Page 2 - ENGLISH; IR Remote Control; Contents; Page; Indoor unit
4 2 P Q VSplit system “Hi-Wall” indoor unit GB - 1 ENGLISH IR Remote Control “Room Controller” “Zone Manager” The unit can be used with infrared Remote Control, with the Carrier “RoomController” or “Zone Manager”.Infrared control installation instructions are contained in the unit instruction andmai...
Page 3 - Dimensions and weight; Table I: Nominal data; Table II: Operating limits
4 2 P Q V GB - 2 Dimensions and weight Table I: Nominal data • Unit is not suitable for operation in laundry premises. • For sizing of power supply wires and delay type fuses, refer to the outdoor unit installation instructions. Mod. 42PQV050 / 42PQV080 A mm 1080 B mm 285 C mm 185 kg 14 ELECTRIC POW...
Page 4 - Table lIl: Material supplied; Table IV: Accessories
4 2 P Q V GB - 3 E N G L I S H Minimum clearances (mm) Obstacle 90 min. 200 min. 100 min. 1900 min. The following field-supplied items are required to complete the installation. Name Specification 42PQV050: Ø (1/2”) 12,70 mm (Gas) / Ø (1/4”) 6,35 mm (Liquid) Connection pipe 42PQV080Ø (5/8”) 15,87 mm...
Page 5 - Unit installation; General information; Choosing the installation site
GB - 4 4 2 P Q V Unit installation Read this instruction manual thoroughly before starting theinstallation. • This unit complies with low-voltage (EEC/73/23) and electro- magnetic compatibility (EEC/89/336) directives. • The installation must be carried out by a qualified installer. • Follow all cur...
Page 7 - Installation; Installing the wall hanging bracket
GB - 6 4 2 P Q V Installation • Before installing the wall hanging bracket, remove it from the unit by pushing at the indicated parts at the bottom of the body. • Fasten the wall hanging bracket to the wall with 4 or more screw anchors through the holes near the outer edge of the bracket. • Install ...
Page 9 - Refrigerant connections
GB - 8 4 2 P Q V Refer to the outdoor unit installation manual for tube sizing,and limitations (slope, length, number of bends allowed,refrigerant charge, etc.). For refrigerant tubes use seamless, insulated refrigeration gradetube, (Cu DHP type according to ISO1337), degreased anddeoxidized, suitab...
Page 10 - Check; Use of additional screws
GB - 9 4 2 P Q V E N G L I S H Check • Next, check the unit drain system by pouring some water into the unit drain pan and ensuring that it flows freely through thedrain hose and that there is no leakage from any other part. Use of additional screws After installation, if there is a significant gap ...
Page 11 - Indoor unit wiring; Electrical connection
GB - 10 4 2 P Q V Indoor unit wiring • Lift the front panel up to the top of the unit; in this way the front panel will be separated from the unit. • Remove the plastic cover of the terminal board.• Make the electrical connections to the terminal board as per the wiring diagram. • When the electrica...
Page 12 - address selector and fault code; Operating test; Fault code
GB - 11 4 2 P Q V E N G L I S H Operating test, address selector and fault code Operating test • Perform the operating test after the units have been installed in position and the gas leak test has been completed. • Check all electrical connections (instructions and wiring diagram). • Insert the bat...
Page 13 - Fault code and guide for the owner; Guide for the owner
GB - 12 4 2 P Q V Table VI: Fault code Code Description 2 Condensate Pump Failure or water drain Failure 3 Indoor unit Room Air sensor fault 4 Indoor unit Tc Coil sensor fault 10 Indoor unit software fault (EEProm Corrupt) 12 Indoor unit software fault (Address / Zone Corrupt) 14 Loss of Signal From...