Page 3 - LEGEND; Fig. 1 — Typical Carrier Linkage System; CCN; Carrier Comfor t Network; CSAM —; Comfort System
3 CCN PRIMARY BUS (BUS 0) FULLY COMPATIBLE AIR HANDLER CC6400 OR CSAM EQUIPPED NON-CCN AIR HANDLER COMFORTID EQUIPPED AIR TERMINAL (1 OF UP TO 128) ADDRESSED SEQUENTIALLY SECONDARY BUS DATA COLLECTION OPTION BRIDGE (RECOMMENDED) SYSTEM MONITORING SOFTWARE CCN LEGEND Fig. 1 — Typical Carrier Linkage ...
Page 4 - Mount Zone Controller; ZONE Controller; Square —
4 R E L A T I V E H U M I D I T Y S E N S O R — The33AMSENRHS000 relative humidity sensor is required forzone humidity control (dehumidification).NOTE: The relative humidity sensor and CO 2 sensor cannot be used on the same zone controller.INDOOR AIR QUALITY (CO 2 ) SENSOR — An indoor air quality se...
Page 5 - Fig. 3 — VAV Fan Terminal Zone Controller
5 — HF23BJ042 Made in Switzerlandby Belimo Automation LR 92800 NEMA 2 Class 2 Supply LISTED94D5TENP IND ®. EQUIP. 24VAC/DC50/60 Hz3VA 2W 5K WIP yel blu ora blk red wht COM 1 2 3 35 in-lb (4 Nm)80...110s 0 1 J4 J3 J1 SR VC 24V AC + G - HIGH Part Number: 33ZCVAVTRM S/N: Bus#: Element#: Unit#: J...
Page 6 - UL; Fig. 5 — Secondary Terminal Zone Controller; END VIEW INLET; Fig. 6 — Service Clearance for Zone Controller Mounting
6 3 5 i n - l b ( 4 N m )8 0 . . . 11 0 s H F 2 3 B J 0 4 2 M a d e i n S w i t z e r l a n d b y B e l i m o A u t o m a t i o n L R 9 2 8 0 0 NEMA 2 LISTED94D5 TEMP. IND. ®. EQUIP. UL Class 2 Supply 24VAC/DC5 0 / 6 0 H z 3VA 2W COM 1 2 3 blk red wht yel blu ora WIP 5K ® LOW HIGH Unit#: Part...
Page 7 - CW TO OPEN, CCW TO CLOSE; Fig. 7 — Damper Configuration
7 Connect the Power Transformer — An individual, field-supplied, 24 vac power transformer is recommended foreach zone controller. If multiple zone controllers are poweredfrom one power transformer (100 va maximum for UL [Under-writers’ Laboratories] Class 2 conformance), maintain polarityon the powe...
Page 8 - Low; TRAN; TRANSFORMER
8 2W 3V A 50/60Hz 24V AC/DC HF23BJ042 80...1 10s 35 in-lb(4Nm) SA T SPT HEA T2 HEA T1 24V AC B W R 24 V A C R B W Low Hi Wht Red Blk com Ora Blu Ye l 1 0 N/A PAT T56 SA T SPT +24V SECFLOW DMPPOS +10V GND GND GND GND GND RH/IAQ Or Bl Y V oltage Line comunications CCN Not used comunications CCN Automa...
Page 10 - CC
10 CL OP COM HWV V oltage Line Automation By Belimo Switzerland Made in 2W 3V A 50/60Hz 24V AC/DC HF23BJ042 80...1 10s 35 in-lb(4Nm) SA T SPT HEA T2 HEA T1 24V AC N/A PAT T56 SA T SPT +24V SECFLOW DMPPOS +10V GND GND GND GND GND RH/IAQ B W R 24 V A C Or Bl Y R B W Low Hi Wht Red Blk com Ora Blu Ye l...
Page 15 - PAT
15 HWV Fan Motor V oltage Line V oltage Line M 2W 3V A 50/60Hz 24V AC/DC HF23BJ042 80...1 10s 35 in-lb(4Nm) SA T SPT FA N HEA T2 HEA T1 24V AC N/A PAT T56 SA T SPT +24V SECFLOW DMPPOS +10V GND GND GND GND GND RH/IAQ Damper Second CCW COM CW Heat3 Used Not 24 V A C B W R 24 V A C Or Bl Y R B W Low Hi...
Page 17 - comunications; IM
17 F AN AC Not Used LINE VOL T AGE TRAN Not Used (+) (GND) (-) SHIELD SHIELDED (CCN-TYPE) CABLE REMOTE TRANSFORMER GROUND TERMINAL GROUND comunications CCN comunications CCN 2W 3V A 50/60Hz 24V AC/DC HF23BJ042 80...1 10s 35 in-lb(4Nm) SPT FA N HEA T2 HEA T1 24V AC N/A PAT T56 SA T SPT +24V SECFLOW D...
