Page 2 - Table 1 — Unit Sizes and Modular Combinations; MAJOR SYSTEM COMPONENTS
SAFETY CONSIDERATIONS Installing, starting up, and servicing this equipment can be hazardous due to system pressures, electrical compo-nents, and equipment location (roof, elevated structures, etc.).Only trained, qualified installers and service mechanics shouldinstall, start up, and service this eq...
Page 3 - — Terminal Block
7 8 9 4 5 6 1 2 3 – 0 • STAT EXPN HIST CLR SCHD SRVC SET TEST ENTR F U S E 1 LO C A L /E N A B L E S W 1 S T O P C C N F U S E 3 F U S E 2 F U S E F U S E FU S E C B 5 C B 6 EQUIP GND 99NA505322 D COMM 1COMM 3 PWR X X S1 S2 X X POINT NUMBER OF FIRST CHANNEL COMM 3 PWR LV EXV STA TUS COMM STA TUS COM...
Page 4 - Switch Positions and Operation
also controls the EXV driver module (as appropriate), com-manding it to open or close each EXV in order to maintainthe proper superheat entering the cylinders of each lead com-pressor. Information is transmitted between the processor mod-ule and relay module, the EXV driver module, and the key-pad a...
Page 5 - Sensors —; Table 3 — Thermistor and Transducer Locations; OPERATION DATA; Fig. 2 — Compressor Protection Control Module
The TXV is set at the factory to maintain approximately 8 to 12° F (4.4 to 6.7° C) suction superheat leaving the coolerby monitoring the proper amount of refrigerant into the cooler.All TXVs are adjustable, but should not be adjusted unlessabsolutely necessary. When TXV is used, thermistors T7 andT8...
Page 24 - DISPLAY; CLOCK ON; ALARMS; Fig. 4 — Keypad and Display Module
Head Pressure Control EXV UNITS (All 30GN units except 040 and 045 with op-tional brine) — The microprocessor controls the condenserfans in order to maintain the lowest condensing temperaturepossible, thus the highest unit efficiency. Instead of using theconventional head pressure control methods, t...
Page 25 - Table 5 — Condenser Fan Sequence; FAN ARRANGEMENT
Table 5 — Condenser Fan Sequence FAN ARRANGEMENT 30GN FAN NUMBER(S) FAN CONTACTOR (FC) CONTROLLED BY 040-050 1 FC-A1 Compressor A1 2 FC-B1 Compressor B1 3 FC-A2 First Stage Microprocessor 4 FC-B2 Second Stage Microprocessor 060,070 1 FC-A1 Compressor A1 2 FC-B1 Compressor B1 3, 4 FC-A2 First Stage M...
Page 30 - TEST
Table 9 — Keypad Directory (cont) STATUS (cont) SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT 10 OUTPUTS (cont) EXVB X EXVB Percent Open** HGBA X† Hot Gas Bypass Relay Circuit A (on/off)** HGBB X† Hot Gas Bypass Relay Circuit B (on/off)** MMA X† Motormaster T A Output Percent** MMB X† Motormaster B Outpu...
Page 31 - SCHEDULE
Table 9 — Keypad Directory (cont) TEST (cont) SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT 2 COMPRESSORS AND UNLOADERS (cont) CPA3 X† Test Compressor A3 (on/off)** CPA4 X† Test Compressor A4 (on/off)** CPB1 X Test Compressor B1 (on/off) CPB2 X† Test Compressor B2 (on/off)** CPB3 X† Test Compressor B3 (o...
Page 32 - SERVICE
Table 9 — Keypad Directory (cont) SCHEDULE (cont) SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT 3 PERIOD 1 (cont) FRI X Friday Flag (yes/no) SAT X Saturday Flag (yes/no) SUN X Sunday Flag (yes/no) HOL X Holiday Flag (yes/no) To toggle between inputs (Yes/No) Press: (no) or (yes) 4 PERIOD 2 PERIOD 2 Perio...
Page 34 - HISTORY
Table 9 — Keypad Directory (cont) HISTORY SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT 1 RUN TIME RUN TIME Run Time Information HR X Total Hrs Unit Has a Comp Operating HRA X Circuit A Run Time HRB X Circuit B Run Time HA1 X Circuit A, Comp A1 Operating Hours HA2 X Circuit A, Comp A2 Operating Hours** H...
Page 35 - SET POINT
Table 9 — Keypad Directory (cont) SET POINT To read a set point, go to proper subfunction and read desired set point. To change a set point, enter new set point value, then press . LOCAL/ENABLE-STOP-CCN switch must be in LOCAL/ENABLE or STOP position. SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT 1 SET P...
