Page 2 - City Hall; RHT Energy Solutions; Disclaimer
City Hall 20 E. Main St., Ashland, Oregon RHT Energy Solutions Page 2 Disclaimer In no event will RHT Energy Solutions be liable for (i) the failure of the customer to achieve the estimated energy savings, and/or any other estimated benefits included herein, or (ii) for any damages to customer’s sit...
Page 3 - Contacts and Preparation
City Hall 20 E. Main St., Ashland, Oregon RHT Energy Solutions Page 3 Contacts and Preparation SITE CONTACTS The following City of Ashland personnel assisted with this project: Adam Hanks Project Manager City of Ashland 20 E. Main St. Ashland, OR 97520 TEL: (541) 552-2046 Email: [email protected] EN...
Page 4 - Contents; Existing Equipment
City Hall 20 E. Main St., Ashland, Oregon RHT Energy Solutions Page 4 Contents Contacts and Preparation .............................................................................................................................. 3 Contents .....................................................
Page 5 - Executive Summary; kWh
City Hall 20 E. Main St., Ashland, Oregon RHT Energy Solutions Page 5 1.0 Executive Summary RHT Energy Solutions (RHT) was contracted by the City of Ashland to perform energy audits on its municipal facilities. On February 27, 2013, Buzz Thielemann and Rick Reichert of RHT conducted an energy scopin...
Page 9 - Energy Efficiency Measures; Note strobing effect of using magnetic
City Hall 20 E. Main St., Ashland, Oregon RHT Energy Solutions Page 9 3.0 Energy Efficiency Measures Following are the capital energy efficiency measures that were identified. Note that several low cost/no cost measures were also identified (see Section 1.4), as were two capital improvements that we...
Page 11 - IBM Endpoint Manager for Power Management; Unlimited; floor
City Hall 20 E. Main St., Ashland, Oregon RHT Energy Solutions Page 11 To further conserve energy and reduce annual energy costs, a City-wide policy should be established to turn off all desktop computer monitors before leaving the building. Power management software is available from several vendor...
Page 12 - , with an outdoor temperature of; floor thermostat was set to; Oil filled combination convection / radiation desk
City Hall 20 E. Main St., Ashland, Oregon RHT Energy Solutions Page 12 Low cost/no cost Recommendation 1: Establish new City portable heater policy: A City policy on the use of portable heaters should be established immediately, and the use of all existing portable heaters should be stopped immediat...
Page 13 - Low Cost/No Cost Recommendation 2: Install Lock Box on 1; floor thermostat was set to run continuously.
City Hall 20 E. Main St., Ashland, Oregon RHT Energy Solutions Page 13 Because there is a wide variance in thermal comfort with all people, a wise choice would be to require the use of radiant flat-panel vanity/desk heaters with input power of 200-400 Watts each. Experience has shown that the smalle...
Page 14 - Potential Capital Improvements; Infrared image shows heat
City Hall 20 E. Main St., Ashland, Oregon RHT Energy Solutions Page 14 Low Cost/No Cost Recommendation 3: Install occupancy sensors or simple mechanical timers to restroom lighting: This will ensure that non-priority lights do not remain on when not in use. Be sure to use program-start ballasts (not...
Page 15 - Inside Film
City Hall 20 E. Main St., Ashland, Oregon RHT Energy Solutions Page 15 #1: Add R12 insulation to areas of the exterior walls that are inadequately insulated . With the exception of the relatively new addition in the corner of the 2 nd story, City Hall walls are inadequately insulated. This table sho...
Page 17 - General Facility Data
City Hall 20 E. Main St., Ashland, Oregon RHT Energy Solutions Page 17 9.0 General Facility Data Operating hours: Typically 7am to 6pm, Monday – Friday with occasional evening usage of meeting rooms. Domestic hot water: An instant water heater was observed under the sink on the 2 nd floor break room...