Page 18 - SECOND
18 2W 3V A 50/60Hz 24V AC/DC HF23BJ042 80...1 10s 35 in-lb(4Nm) GND CCW SECFLOW +10V CW GND Or Bl Y R B W Low Hi Wht Red Blk com Ora Blu Ye l 1 0 Automation By Belimo Switzerland Made in F ig . 8J — Zone Contr o lle r Wir ing — Dual Duct Applica ti o n s ( c ont ) L E GEND CCN — Carr ier Com for t N...
Page 19 - Install Sensors
19 Install Sensors SPACE TEMPERATURE SENSOR INSTALLATION —A space temperature sensor must be installed for each zonecontroller. There are three types of SPT sensors available fromCarrier: the 33ZCT55SPT space temperature sensor with timedoverride button, the 33ZCT56SPT space temperature sensorwith t...
Page 20 - Warm; Fig. 9 — Airflow Pickup Installation
20 3 5 i n - l b ( 4 N m )8 0 . . . 11 0 s H F 2 3 B J 0 4 2 M a d e i n S w i t z e r l a n d b y B e l i m o A u t o m a t i o n 1 0 yel blu ora WIP 5K LISTED94D5TEMP. IND. ®. EQUIP. UL Class 2 Supply L R 9 2 8 0 0 NEMA 2 24VAC/DC5 0 / 6 0 H z 3VA 2W COM 1 2 3 blk red wht H L LOW PRESSURETU...
Page 21 - Temperature Sensor, and Supply-Air Temperature Sensor; TEMP; CCN COM; Cool; CCN COM; Fig. 12 — Space Temperature Sensor Wiring
21 Table 1 — Thermistor Resistance vs Temperature Values for Space Temperature Sensor, Return-Air Temperature Sensor, and Supply-Air Temperature Sensor TEMP (C) TEMP (F) RESISTANCE (Ohms) –40 –40 335,651 –35 –31 242,195 –30 –22 176,683 –25 –13 130,243 –20 –4 96,974 –15 5 72,895 –10 14 55,298 –5 23 4...
Page 22 - Fig. 14 — Communication Bus Wiring to Zone Controller
22 Before wiring the CCN connection, refer to the Connect to the CCN Communication Bus section on page 26, for commu-nication bus wiring and cable selection. The cable selectedmust be identical to the CCN communication bus wire used forthe entire network. The other end of the communication bus cable...
Page 24 - UNIT WITH ELECTRIC REHEAT; ZC —; Zone Controller; UNIT WITH OCTOPUS
24 The CO 2 sensors (33ZCSENCO2) factory set for a range of 0 to 2000 ppm and a linear voltage output of 0 to 10 vdc.Figure 19 shows ventilation rates for various CO 2 set points when outside air with a typical CO 2 level of 350 ppm is used. Refer to the instructions supplied with the CO 2 sensor fo...
Page 25 - Fig. 20 — Indoor Air Quality Sensor Wiring
25 Indoor Air Quality Sensor Wiring — To wire the sensorsafter they are mounted in the conditioned air space and returnair duct, see Fig. 20 and the instructions shipped with the sen-sors. For each sensor, use two 2-conductor 18 AWG twisted-pair cables (unshielded) to connect the separate isolated 2...
Page 26 - Table 2 — Recommended Cables; Red; Fig. 21 — Wall Mounted Relative Humidity Sensor
26 7. Strip 1 / 4 -in. of insulation from each conductor and equip each with a 1 / 4 -in. female quick connect terminal. 8. Connect the RED wire to terminal +24v on the control board. 9. Connect the BLACK wire to terminal GND on the control board. 10. Connect the WHITE/CLEAR wire to terminal RH/IAQ ...
Page 27 - Fig. 22 — Humidity Sensor Wiring
27 3. Connect the other end of the communication bus cable to the terminal block labeled CCN in the zone control-ler of the first air terminal. Following the color codein Table 3, connect the Red (+) wire to Terminal 1.Connect the White (ground) wire to Terminal 2. Con-nect the Black (–) wire to Ter...
Page 28 - Remo
28 303 FIELD-SUPPLIED DR Y CONT ACT SWITCH TRANSFORMER GROUND TERMINAL GROUND comunications CCN Not used comunications CCN Automation By Belimo Switzerland Made in (+) (GND) (-) TRAN 2W 3V A 50/60Hz 24V AC/DC HF23BJ042 80...1 10s 35 in-lb(4Nm) HEA T2 HEA T1 24V AC B W R 24 V A C R B W Low Hi Wht Red...
