Page 2 - Single, reliable operation —; Application versatility; Ease of installation —; Table of contents
Single, reliable operation — The 16JB absorption chiller employs asingle generator to provide one stageof solution reconcentration, makingit the most basic of the cycles availabletoday. Simplicity of design, combinedwith its numerous other quality fea-tures, equates to inherently high reli-ability. ...
Page 4 - Superior corrosion protection —; continuously
Features/Benefits (cont) Factory-trained service organiza-tion — Carrier’s extensive service organization offers trained and experi-enced service technicians in everymajor city. In addition to routine main-tenance and repair services,Carrier also offers a wide array of pre-ventative maintenance, ful...
Page 8 - Options and accessories
Options and accessories ITEM OPTION* ACCESSORY† 300 psig (2068 kPa) NIH Waterboxes X Special Tubing X Unit Voltage 50/60 Hz X CSA Certification X Flanged Waterbox Connections X Victaulic Waterbox Connections X Shipping Configuration (1- or 2-piece) X Hot Water Generator (ASME 250 psig [1724 kPa]) X ...
Page 11 - Physical data
Physical data ENGLISH UNIT 16JB 010 012 014 018 021 NOMINAL COOLING CAPACITY (ton) 108 122 137 186 211 RIGGING WEIGHT* (lb) Absorber/Evaporator 6,300 6,370 6,370 8,050 8,610 Generator/Condenser 2,700 2,730 2,730 3,450 3,690 Total 9,000 9,100 9,100 11,500 12,300 OPERATING WEIGHT (lb) 11,240 11,400 11...
Page 13 - Dimensions
Dimensions 16JB SIZES 010-068 TYPICAL FRONT VIEW Carrier A C TYPICAL SIDE VIEW B D DIMENSIONS (ft-in.) UNIT 16JB 010 012 014 018 021 024 028 032 Overall Length A 16- 9 16- 9 16- 9 16-10 1 ⁄ 2 16-10 1 ⁄ 2 16-10 3 ⁄ 4 16-10 3 ⁄ 4 16-11 3 ⁄ 8 Overall Width B 5- 2 9 ⁄ 16 5- 2 9 ⁄ 16 5- 2 9 ⁄ 16 5-10 5-1...
Page 14 - Performance data; Part-load performance; ARI 560, latest edition, defines Integrated Part Load Value
Performance data ENGLISH UNIT 16JB 010 012 014 018 021 024 028 032 COOLING CAPACITY (ton) 108 122 137 186 211 245 279 326 CHILLED WATER Flow Rate (gpm) 259 292 328 446 506 587 669 781 Pressure Drop (ft) 15.9 16.0 16.4 15.6 15.7 15.9 16.2 15.6 COOLING WATER Flow Rate (gpm) 389 439 493 670 760 882 100...
Page 15 - Application data; Vent and drain connections; Provide high points of the machine piping system with; Range of application; Service access
Application data Vent and drain connections All vent and drain connections are found on the waterboxcovers. Connection size is 3 ⁄ 4 in. FPT. Provide high points of the machine piping system with vents and the low points with drains. If shutoff valves areprovided in the main water pipes near the uni...
Page 19 - Controls; Microprocessor controls; Set Point Control, and System Configuration
Controls Microprocessor controls Microprocessor controls provide the safety, interlock, ca-pacity control, and indications necessary to operate the chillerin a safe and efficient manner. Control system The microprocessor control on each 16JB double-effectchiller is factory mounted, wired, and tested...
Page 21 - Control sequence
Control sequence To start: Local start-up (manual start-up) is initiated by press- ing the LOCAL menu softkey which is indicated on the de-fault local interface device (LID) screen. All pre-start safetiesare checked to verify that all pre-start alerts and safeties arewithin limits. If one is not, an...
Page 22 - Typical piping and wiring
Typical piping and wiring LEGEND Field Piping Control WiringPower Wiring 22
Page 23 - Guide specifications; Hermetic Absorption Liquid Chiller; Part 1 — General; not; Part 2 — Products
Guide specifications Hermetic Absorption Liquid Chiller Size Range: 108 to 680 Tons (380 to 2392 kW) Carrier Model Number: 16JB Part 1 — General 1.01 SYSTEM DESCRIPTION Microprocessor controlled, single-effect (one-stage)absorption liquid chiller utilizing hermetic refrigerantand solution pumps, lit...
Page 24 - requires
Guide specifications (cont) B. Operating Characteristics: 1. Chiller operation shall be characteristic of a single effect absorption cycle. The weak solution pumpedfrom the absorber to the generator shall initiallypass through a solution heat exchanger to im-prove operating efficiency by pre-heating...