Page 18 - Electric meter number:
City Hall 20 E. Main St., Ashland, Oregon RHT Energy Solutions Page 18 Roofing: Membrane over 3-inch foam insulation (estimated). Exterior Lighting: Assumed to be high-pressure sodium (HPS) on daylight sensor control. Electric meter number: 14292 Natural Gas meter number: 123710 (serves the back-up ...
Page 19 - Additional pictures; Ton Heat Pump on Roof
City Hall 20 E. Main St., Ashland, Oregon RHT Energy Solutions Page 19 10.0 Additional pictures 1.5 Ton Heat Pump on Roof Two 4 Ton Heat Pumps on roof Stationary Heat Pump Condenser Fan Heat Pump #4 on shed roof (Large air handler is inside shed)
Page 20 - Stand
City Hall 20 E. Main St., Ashland, Oregon RHT Energy Solutions Page 20 Stand ‐ by generators
Page 22 - Appendix A – Energy Data
Page 23 - Energy Data - City Hall - Electricity Only
Energy Data - City Hall - Electricity Only Meter #: 14292 / 01 720 643 Months 24 Converted to kBTU 375,430 Square Feet 8,443 Average Annual EUI 44.466 Start Date End Date Days in Period kWh $ Avg $/kWh 10/08/2012 11/07/2012 30 7,640 563.43 $ 0.0737 09/10/2012 10/08/2012 28 7,240 539.84 $ 0.0746 08/0...
Page 29 - Appendix C – Energy Efficiency Measures
Page 38 - Replace single-paned windows at City Hall; City Hall baseline electricity usage per year: 110,000 kWh; Estimated annual energy savings:
Replace single-paned windows at City Hall Estimated Project Cost: $34,000 City Hall baseline electricity usage per year: 110,000 kWh Estimated % energy savings: 5% Estimated annual energy savings: 5,500 kWh City Hall electricity cost / kWh: $0.0678 Estimated annual cost savings: $373 Simple Payback:...
Page 39 - Appendix F – Existing Equipment Data Sheets
Page 40 - replacement; Heat pump uniqueness; Heat Pump Systems
Copyright 2001 Carrier Corporation Form 38AQS-5PD Heat Pump Heat Pump Systems that SaveEnergy and Provide Outstanding Heating and Cooling All Year• All-season comfort in any climate• High energy savings capability• Suitable for new construction or replacement Features/Benefits System indoor and outd...
Page 41 - 8AQS application versatility; Latest safety standards for; Cooling mode —; During cooling, the; Heating mode —; 6D COMPRESSOR
2 surrounding air (even outside air at ex-tremely cold temperatures), and ends with the indoor coil releasing or reject-ing heat to the air around it. Variable refrigeration circuit-ing (VRC) — 38AQS units For that extra measure of heat pump performance, variable refrigeration cir-cuiting provides i...
Page 42 - Table of contents
3 Easy installation and service — The 40RMQ multiposition designand component layout help you to get the unit installed and running quickly. The direct-expansion (DX) coils have factory-installed thermostatic expan-sion valves (TXVs) with matching dis-tributor nozzles. All 40RMQ units also include f...
Page 43 - Model number nomenclature; Quality Assurance
4 Model number nomenclature 38AQS 008 – – – 5 0 1 – – 38AQS — Split System Heat Pump – – — Not Used Nominal Tons Packaging 008 — 7-1/2 Tons 0 — Base Unit 012 — 10 Tons 1 — Domestic 016 — 15 Tons Revision Number – – — Not Used 0 — Original – — Aluminum (Standard) 1 — 575-3-60 (Sizes 012,016 Only) C —...
Page 53 - Standard Efficiency
Single-package standard efficiencyrooftop heat pumps with: • State-of-the-art defrost system • Dependable 4-way valve operation • Refrigerant filter strainer and accumulator • Field-installed electric heaters available • Advanced hermetic compressors mounted on vibration isolators • Factory-installe...
