Page 2 - INSTALLATION GUIDELINE; Replacement /Retrofit – R22 to Puron
2 INSTALLATION GUIDELINE Replacement /Retrofit – R22 to Puron ® Split system heat pumps are intended to be installed with matching indoor sections only. The 38AUQ heat pump outdoor units are matched only with same-size 40RUQ indoor sections. Existing R-22 indoor coils cannot be converted to R-410A h...
Page 7 - INSTALLATION; Fig. 4 — Service Clearance Dimensional Drawing; UNCRATE UNIT —; CONSIDER SYSTEM REQUIREMENTS; RIGGING —; UNIT DAMAGE HAZARD
7 . INSTALLATION Jobsite Survey Complete the following checks before installation. 1. Consult local building codes and the NEC (National Electrical Code) ANSI/NFPA 70 for special installation requirements. 2. Determine unit location (from project plans) or select unit location. 3. Check for possible...
Page 8 - REFRIGERANT LINE SIZING —; Table 3 — Maximum Vertical Separation*
8 Table 2 — 38AUQ*07-12 Piping Recommendations (Single-Circuit Unit) CHECK VERTICAL SEPARATION — If there is any vertical separation between the indoor and outdoor units, check to ensure that the separation is within allowable limits. Relocate equipment if necessary.PROVIDE SAFETY RELIEF — If local ...
Page 10 - Fig. 7 — Typical Piping Connection Assembly; Step 6 — Install Accessories; Field Power Supply —
10 MAKE PIPING CONNECTIONS — Piping connections at the 38AUQ unit are ball valves with stub tube extensions. Do not open the unit service valves until all interconnecting tube brazing as been completed.The stub tube connections include ¼-in SAE service fittings with Schrader valve cores (see Fig. 7)...
Page 11 - Fig. 8 — Disconnect Switch and Unit; Units Without Factory-Installed Disconnect —; Fig. 9 — Power Wiring Connections; Voltage and Current Balance -; Convenience Outlets; FIRE HAZARD; Units Without Disconnect Option
11 Field power wires are connected to the unit at line-side pres- sure lugs on compressor contactor C and TB1 (see wiring dia- gram label for control box component arrangement) or at facto- ry-installed option non-fused disconnect switch. Max wire size is #4 AWG (copper only). NOTE: TEST LEADS - Uni...
Page 12 - Installing Weatherproof Cover
12 Fig. 10 — Convenience Outlet Location Non-powered type: This type requires the field installation of a general-purpose 125-volt 15-A circuit powered from a source elsewhere in the building. Observe national and local codes when selecting wire size, fuse or breaker requirements and disconnect swit...
Page 13 - Fig. 12 — Weatherproof Cover Installation; All Units —; Fig. 13 — Typical Remote Thermostat Connections
13 Press the gasket over the screw heads. Slip the backing plate over the screw heads at the keyhole slots and align with the gasket; tighten the two screws until snug (do not over-tighten). Mount the weatherproof cover to the backing plate as shown in Fig. 12. Remove two slot fillers in the bottom ...
Page 15 - System Check; The crankcase heater must be firmly attached to the com-; Turn On Crankcase Heater; Turn on the crankcase heater for 24 hours before starting the; Preliminary Charge
15 PRE-START-UP System Check 1. Check all indoor section and other equipment auxiliary components. Consult the manufacturer’s instructions regarding any other equipment connected to the con- densing unit. If the unit has field-installed accessories, be sure all are properly installed and correctly w...
Page 16 - Advanced Scroll Temperature Protection (ASTP); Fig. 14 — Advanced Scroll Temperature; Start Unit
16 Advanced Scroll Temperature Protection (ASTP) A label located above the terminal box identifies Copeland Scroll compressor models that contain this technology. See Fig. 14. Advanced Scroll Temperature Protection (ASTP) is a form of internal discharge temperature protection, that unloads the scrol...
Page 19 - OPERATING SEQUENCE; Base Unit Controls —
19 OPERATING SEQUENCE Base Unit Controls — Indoor (Supply) Fan The indoor fan contactor (IFC) is remotely located at the fan coil or fan section. If the thermostat fan operation is selected as Continuous, the IFC is energized and the indoor (supply) fan motor runs continuously. If the thermostat fan...
Page 20 - ROUTINE SYSTEM MAINTENANCE; Quarterly Inspection; SERVICE; Refrigeration System
20 ROUTINE SYSTEM MAINTENANCE These items should be part of a routine maintenance program, to be checked every month or two, until a specific schedule for each can be identified for this installation: Quarterly Inspection (and 30 days after initial start) Indoor section • Coil cleanliness checked.• ...