Page 29 - Perform System; Fig. 24 — Typical Water Valve and Sensor Installation; AIR TERMINAL; GND; Fig. 25 — Communication Bus Wiring; Carrier Comfort Network; ZC
29 START-UP Use the Carrier network communication software to start up and configure the zone controller. All set-up and set point configurations are factory-set and field-adjustable. Changes can be made using the ComfortWORKS ® soft- ware, ComfortVIEW™ software, or Network Service Tool.The Network ...
Page 31 - Table 4 — Points Display Screen
31 4. If the terminal is a parallel or series powered fan box, force the Fan Override to Enable. If the damper is openit may have to be repositioned to the proper positiondepending on the box type. Damper percent changewill be displayed. After the damper is positioned cor-rectly, the fan relay shoul...
Page 32 - Modify Controller Configuration —; Table 5 — Alarm Limit Configuration Screen
32 SUPPLY AIR TEMPERATURE — Temperature of the airleaving the zone controller downstream of any ducted heatsource. Measured by a 10 k Ω thermistor (Type III). This tem- perature is used to control the maximum discharge air to thespace when local heat is active. The sensor is not required orrecommend...
Page 34 - Table 6 — Linkage Coordinator Configuration Screen
34 LINKAGE COORDINATOR CONFIGURATIONSCREEN — The Linkage Coordinator Configuration screenallows the user to set the linkage coordinator configuration set-tings. See Table 6.Linkage Master Zone — This decision defines if the zonecontroller will function as a Linkage Coordinator (LinkageMaster) for it...
Page 36 - Table 7 — Occupancy Schedule Information Screen; OVRD
36 Table 7 — Occupancy Schedule Information Screen If a 1 is configured in the corresponding place for a certain day of the week, the related “Occupied from” and “Occupiedto” times for that period will take effect on that day of theweek. If a 1 is placed in the holiday field the related times willta...
Page 37 - Service Configuration Selection Screen —; Table 8 — Set Point Screen
37 Air Quality — The Air Quality set point is used to configurethe IAQ set point for the zone controller if optional controlledventilation support is used.Air Quality Units none shown (ppm (ppm): implied) Range 0 to 5000 Default Value 850 Delta Airflow — The Delta Airflow set point is used to con-fi...
Page 39 - Table 10 — Terminal Service Configuration Screen
39 Table 10 — Terminal Service Configuration Screen Probe Multiplier — This configuration is used to input a factorfor the velocity pressure probe installed in the terminal inlet.Most inlet probes will have some aerodynamic characteristicsthat will affect the differential pressure output from the pr...
Page 41 - Table 11 — Options Service Configuration Screen
41 Start Value: Units F (C) Range 40 to 125 Default Value 80 Ducted Heat — The Ducted Heat configuration is used to con-figure the terminal for ducted heat. If a local heat source is inthe duct and requires airflow to provide heat, set the DuctedHeat configuration for yes.Ducted Heat Range No/Yes De...
Page 43 - Table 12 — Secondary Damper Service Configuration Screen; Maintenance Table Menu Screen —
43 Table 12 — Secondary Damper Service Configuration Screen Secondary Duct Size — The Secondary Duct Size setting isused to input the inlet diameter of the terminal, if used with around inlet. The Inlet Area configuration is used for oval orrectangular inlets. The zone controller will use the larger...
Page 45 - Table 13 — Linkage Maintenance Screen
45 → Table 13 — Linkage Maintenance Screen Next Unoccupied Day — This variable displays the day whenthe next associated zone is scheduled to change from occupiedto unoccupied mode. This point is read in conjunction with thenext unoccupied time to allow the user to know the next timeand day when a zo...
Page 46 - Table 14 — Occupancy Maintenance Screen
46 This number is rounded to the nearest tenth of an inch and will be subtracted to the static pressure reset value unless thestatic pressure reset value has reached zero.Pressure IncreaseValue: Display Units in. wg Display Range 0.000 to 5.000 Default Value 0.000 Network Access Read/Write OCCUP A N...
Page 48 - Table 15 — Zone Air Balance/Commissioning Table
48 → Table 15 — Zone Air Balance/Commissioning Table Heating Override — This variable can be used to test the heatoutputs. Enabling this variable will cause the heat to be modu-lated or staged to full heat until this point is disabled or theforce released. Ducted reheat operation will be controlled ...
Page 49 - Table 16 — Zone Maintenance Table
49 ZONE MAINTENANCE TABLE — The Zone Maintenancetable is used to display zone set points and variables. SeeTable 16.Occupied — This variable indicates if the zone controller isoperating in the occupied mode.Occupied: Display Range No/Yes Default Value No Network Access Read Only Linkage Slave — This...