Page 2 - Table of Contents
2 Form 6104 BCF23-R05 Table of Contents General Information ............................................................................................................................. 3-4 To the Owner ....................................................................................................
Page 3 - Appliance manufacturer’s instructions; Hazard defi nitions; Intended to bring special attention to information,; Specifi cations; NOTICE; immediately contact your qualifi ed service agency; General Information
3 Form 6104 BCF23-R05 Before you begin . . . The following resources will give you addional information for your installation. We suggest that you consult these resources whenever possible. Pay particular attention to the appliance manufacturer’s instructions. Appliance manufacturer’s instructions -...
Page 4 - Failure to follow these instructions; Pre-installation checklist; Combustion air supply; Owner’s Responsibility:; Failure to follow these instructions,
4 Form 6104 BCF23-R05 Please read all instructions before proceeding. Follow all instructions completely. This equipment must be installed, adjusted and started by a qualifi ed service agency that is licensed and experienced with all applicable codes and ordinances and responsible for the installati...
Page 5 - Fuel supply; When fuel supply is below the burner fuel unit —; Figure 1 – Typical Nameplate; Damage to the fi lter or pump seals could cause; Correct Nozzle and Flow
5 Form 6104 BCF23-R05 Nozzle pressure The fuel unit nozzle port pressure is factory set at 300 psig. Some original equipment manufacturer burner applications may call for a lower pressure to obtain a required fi ring rate. Do not change this pressure un-less directed to do so by the appliance manufa...
Page 6 - Verify fi ring rate; Figure 2 – Chamber Dimensions
6 Form 6104 BCF23-R05 Vent system The fl ue gas venting system must be in good condition and must comply with all applicable codes. Verify burner components — Burner box, Model CF1400 or CF2300A Air tube assembly Mounting fl ange kit Pedestal mounting assembly kit (recommended) Oil nozzle, per Table...
Page 7 - Verify air tube; Figure 3 – Air tube mounting dimensions; Table 2 - Air tube capacity Versus fi rebox
7 Form 6104 BCF23-R05 Verify air tube The information in this section may be disregarded if the air tube is supplied by the appliance manufacturer. On the CF1400 , there are two tube arrangements available – Tube A — 4.0 to 11.0 GPH per Table 2Tube B — 7.0 to 13.6 GPH per Table 2 The CF1400 maximum ...
Page 8 - Mount the burner; Protect Against Stray
8 Form 6104 BCF23-R05 This burner is designed for clean, dry installations.Electrical controls are not protected against rain or sprayed water.Keep the installation clear of dust, dirt, corrosive vapors, and moisture.Protective covers and more frequent maintenance may be required. yy y y Wet, dusty ...
Page 9 - Figure 5 – Nozzle and nozzle line assembly; Check electrode settings; Failure to properly maintain these specifi cations
9 Form 6104 BCF23-R05 Mount air tube to burner Remove the rear access door from the back of the burner for improved access to the interior. Attach the air tube to the burner with the bolts and acorn nuts provided. The acorn nuts must go on the outside of the burner, with the bolts inserted from the ...
Page 10 - Figure 6 – Nozzle line assembly in burner; Set dimension Z; do not; Install nozzle line assembly; Figure 7 – Adjusting plate assy.
10 Form 6104 BCF23-R05 Figure 6 – Nozzle line assembly in burner Z 2308 a Measure dimension from front (flat) face of head toend of air tube, as shown. Z b c d Measure dimension Z from the flatsurface between (not on) the raised fins. 2324 Set dimension Z Replace the rear access door on the burner, ...
Page 11 - Figure 8 – Burner installed in appliance front; Insert burner; with length 11 inches
11 Form 6104 BCF23-R05 Figure 8 – Burner installed in appliance front Dimension CF 1400 CF 2300 H 18” 18-1/2” J 10-7/8” 10-1/2” K 13-5/8 15-5/8” Insert burner Position the burner in the front of the appliance and loosely tighten the nuts on the mounting studs. The burner should be pitched downward 2...
Page 12 - Failure to follow these guidelines will cause; Factory-Installed Pump; Connect fuel lines; Fuel unit by-pass plug; Burner fuel fl ow; Failure to properly install the oil
12 Form 6104 BCF23-R05 Models CF1400 and CF2300 are shipped with the pump bypass plug installed.Do not remove the bypass plug from the pump. It is required for step-fi ring (Lo/Hi) operation.Do not operate the burner unless a return line or bypass loop is installed or the pump seal will rupture. Car...