Page 21 - Liquid Line Filter Drier; Do not unsweat a filter drier; Field Refrigerant Access Ports; Fig. 20 — CoreMax Access Port Assembly; SEAT
21 Liquid Line Filter Drier The factory-provided reversible filter drier is specifically de- signed to operate with Puron®. Replace the filter drier with factory-authorized components only with a filter drier with desiccant made from 100% molecular sieve grade XH-11. Fil- ter drier must be replaced ...
Page 22 - Table 12 —38AUQ Defrost Board I/O and Jumper Configurations
22 Heat Pump Controls Compressor Protection Compressor Overcurrent The compressor has internal limbered motor protection. Compressor Overtemperature The compressor has an internal protector to protect it against excessively high discharge gas temperatures. High Pressure Switch The system is provided...
Page 23 - Fig. 23 — DIP Switch Settings — Defrost Board
23 Fig. 21 — Defrost Control Board (DFB) Location Fig. 22 — Defrost Control Board (DFB) Arrangement Reversing valve control The DFB has two outputs for unit reversing valve control. Op- eration of the reversing valves is based on internal logic; this application does not use an “O” or “B” signal to ...
Page 25 - Fans; LOC
25 Fig. 24 — 38AUQ*07 Exterior Fig. 25 — 38AUQ*07 Interior Fans ServiceValves LOC HPS High FlowAccess Ports Outdoor Coil DefrostThermostat(DFT)
Page 28 - Input
28 COMFORT ALERT DIAGNOSTIC MODULE The Comfort Alert Diagnostic Module (CADM) monitors and analyzes data from the Copeland Scroll ® three-phase compres- sor and the thermostat demand. The CADM also provides a 3-minute anti-recycle time delay to compressor cycling.The CADM detects causes for electric...
Page 29 - Table 14 — LED Status Codes
29 Table 14 — LED Status Codes Status LED Status LED Description Status LED Troubleshooting Information Green “POWER” Module has power Supply voltage is present at module terminals Red “TRIP” LED On Solid Thermostat demand signal Y is present, but the compressor is not running. 1. Compressor protect...
Page 30 - Table 15 — CADM Troubleshooting; Lubrication; PERSONAL INJURY AND UNIT DAMAGE
30 Table 15 — CADM Troubleshooting Lubrication FAN MOTORS have sealed bearings. No provisions are made for lubrication.COMPRESSOR has its own oil supply. Loss of oil due to a leak in the system should be the only reason for adding oil after the system has been in operation. Outdoor Coil Maintenance ...
Page 31 - FASTENER TORQUE VALUES; Table 16 — Torque Values
31 Clean coil as follows: 1. Turn off unit power, tag disconnect.2. Remove top panel screws on outdoor coil end of unit.3. Remove coil corner post. To hold top panel open, place coil corner post between top panel and center post. 4. Remove screws securing coil to compressor plate and compressor acce...
Page 32 - TROUBLESHOOTING
32 TROUBLESHOOTING PROBLEM CAUSE REMEDY Compressor and Outdoor Fan Will Not Start. Power failure. Call power company. Fuse blown or circuit breaker tripped. Replace fuse or reset circuit breaker. Determine root cause. Defective thermostat, contactor, transformer, control relay, or capacitor. Replace...
Page 33 - APPENDIX A; AIR CONDITIONER AND HEAT PUMP WITH; warnings; APPENDIX B; WIRING DIAGRAM LIST
33 APPENDIX A AIR CONDITIONER AND HEAT PUMP WITH PURON ® — QUICK REFERENCE GUIDE • Puron ® (R-410A) refrigerant operates at 50 percent to 70 percent higher pressures than R-22. Be sure that servicing equipment and replacement components are designed to operate with Puron ® . • Puron ® refrigerant cy...
Page 34 - APPENDIX C; MOTORMASTER SENSOR LOCATIONS; Fig. 31 Motormaster Sensor Locations per Unit Size
Copyright 2009 Carrier Corp • 7310 W. Morris St. • Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 09/09 Catalog No: 38AUQ-01SI Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Replaces: New 34 APPENDIX C MOTORMASTER SE...
Page 35 - I. PRELIMINARY INFORMATION; OUTDOOR UNIT
CL-1 III. START UP START-UP CHECKLIST I. PRELIMINARY INFORMATION OUTDOOR: MODEL NO. SERIAL NO. INDOOR: AIR HANDLER MANUFACTURER MODEL NO. SERIAL NO. ADDITIONAL ACCESSORIES II. PRE-START-UP OUTDOOR UNIT IS THERE ANY SHIPPING DAMAGE? (Y/N) IF SO, WHERE: WILL THIS DAMAGE PREVENT UNIT START-UP? (Y/N) CH...