Page 2 - OUTDOOR LIQUID CHILLER; Physical data; Leveling unit; Unit must be level when installed to ensure proper oil; Cooler temperature
Table of contents Page Features ............................................................................. 1 Field-Installed Accessories ...............................................1 Factory-Installed Option (FIOP)......................................1 Model Number Nomenclature .................
Page 3 - Leaving water temperature reset; Cooler flow range
Application data (cont) MINIMUM COOLER WATER FLOW RATES AND MINIMUM LOOP VOLUME MINIMUM PRESSURE MINIMUM UNIT 30GB FLOW (1) DROP VOLUME (2) Gpm ft of water Gallons 060 67 3.8 180 NOTES. 1 . Minimum flow based on 1 5 fps veiocity in cooier without special cooler baffling 2. Minimum Loop Volumes: Gall...
Page 4 - Condenser; A WARNING; Provide sufficient volume in the chilled water loop — At
Application data (cont) per ton (6.5 to 10.8 liters per kW). To achieve this volume, it is often necessary to install a tank in the loop. Tank should be baffled to insure that there is no stratification and that water (or brine) entering tank is adequately mixed with liquid in the tank. GOOD GOOD Co...
Page 5 - Oversizing chillers; MULTIPLE UNIT SEPARATION; Electrical/utility interests
Correct unit capacity — On glycol performance capacity correction curve, read 0.95. Corrected capacity = 0.95 x determined capacity - 0.95 X 61.3 = 58.2 tons Correct chilled water flow — On the gpm correction factor curve, read 1.15. Chilled water flow (at corrected capacity) 24 X corrected capacity...
Page 6 - Hot gas bi^pass usage, while frequently specified, is not; Selection procedure
Time clock shutdown (or other controlled shutdown not associated with leaving chilled water temperature) requires use of accessory demand limit control module. Second step of the demand limit control (0-50% of capacity) is set for 0 (zero) capacity. This allows unit to go through a normal pumpout cy...
Page 7 - Performance data; STANDARD RATINGS* — REFRIGERANT 22
Performance data STANDARD RATINGS* — REFRIGERANT 22 UNIT CAPACITY COMPRESSOR POWER INPUT (kW) FAN POWER COOLER WATER PRESSURE DROP (ft water) ENERGY EFFICIENCY RATIO (EER) 30GB (tons) (Btuh) (kW) 060 59 7 716,400 68.4 7.81 13.7 94 *Per ARl Standard 590-81, Section 7 2 NOTE: 95 F condenser entering a...
Page 8 - CAPACITY CONTROL STEPS
Performance data (cont) 300- 270 240- 210 180- ISO 120 - 90- 75- •5 60-1 a. Ko UJ 5 (f> UJ a. 45- 30- 27 24 21 18- 15- 12 - 9- TOTAL COOLER PRESSURE DROP (Water Side) 80 90100 600 TOO 1000 COOLER WATER FLOW (6PM) 800 -T— 3 7 10 15 20 COOLER WATER FLOW (L/S) 30 —I-----1—I 40 50 60 CAPACITY CONTROL...
Page 10 - Dimensions; DIMENSIONS; WEIGHT DISTRIBUTION
Dimensions DIMENSIONS ft-in. (mm) DIM. UNIT 30GB060 A 13-7% (4162) B 11-3 (3429) C 12-5% (3797) D 10 - 0 % (3061 ) E 5-8%2 (1730) F 5-3% (1619) G 4-6% (1387) H 7-6 (2286) J 5-0 (1524) COOLER END VIEW TOP VIEW SIDE VIEW 'AMER. STD. ST PIPE THO. 4"-(070 UNIT) Space for service and airflow. Mountin...
Page 11 - Electrical data ~ 60 Hz; Controls; Microprocessor — Microprocessor controls overall; perature control with return water temperature
Electrical data ~ 60 Hz 30GB UNIT COMPRESSORSt FAN MOTORS* Volts MCA MORA(Fuse) ICF RLA (ea) LRA (ea) Total MTA Total Fans (Ph) FLA (ea) Fan No. MTA (FCB) Nameplate Supplied* Compressor No. CB h O. Min Max 1 2 1 2 1 2 1,2 3,4,5,6 208-230 187 254 342 500 846 119 158.5 506 690 166 222 6 ( 1 ) 4.6 7 7 ...
Page 13 - Control sequence; switch cuts out compressors if compressor discharge
Control sequence Off cycle — During unit off cycle, crankcase and, if ambient temperature is below 36 F (2 C), cooler and control box heaters are energized. Electronic expansion valves are closed. Start-up — After control circuit ON/OFF circuit breaker switched ON, prestart process takes place for 2...
Page 14 - Typical installation
Typical installation AIRFLOW THROUGH AIR-HANDLING UNIT CONTROL WIRING CHILLED WATER PIPING ST - STARTER FD - FUSED DISCONNECT NOTES: 1. Wiring and piping shown are generai points-of-connection guides oniy and are not intended for or to include all details for a specific installation. 2. All wiring m...
Page 15 - Guide specifications
Guide specifications 1. GENERAL 1.1 Furnish and install complete, factory-assembled air-cooled reciprocating liquid chiller units of the type, size and capacity shown on the equipment schedules. Unit shall be for outdoor use and rated in accordance with ARI Standard 590 latest edition. 1.2 Equipment...
Page 16 - Specifiers note — Application of 30GB outdoor chillers; UNITED
Guide specifications (cont) 7.4 Electronic ground current sensing device shall be available as accessory for each compressor to monitor the compressor 3-phase power supply. It shall be activated when no more than 2.5 amps is measured to ground and shall deactivate the compressor to prevent formation...