Page 2 - ENGLISH; Table I; Contents; ATTENTION INSTALLERS AND SERVICE TECHNICIANS!
38GL...G / 38GLS...G / 38YY...G / 38YYS...G Cooling only and heat pump split system outdoor units GB - 1 ENGLISH Cooling only(A/C) Heat pump (H/P) Hi-Wall series Hi-Wall series Console series Cassette series Satellite Power Cooling only Heat pump “42PHQ---N” “42HMC---N” “42VMC---N” “40KMC---N” “40SM...
Page 3 - Dimensions and weight; Connections; Table II: Connections
GB - 2 38GL...G / 38GLS...G / 38YY...G / 38YYS...G R-410A Dimensions and weight Mod. 38GL(S)018G, 024G Mod. 38YY(S)018G Mod. 38GL-028G, 036G Mod. 38YYS024G Mod. 38YY-024G, 028G, 036G E E D B C F A E E D B C F A E E D B C F A 햲 Outdoor unit 햳 Indoor unit 햴 Height difference Connections All fittings a...
Page 4 - Minimum clearances; System charge
E - 3 GB - 3 E N G L I S H 38GL...G / 38GLS...G / 38YY...G / 38YYS...G R-410A Minimum clearances B A C D E System charge Model Refrigerant Suitable up to Extra charge Extra charge (g) with indoor unit charge (g) m g/m 42VMC---(A)N 40SMC---N 38GL(S)018G 1090 8 15 – – 38GL(S)024G 1265 8 15 220 150 38G...
Page 5 - Choosing the installation site; General information; Unit installation
GB - 4 38GL...G / 38GLS...G / 38YY...G / 38YYS...G • Carefully recover refrigerant within this unit before final disposal or when servicing. Never vent refrigerant to atmosphere.Use approved recovery equipment for R-410A refrigerant.Do not use R-22 equipment. Choosing the installation site Positions...
Page 7 - Refrigerant connections
GB - 6 38GL...G / 38GLS...G / 38YY...G / 38YYS...G R-410A Refrigerant connections Charge liquid-no gas. Copper tubes during storage. Use tools designed for R-410A higher pressure.Keep inside clean. 2-stage vacuum pump. Replace oil regularly. No moisture.No dust. No leak.No mineral oil. Neat. Dry nit...
Page 8 - Connection to unit; Flaring the ends of the tubing
E - 7 GB - 7 E N G L I S H 38GL...G / 38GLS...G / 38YY...G / 38YYS...G R-410A The unit can be installed: 햲 on the floor; 햳 on the wall using the bracket kit. Connect tubing in accordance with the limits shown on Table II(Connections).Finger-tighten the fitting several turns, then tighten it with a w...
Page 9 - Air purging; Table III: Operating limits
GB - 8 38GL...G / 38GLS...G / 38YY...G / 38YYS...G Refrigerant connections m Pipe n Pipe insulation o Fastening tape m n o Air purging Use only a vacuum pump to purge air from the piping. NEVER use the system compressor as a vacuum pump. NEVER use the unit refrigerant gas to purge the connectingpipe...
Page 10 - Cooling only unit; 쐋 쐏; Heat pump unit; 쐋 쐏; Heat pump system; Electrical connections
E - 9 GB - 9 E N G L I S H 38GL...G / 38GLS...G / 38YY...G / 38YYS...G R-410A Cooling only unit Cooling only system 쐃 쐇 230V ~ 50Hz R C Y O W 2 R Y C S L N 쐋 쐏 햳 햲 햲 Power supply cable (H07 RN-F) 햳 Interconnection cable (A07 RN-F) 쐃 Indoor unit 쐇 Outdoor unit 쐋 Main switch 쐏 Time-delay fuse or circu...
Page 11 - Table IV: Electrical data; Unit
GB - 10 38GL...G / 38GLS...G / 38YY...G / 38YYS...G R-410A Electrical connections Notes: 1. Unit is suitable for outdoor installation.2. Data referred to the outdoor unit only.3. Starting current duration is usually lower than 1 sec.4. Wire size shown applies to line length up to 15 m.5. If the indo...
Page 12 - Pump Down and refrigerant circuit
E - 11 GB - 11 E N G L I S H 38GL...G / 38GLS...G / 38YY...G / 38YYS...G Pump Down and refrigerant circuit Pump-down Pump-down is an operation intended to collect all the systemrefrigerant in the outdoor unit.This operation must be carried out before disconnecting therefrigerant tubing in order to a...
Page 13 - Troubleshooting; Guide for the owner; Unit maintenance, troubleshooting and guide for the owner; Unit maintenance
GB - 12 38GL...G / 38GLS...G / 38YY...G / 38YYS...G R-410A Troubleshooting Compressor and fan of the outdoor unit will not start:• Unit not energized; check the mains power connections.• Main switch OFF; check and put to the ON position.• Main switch fuses have blown; replace.• Wait for 3 minutes; c...