Page 2 - Table of contents; Page
2 Fan wheels are designed to provide low operating costs The forward-curved, centrifugal, double-inlet fans are statically and dynamically balanced at the factory tominimize transmission of vibration to the building structure. The belt-driven motor (single or three phase) has a variable-pitch pulley...
Page 3 - Physical data; Model number nomenclature
3 Physical data UNIT SIZE 42BHC, BVC 06 08 10 12 16 20 30 40 NOMINAL CFM 600 800 1000 1200 1600 2000 3000 4000 42BHC SHIPPING WT (lb) (no heat/ with heat) 203/234 205/236 253/287 256/290 312/346 344/380 437/474 553/590 42BVC SHIPPING WT (lb) (no heat/ with heat) 200/231 202/233 243/277 247/281 289/3...
Page 4 - 2BHC, BVC OPTIONS AND ACCESSORIES; Factory-installed options; Options and accessories
4 42BHC, BVC OPTIONS AND ACCESSORIES *Factory-installed option. †Field-installed accessory. The 42BHC and 42BVC fan coil units are designed tooffer maximum flexibility in an application, accessibility forservice, quiet operation and durability. Factory-installed options Automatic air vents — Automat...
Page 5 - Thermostats —; THERMOSTAT FUNCTIONS; Valve packages —
5 Thermostats — Three thermostats are available for field installation:Honeywell T834C manual changeover, single-stage heatthermostat features:• off-cool-heat system switch• on-auto fan mode switch• single-stage electric heat• outside air signalHoneywell T8500 digital, automatic/manual changeover,2-...
Page 6 - Base unit dimensions
6 Base unit dimensions 42BHC FAN COIL BASE UNIT (NO CONTROLS) NOTES: 1. All dimensions are in inches (± 1 / 4 in.). 2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to change without notice. 3. Right hand shown,...
Page 7 - 2BHC FAN COIL WITH MOTOR CONTROL OPTION
7 42BHC FAN COIL WITH MOTOR CONTROL OPTION NOTES: 1. All dimensions are in inches (± 1 / 4 in.). 2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to change without notice. 3. Right hand shown, left hand opposite...
Page 8 - 2BHC FAN COIL WITH ELECTRIC HEAT OPTION
8 Base unit dimensions (cont) 42BHC FAN COIL WITH ELECTRIC HEAT OPTION NOTES: 1. All dimensions are in inches (± 1 / 4 in.). 2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to change without notice. 3. Right ha...
Page 10 - 2BVC FAN COIL WITH MOTOR CONTROL OPTION
10 NOTES: 1. All dimensions are in inches (± 1 / 4 in.). 2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications aresubject to change without notice. 3. RH shown, LH opposite.4. Hanger rods, which are field-supplied, are shown for...
Page 11 - 2BVC FAN COIL WITH ELECTRIC HEAT OPTION
11 42BVC FAN COIL WITH ELECTRIC HEAT OPTION NOTES: 1. All dimensions are in inches (± 1 / 4 in.). 2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to change without notice. 3. Right hand shown, left hand opposit...
Page 14 - Accessory dimensions; TOP VIEWS; MIXING BOX
14 Accessory dimensions 3 A C 2.4 4 H 2.4 3 1 2 2 W B TOP VIEWS BOTTOM/REAR INLET TOP/REAR INLET RIGHT HAND SIDE VIEWS W 4 2.4 C 1 H A A B A 2.4 MIXING BOX NOTE: All dimensions in inches. 42BHC,BVC UNIT SIZE DIMENSIONS (in.) H W A B C 06 18.5 28 6 24 11 08 18.5 28 6 24 11 10 20.25 37 8 33 13 12 20.2...
Page 15 - MIXING BOX RAILS
15 1 W D 3 A 1 FRONT VIEW SIDE VIEW MIXING BOX RAILS NOTE: All dimensions in inches. UNIT DIMENSIONS (in.) W D A 42BHC06 28 51.6 16.1 42BHC08 28 51.6 16.1 42BHC10 37 55.2 18.1 42BHC12 37 55.2 18.1 42BHC16 47 55.4 18.1 42BHC20 48 57.8 18.1 42BHC30 48 59.8 20.1 42BHC40 62 63.0 20.1 UNIT DIMENSIONS (in...
Page 16 - VALVE PACKAGES; Basic —; Basic valve package includes 2 or 3-way; Deluxe —; Deluxe valve package includes a circuit
16 Accessory dimensions (cont) A A B B D C F F E E D C VALVE PACKAGES NOTE: All dimensions in inches. CONTROL VALVE PIPING PACKAGE SIZE A B C D E F Cv CLOSE OFF Normal Close Off Spring Return 2-way 1 / 2 in. 12.45 2.285 — — 15.25 7.41 3.5 25 psig 3 / 4 in. 12.71 3.156 — — 17.71 7.936 5 20 psig 1 in....
Page 17 - PIPING CONNECTION LOCATION DIAGRAM*
17 C D HWS B A 2 (51) RH Tell-Tale Drain LH Tell-Tale 0 CWS CWR HWR 1-5/ 8 (41) ) 4 6 2( 8/ 3- 0 1 E F ) 9 1 2( 8/ 5- 8 H G ) 5 7 1( 8/ 7- 6 0 PIPING CONNECTION LOCATION DIAGRAM* LEGEND *Right-hand unit with re-heat coil shown. CWR — Cold Water Return CWS — Cold Water Supply HWR — Hot Water Return H...