Page 56 - ARI* capacity ratings
ARI* capacity ratings UNIT 50TJQ NOMINAL TONS STANDARD CFM COOLING HEATING (High Temp) SOUND RATING (Bels) Capacity (Btuh) SEER† Capacity (Btuh) HSPF Belt Drive Direct Drive 004 3 1200 35,600 10.20 10.00 34,400 6.7 8.4 005 4 1600 46,500 10.00 9.70 46,500 7.0 8.0 006 5 2000 57,000 10.00 9.90 57,000 7...
Page 57 - Product Data; FEATURES
MODEL PH1010 SEER 3 PHASE HEAT PUMP UNITSIZES 048, 060 — 4 AND 5 NOMINAL TONS Product Data FEATURES AVAILABLE Nominal sizes are available in 048 and 060 sizesto meet the needs of light commercial applications. EFFICIENCY: With SEER of at least 10.0 and HSPF of 7.0, theseheat pump systems provide eco...
Page 59 - SPECIFICATIONS
—3— PH10 SPECIFICATIONS * The ampacity of non-metallic (NM) sheathed cable shall be that of 60°C (140 ˚ F) conductors per NEC 1999, Article 336-26. If wire used is other than specified in chart, refer to applicable tables available in 1999 NEC. Copper wire must be used from disconnect to unit. † Len...
Page 60 - REFRIGERANT METERING DEVICE AND LINE SET DATA; OPTIONAL EQUIPMENT USAGE GUIDELINE
—4— PH10 REFRIGERANT METERING DEVICE AND LINE SET DATA * Piston listed is for any approved coil combination. † Charging subcooling for indoor TXV-type expansion device. . OPTIONAL EQUIPMENT USAGE GUIDELINE * For tubing line sets between 80 and 200 ft (250 ft total equivalent length), refer to the Re...
Page 62 - COMBINATION RATINGS
—6— PH10 COMBINATION RATINGS * Outdoor section/indoor section combination tested in accordance with DOE test procedures for heat pumps. Ratings for other combinations are determined under DOE computer simulation procedures. † In most cases, only 1 method should be used to achieve TDR function. Using...
Page 63 - DETAILED COOLING CAPACITIES*
—7— PH10 DETAILED COOLING CAPACITIES* See notes on page 8. EVAP AIR CONDENSER ENTERING AIR TEMPERATURES °F 85 95 105 115 CFM EWB Capacity MBtuh† Total Sys kW** Capacity MBtuh† Total Sys kW** Capacity MBtuh† Total Sys kW** Capacity MBtuh† Total Sys kW** Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡...
Page 64 - DETAILED COOLING CAPACITIES* Continued
—8— PH10 DETAILED COOLING CAPACITIES* Continued EVAP AIR CONDENSER ENTERING AIR TEMPERATURES °F 85 95 105 115 CFM EWB Capacity MBtuh† Total Sys kW** Capacity MBtuh† Total Sys kW** Capacity MBtuh† Total Sys kW** Capacity MBtuh† Total Sys kW** Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ PH10PR060-...
Page 65 - HEAT PUMP HEATING PERFORMANCE
—9— PH10 HEAT PUMP HEATING PERFORMANCE See notes on page 10. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES °F –3 7 17 27 37 47 57 67 EDB CFM Capacity MBtuh† Total Pwr Capacity MBtuh† Total Pwr Capacity MBtuh† Total Pwr Capacity MBtuh† Total Pwr Capacity MBtuh† Total Pwr Capacity MBtuh† Total Pwr...
Page 66 - HEAT PUMP HEATING PERFORMANCE Continued; SYSTEM DESIGN
— 10 — © Payne Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231 Printed in U.S.A. edition date: 3/06 Catalog No. SS-PH10-09 Manufacturer reserves the right to change, at any time, specifications or designs without notice and obligations Replaces: SS-PH10-08 HEAT PUMP HEATING P...