Page 4 - Parts List; Table 1 – Installation Materials; SYSTEM REQUIREMENTS; Table 3 – Maximum Refrigerant Line Lengths; Table 4 – Pipe Sizes
4 These installation instructions cover the installation of the matchedsystems listed in table 2. Parts List Indoor Unit The following items are included with the indoor unit: Table 1 – Installation Materials Description Qty Usage Wall Mounting Bracket 1 For Indoor Unit Installation Screws, 4XL10 2 ...
Page 5 - Refrigerant Charge; Metering Device; Power and Connecting Cables -- Field Supplied; Control Wiring; User Interface
5 Refrigerant Charge The 38HDF and 38QRF units can be matched with multiple outdoor units and thus additional charge might be required whenmatched with the 40QNC or 40QNQ units. Table 6 – Additional Charge Additional Charge lb (kg) Unit Size 38HDF 38QRF 018 1.2 (0.55) 0.8 (0.36) 024 1.0 (0.45) 0.5 (...
Page 6 - INSTALLATION; Unpack Unit; Consider System Requirements; Refrigerant Line Routing
6 INSTALLATION Complete Pre--installation Checks 1. Unpack Unit -- Store the indoor and outdoor units in the original packaging until it is moved to the final site for in-stallation. 2. Inspect Shipment -- Upon receipt of shipment, check the indoor and outdoor units for damage. If there is any dam- ...
Page 7 - Side Or Bottom Piping; INSTALL OUTDOOR UNIT; Mounting on Ground; CAUTION
7 point A or B as shown in Fig. 12 or Fig. 13. Drill the hole at aslope so that the outside end is 1/2 inch (13 mm) lower than inside end to ensure optimal drainage. Refer to Fig. 14. Side Or Bottom Piping Remove the knockout in the unit and drill a 2--1/2 inch (63.5 mm)hole where the pipe penetrate...
Page 8 - Mounting Unit on Wall; Complete Outdoor Refrigerant Piping Connec-; Connection at Outdoor Unit; UNIT DAMAGE HAZARD
8 Mounting Unit on Wall The units can also be mounted on the wall using the accessory mounting kit. Complete Outdoor Refrigerant Piping Connec- tions Follow the following general guidelines: 1. Use refrigerant grade field – supplied tubing. Refer to Table 4 for the correct line sizes. 2. Do not use ...
Page 9 - Complete Outdoor Power and Control Wiring; WARNING; Power Wiring
9 38QRF Units 1. Assemble the connector tubes to the factory supplied filter drier by brazing the factory supplied flare connectors to theinlet and outlet for the filter drier (see Fig. 19) A09507 Fig. 19 -- 38QRF018--036 Connector Tube Assembly 2. Perform step 2 and 3 from the 38HDF section.3. Remo...
Page 10 - Make sure you have enough control wires to cover the dis-; NOTE
10 Control Wiring The control circuit is 24 volts AC (minimum 40VA) supplied fromthe indoor unit. 1. Make sure you have enough control wires to cover the dis- tance between the indoor and outdoor unit. 2. Route one end of the control wiring through the opening provided in the unit side panel and con...
Page 16 - Run Power Wiring for Indoor Unit; ELECTRICAL SHOCK HAZARD; Install All Power, Interconnecting Wiring, Piping and
16 Run Power Wiring for Indoor Unit Be sure field wiring complies with local building codes and NEC,and unit voltage is within limits shown in Table 11.Contact local power company for correction of improper line voltage. ! WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result i...
Page 17 - USER INTERFACE; Unit Configuration; Wired Control
17 A W a ll H a nging B ra cket H ook H ole R eta iner C lip R eta iner C lip B UNIT SIZE DIMENSION A B 40QNC01824 13.4 10.6 40QNC030 12.2 12.2 40QNC036 12.2 12.2 40QNQ018 13.4 10.6 40QNQ024 13.4 10.6 40QNQ030 12.2 12.2 40QNQ036 12.2 12.2 A08365 Fig. 29 -- Wall Mounting Details 8. If the refrigerant...
Page 19 - Zone Manager; Manager to the communication board.
19 Zone Manager If a Zone Manager is required, the following steps should beperformed at the same time the indoor control and power wiring are being connected: 1. Plug the communication board to the J8 as shown in Fig. 332. Connect one end of the wire harness supplied with the Zone Manager to the co...
Page 20 - Outdoor Unit; Service Valve; Deep Vacuum Method; MINUTES; MI
20 START--UP Preliminary Checks 1. Check condensate drainage system; on the opposite side of the drain connection, insert a water bottle up into the fancoil unit and fill the drain pan. Water must flow steadily; if not, check the pipe slope or inspect for any pipe restrictions. 2. Make sure all wiri...
Page 21 - Test Mode Sequence of Operation
21 Triple Evacuation Method The triple evacuation method should only be used when vacuum pump is only capable of pumping down to 28 in. of mercuryvacuum and system does not contain any liquid water. Refer to Fig. 37 and proceed as follows: 1. Pump system down to 28 in. of mercury and allow pump to c...
Page 22 - SERVICE; Filter Drier; Refrigerant Charging
22 SERVICE ! WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death.Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch w...
Page 23 - TROUBLESHOOTING; See Table 12 and Table 13 for troubleshooting information.; Fault Code; Table 13 – Troubleshooting
23 TROUBLESHOOTING See Table 12 and Table 13 for troubleshooting information. Fault Code Once a failure occurs with the indoor unit in operation, the green LED on the indoor unit flashes at intervals of 0.5 seconds. The fault code is deduced from the number of times the green LED flashes, blocking u...