Page 37 - Table 10 — Operational and Mode Display Codes
Table 10 — Operational and Mode Display Codes The operating modes are displayed by name or code num- ber, to indicate the operating status of the unit at a giventime. The modes are: CODE DESCRIPTION LOCAL OFF Unit is off. LOCAL/ENABLE-STOP-CCN switch is inOFF position, or LOCAL/ENABLE-STOP-CCN switc...
Page 38 - Example 3 — Using Test Function; KEYPAD; Chilled Fluid Set Point
Keypad entry allows the operator to make the following checks by using : • LID display check. Proper display is 8.8.8.8.8.8.8.8.• Operation of alarm relay.• Operation of condenser fans.• Operation of chilled fluid pump.• Operation of liquid line solenoids.• Operation of the hot gas bypass relays.• O...
Page 41 - Fig. 6 — Cooling External Temperature Reset; — Power
Fig. 6 — Cooling External Temperature Reset LEGEND COMM — Communications BusPWR — Power SW — Switch NOTE: For specific connection points,see Fig. 25 - 29. Fig. 7 — 4 IN/4 OUT Options Module Wiring for Reset, Demand Limit, and Dual Set Point 41
Page 42 - Example 6 — Changing Reset Type; To change type of reset, first log on as shown in; To use Demand Limit, first enable loadshed, then enter; Table 12 — Service Functions; To view and modify configurations, the password must be; Fig. 8 — 4-20 mA Cooling Temperature Reset
Example 6 — Changing Reset Type To change type of reset, first log on as shown in Table 12. Also refer to Set Point Function section, page 38,for information on entering reset set points using resetfeature. KEYPAD DISPLAY COMMENTS ENTRY RESPONSE FLD CFG Field configurationsubfunction ofservice funct...
Page 46 - CCN — Carrier Comfort Network
NOTE: This is true only if the occupied period starts at 00:00(midnight). If the occupied period starts at a time other thanmidnight, then the occupied period must end at 00:00 hours(midnight) and new occupied period must be programmedto start at 00:00 in order for the chiller to stay in the occu-pi...
Page 47 - Example 10 — Holiday Schedule Function; TROUBLESHOOTING; Fig. 10 — Sample Time Schedule
Periods 4 and 5 can be programmed in the same manner, flagging Thursday and Friday yes for period 4 and Saturdayyes for period 5. For this example, periods 6, 7, and 8are not used: they should be programmed OCC 00.00,UNO 00.00.NOTE: When a day is flagged yes for 2 overlapping periods,occupied time w...
Page 48 - Table 15 — Typical Stoppage Faults and Reset Types
Unit Shutoff — To shut unit off, move LOCAL/ENABLE- STOP-CCN switch to STOP position. Any refrigeration cir-cuit operating at this time continues to complete the pum-pout cycle. Lag compressors stop immediately, and leadcompressors run to complete pumpout. Complete Unit Stoppage — Complete unit stop...
Page 49 - Table 16 — Alarm and Alert Codes
Table 16 — Alarm and Alert Codes DISPLAY ALARM DESCRIPTION ACTION TAKEN CIRCUIT RESET PROBABLE CAUSE OR ALERT BY CONTROL PUMPDOWN METHOD 0 — No Alarms or Alerts Exist — — — — 1 Alert Compressor A1 failure Circuit A shut down No Manual High-pressure switch trip, or wiringerror. 2, 3, 4 Compressor A2,...
Page 50 - Compressor Alarm/Alert Circuit —
Table 16 — Alarm and Alert Codes (cont) DISPLAY ALARM DESCRIPTION ACTION TAKEN CIRCUIT RESET PROBABLE CAUSE OR ALERT BY CONTROL PUMPDOWN METHOD 63 Alarm Complete unit shutdown Alarm only — Auto. Check individual alarms 64 Alert Loss of charge, circuit A Circuit cannot start — Auto. Refrigerant leak ...
Page 56 - EXV — Electronic Expansion Valve; Fig. 13 — EXV Cable Connections to EXV Driver
vapor). To control refrigerant flow for different operating con-ditions, sleeve moves up and down over orifice, thereby chang-ing orifice size. Sleeve is moved by a linear stepper motor.Stepper motor moves in increments and is controlled di-rectly by the processor module. As stepper motor rotates,mo...