Page 14 - Wire the burner; Electrical shock can cause severe personal in-; Electrical Shock Hazard
14 Form 6104 BCF23-R05 Wire the burner — R7184B Install the burner and all wiring in accordance with the National Electrical Code and all applicable local codes or requirements. Wire the burner in compliance with all instructions provided by the appliance manufacturer. Verify operation of all contro...
Page 15 - equence of operation — typical
15 Form 6104 BCF23-R05 Standby Trial for Trial for ignition Lockout Recycle Run 3 4 Ignition carryover Motor-off delay (postpurge) 8 6 7 5 Valve-on delay 2 1 Sequence of operation — typical Install the burner and all wiring in accordance with the National Electrical Code and all applicable local cod...
Page 16 - Z dimension; Prepare the burner for start-up; Tampering with, or bypassing safety controls; Do Not Bypass Safety; Incorrect installation and mishandling of start-; Professional Installation
16 Form 6104 BCF23-R05 Start-up checklist – Verify the following before at- tempting to start burner. Combustion air supply and venting have been inspected and verifi ed to be free of obstructions and installed in accordance with all applicable codes. Oil nozzle has been selected correctly and secur...
Page 18 - Initial air settings; Figure 13A. Damper Motor with Cover
18 Form 6104 BCF23-R05 Initial air settings The following steps outline the procedure for initially setting the damper. Refer to Figures 13A and 13B and Tables 4a or 4b for this procedure. 1. Remove the cover screw ( A ) then the cover ( B ) and place to one side. 2. Using the wrench ( C ) supplied ...
Page 19 - Start the burner; Set appliance limit controls; Hot Gas Puff-back and
19 Form 6104 BCF23-R05 Start the burner Please read and understand the manual supplied with this equipment. This equipment must be installed, adjusted and put into operation only by a qualifi ed individual or service agency that is: Licensed or certifi ed to install and provide technical service to ...
Page 20 - Start burner and vent air from oil line
20 Form 6104 BCF23-R05 Start burner and vent air from oil line Move the low-fi re hold switch to the low fi re hold position (to hold burner in low fi re when started). Verify that the air adjusting cam ( Figure 13b , item d ) has been set to the initial low-fi re air setting as described under Init...
Page 21 - Annual Service; Perform Regular Maintenance; Tampering with or making incorrect; Annual Professional; Monthly maintenance — by owner
21 Form 6104 BCF23-R05 Annual Service Replace the oil supply line fi lter. The line fi lter cartridge must be replaced to avoid contamination of the fuel unit and nozzle.Inspect the oil supply system. All fi ttings should be leak-tight. The supply lines should be free of water, sludge and other rest...
Page 22 - Replacement Parts; For best performance specify genuine; Beckett; replacement parts; Item
22 Form 6104 BCF23-R05 Replacement Parts For best performance specify genuine Beckett replacement parts Item Part Name Description Part No. 1 Timer Nozzle valve delay 21295U 2 Oil Valve Box mounted 21789U 3 Knurled Nut All models 3666 4 Adjusting plate assembly w/ cast aluminum doorw/ stamped sheet-...
Page 23 - Flange A; Figure 14 – Burner Replacement Parts
23 Form 6104 BCF23-R05 Figure 15 – Adjustable mounting plates Model Flange A Flange B Flange C CF1400 51312 (10.00” DIA.) n/a 51629 (12.25” DIA.) CF2300 51313 (12.44” DIA.) 51498 (13.92” DIA.) 51630 (16.00” DIA.) Flange A Flange B Flange C Figure 14 – Burner Replacement Parts 7 8 1 2 3 4 5 6 9 10 11...
Page 24 - Limited; WARRANTY; BECKETT; CORPORATION; Limited Warranty Information
24 Form 6104 BCF23-R05 Limited WARRANTY For Residential, Commercial and Specialty Burners The R. W. BECKETT CORPORATION (“Beckett”) warrants to persons who purchase its Beckett burners from Beckett for resale or for incorporation into a product for resale (“Customers”) that its equipment is free fro...