Page 19 - Basic definitions; Unit hand —; When facing the supply air outlet from the; DESCRIPTION; Application data; UNIT HAND
19 Basic definitions Unit hand — When facing the supply air outlet from the front of the unit (air blowing in your face), your right handwill be the right hand side of the unit and your left hand theleft hand side of the unit. PIPING COMPONENTS LEGEND *Check all system component pressure ratings (co...
Page 21 - Consult factory for normally open
21 PIPING COMPONENTS (cont) LEGEND NOTES:1. Motorized spring return 2-way valves have a maximum close-off differential of 25 psi.2. Motorized spring return 3-way valves have a maximum close-off differential of 25 psi. SYMBOL/SKETCH DESCRIPTION C V FACTOR RATING 1 / 2 3 / 4 1 PSI F 2-WAY MOTORIZED VA...
Page 22 - Selection procedure
22 This selection procedure provides a guide to determineunit performance of the 42BHC, BVC units. Capacitytables (in Performance Data) are based on nominal cfm.Correction factors are provided for other operating condi-tions as explained in the following selection example. For applications outside t...
Page 23 - Performance data
23 42BHC,BVC AIRFLOW CORRECTION FACTORS NOTE: Use Sensible Heat correction factors when calculating heatingcapacity. DIRECT EXPANSION (DX) CORRECTION FACTORS Consult factory for values outside of table.DX Total Capacity (MBtuh) = Base Et x Total Correction FactorDX Sensible Capacity (MBtuh) = Base E...
Page 24 - 2BHC, BVC NOMINAL COOLING CAPACITIES; 2BHC,BVC NOMINAL HEATING CAPACITIES
24 42BHC, BVC NOMINAL COOLING CAPACITIES LEGEND *Based on entering air temperature of 67 F wb, 80 F db and temperature rise of 10 degrees F. NOTE: All ratings at sea level. Ratings in accordance with ARI (Air Conditioning &Refrigeration Institute). 42BHC,BVC NOMINAL HEATING CAPACITIES NOTES: 1. ...
Page 30 - UNIT HORSEPOWER DATA TABLE
30 UNIT HORSEPOWER DATA TABLE LEGEND NOTES: 1. Contact factory if higher horsepower selection is required for a given cfm and total static pressure. 2. The variable pitch motor sheave provided will allow + 15% rpm adjustment. Unit sizes 06, 08, 10 and 12 have 3 / 4 in. bore fan sheaves. Unit sizes 1...
Page 32 - Hydronic coil pressure drop —; Cv FACTOR BY COIL AND UNIT SIZE
32 42BHC,BVC COMPONENT STATIC RESISTANCE (in. wg) Hydronic coil pressure drop — All of the factory’s hy- dronic coils have a coefficient of velocity (Cv) resistancefactor assigned to assist in a more accurate determinationof water pressure drop (see Cv Factor by Coil and Unit Sizetable below). Calcu...
Page 33 - SOUND POWER DATA
33 42BHC,BVC WATER PRESSURE DROP (ft. wg) FOR CV FACTOR AND WATER FLOW RATE (GPM) NOTE: Table interpolation is permissible, and extrapolation is not rec-ommended. SOUND POWER DATA DISCHARGE SOUND RATINGS — A-WEIGHTED SOUND POWER LEVEL RATINGS* (dB) *These noise ratings are calculated values, not act...
Page 34 - Typical wiring schematics; MOTOR CONTROL/DISCONNECT OPTION SINGLE-PHASE POWER
34 Typical wiring schematics BASE UNIT, SINGLE-PHASE POWER MOTOR CONTROL/DISCONNECT OPTION SINGLE-PHASE POWER
Page 35 - MOTOR CONTROL/DISCONNECT OPTION THREE-PHASE POWER
35 BASE UNIT, THREE-PHASE POWER MOTOR CONTROL/DISCONNECT OPTION THREE-PHASE POWER
Page 36 - FAN OPERATION AND HONEYWELL DIGITAL THERMOSTAT
36 Typical wiring schematics (cont) 2-PIPE COOLING ONLY WITH SINGLE-SPEED FAN OPERATION AND HONEYWELL THERMOSTAT 2-PIPE OR 4-PIPE HEATING/COOLING WITH SINGLE-SPEED FAN OPERATION AND HONEYWELL DIGITAL THERMOSTAT NOTES: 1. Optional valves are field wired.2. No HW valve with electric heat. NOTES: 1. Op...
Page 37 - Electrical data
37 42BHC,BVC ELECTRIC HEATER DATA AVAILABILITY 42BHC,BVC ELECTRIC HEATER DATA LEGEND NOTES: 1. Stages available: Single phase: 1-12 kW, 1 stage only 3-12 kW, 1 stage or 2 stage Three phase: 1-40 kW, 1 stage only 4-40 kW, 1 or 2 stage12-40 kW, 1, 2 or 3 stage 2. Electric Heating Capacities (Btuh) = H...
Page 38 - Electric heat options:; †No control fusing necessary.; Controls
38 Standard control features • 4 in. x 4 in. junction boxNOTE: Motor leads are wired to the 4 in. x 4 in. junctionbox, mounted on the external panel. Field verification ofthe motor rotation is required on 3-phase applications. Motor control options • Interlocking disconnect switch*• 24-v class 2 tra...
Page 39 - System Fan Coil Unit; HVAC Guide Specifications — 42B; Guide specifications
39 System Fan Coil Unit HVAC Guide Specifications — 42B Size Range: 600 to 4000 Nominal Cfm Carrier Model Number: 42BHC (Horizontal Fan Coil Unit) 42BVC (Vertical Fan Coil Unit)Part 1 — General 1.01 SYSTEM DESCRIPTION Horizontal and vertical, 2-pipe or 4-pipe, belt-driven, galvanized casing model fa...