Page 57 - Thermistors —
reading correctly. Connect a calibrated gage to leadcompressor suction or discharge pressure connectionto check transducer reading. e. Make sure transducer leads are properly connected in junction box and at processor board. Check trans-former 5 output. Check voltage transducer 5 vdc 6 .2 v. When ab...
Page 60 - Pressure Transducers —; A single style of pressure; — Thermistor Number; Fig. 14 — Thermistor and Pressure Transducer Locations
Pressure Transducers — A single style of pressure transducer is used for both high- and low-pressure sensingon Flotronic™ II chillers. However, this transducer must becalibrated before the unit will operate. On new units, thiswill have been done at the factory in order to test run theunit. If a tran...
Page 61 - Fig. 15 — Thermistor Locations; Fig. 16 — Thermistors
Fig. 15 — Thermistor Locations (Circuits A and B, Lead Compressor Only) FLUID-SIDE TEMPERATURE THERMISTOR T2 (ALL UNITS) COMPRESSOR SUCTION GAS TEMPERATURE THERMISTORS T7 AND T8 (ALL UNITS) AND FLUID-SIDE TEMPERATURE THERMISTOR T1 (ALL UNITS) Fig. 16 — Thermistors 61
Page 62 - Fig. 17 — Lead Compressor Transducer and Thermistor Locations
TRANSDUCER REPLACEMENT Transducers are installed directly in the refrigerant cir-cuit. Relieve all refrigerant pressure using standard re-frigeration practices before removing. 1. Relieve refrigerant pressure using standard refrigeration practices. 2. Disconnect transducer wiring at transducer by pu...
Page 63 - Control Modules; Fig. 18 — Module Address
Control Modules Turn controller power off before servicing controls. Thisensures safety and prevents damage to controller. PROCESSOR MODULE (PSIO), 4 IN/4 OUT MODULE(SIO), LOW-VOLTAGE RELAY MODULE (DSIO-LV),AND EXV DRIVER MODULE (DSIO-EXV) — The PSIO,DSIO and SIO modules all perform continuous diagn...
Page 64 - ACCESSORY UNLOADER INSTALLATION; Some of the 30G FlotronicTM II units come standard with; Fig. 19 — Sensor Bus Wiring
PROCESSOR MODULE (PSIO) (Fig. 20) Inputs — Each input channel has 3 terminals; only 2 of theterminals are used. Application of machine determines whichterminals are used. Always refer to individual unit wiringfor terminal numbers.Outputs — Output is 24 vdc. There are 3 terminals, only 2of which are ...
Page 65 - Installation
If accessory unloaders are desired, an accessory unloader package is used. Package includes a suction cutoff unloaderhead package. The 24-v coil in the package can be usedfor 040-110, 130 (60 Hz), and associated modular units(Table 1). A 115 v or 230 v coil must be used for 130(50 Hz), 150-210, and ...
Page 66 - Table 19 — Troubleshooting; Table 20 — Standard and Accessory Unloaders
Table 19 — Troubleshooting SYMPTOMS CAUSE REMEDY COMPRESSOR DOESNOT RUN Power line open Reset circuit breaker. Control fuse open Check control circuit for ground or short.Replace fuse. High-Pressure Switch (HPS)tripped Move LOCAL/ENABLE-STOP-CCN switch to STOPposition then back to RUN or CCN positio...
Page 68 - Fig. 23 — Accessory Unloader Control Wiring, All Units
LEGEND C — Contactor PWR — Power CB — Circuit Breaker SW — Switch COMM — Communications Bus TRAN — Transformer HGBPR — Hot Gas Bypass Relay U — Unloader *Or HGBPR-A.†Or HGBPR-B. LEGEND COM — Communications Bus TB — Terminal Block HGBPR — Hot Gas Bypass Relay TRAN — Transformer NO — Normally Open U —...
Page 69 - FIELD WIRING
FIELD WIRING Refer to Fig. 25-35 for field wiring. NOTE: Contacts must be rated for dry circuit application, capable ofreliably switching a 5 vdc, 1 mA to 20 mA load. Fig. 25 — Demand Limit — Two External Switch Inputs Fig. 26 − Demand Limit — 4-20 mA Signal (Externally Powered) Fig. 27 — Demand Lim...
Page 70 - TB — Terminal Block; Fig. 34 — Remote Alarm; TB
REPLACING DEFECTIVE PROCESSOR MODULE The replacement part number is printed on a small label on the front of the PSIO module. The model and serial num-bers are printed on the unit nameplate located on an exteriorcorner post. The proper software and unit configuration datais factory installed by Carr...