mount the sampling tube support bracket to the cross member with two 1/4AB-14 5/8-in. screws (P/N AL48AM307) as shown in Fig. 5. Insert large snapbushing (P/N HY93NH085) into hole in bracket. 11. Slide sampling tube into bracket. (See Fig. 4.) Pull the sampling tube so that the locking collar ...
Page 5 - Link Units; Supply Air Smoke Detector Installation; ELECTRICAL SHOCK HAZARD; Failure to follow this warning could result in personal; Find the 2 plugs located in the blower side plate. Remove
5 SAMPLING TUBESUPPORT BRACKET C07176 Fig. 5 --- Sampling Tube Support Bracket CUT OFF CONNECTOR, LABELED TB3-5, ON ORN WIRE PL19 C07177 Fig. 6 --- Return and Supply Air Smoke Detector Wiring on Comfort Link Units Supply Air Smoke Detector Installation (CRSMKSUP001D00) The supply air smoke detector ...
Page 7 - IMPORTANT
7 6. Slide the sampling tube collar over the sampling tube until the tabs lock into the tube. 7. Slide sampling tube into smoke detector with eight slots. Make sure sampling tube holes are aligned facing UP. 8. Insert plug into far end of the sampling tube.9. Place rubber gaskets over each sampling ...
Page 8 - Configuring the; Link; ENTER; OPERATION
8 SMOKE DETECTOR WIRE TIES C07180 Fig. 9 --- Supply Smoke Detector Location and Wire Routing (Top View) AS SHOWN TO PLUG ROUTE RJ-45 HARNESS ALONG SUPPLY SMOKE DETECTOR THRU BOX, AND OUT SMOKE POWER HARNESS PUNCH OUT KNOCK OUT INSTALL CONTROL MODULE HEREUSING THREE SCREWS RJ-45 HARNESS CUT TAPE BEFO...
Page 9 - MAINTENANCE; Cleaning Procedure; FLASHES; Controller Tests
9 The smoke detector contains a photoelectric detector approvedfor an extended air speed range of 100 to 4000 feet per minute and an operational temperature range of -4 _ to 158 _ F. Do not operate the smoke detector out of these ranges.The smoke detector operates on 24 vac, 120 vac, or 220/240 vac....
Page 10 - TROUBLESHOOTING; Dirty LED
10 To perform a controller alarm test: 1. Press the controller’s test/reset switch for seven seconds. Verify that the controller’s Alarm LED turns on. 2. After performing a controller alarm test, reset the sensor by pressing the test/reset switch for two seconds. Verifythat the controller’s Alarm LE...