Page 2 - Contents; Figures
Contents Getting Other Informations and Publications ........ 1 General Instructions ................................................. 3 Important ................................................................ 3Shipping Damage .................................................... 3General ............
Page 3 - Getting Other Information and Publications; ACCA — Air Conditioning Contractors of America
Manual 2100-344Page 1 Getting Other Information and Publications These publications can help you install the air conditioner orheat pump. You can usually find these at your local libraryor purchase them directly from the publisher. Be sure toconsult current edition of each standard. National Electri...
Page 5 - GENERAL INSTRUCTIONS; IMPORTANT
Manual 2100-344Page 3 TABLE 4 RATED CFM AND EXTERNAL STATIC PRESSURE (ESP) WET COIL (COOLING) l e d o M d e t a R M F C d e t a R P S E d e d n e m m o c e R e g n a R w o l F r i A 4 2 2 1 H P 0 0 8 0 2 . M F C 0 8 8 - 0 8 6 0 3 2 1 H P 0 0 0 1 0 3 . M F C 0 0 1 1 - 5 7 7 6 3 2 1 H P 0 0 1 1 0 2 . ...
Page 7 - INSTALLATION; LOCATION; – This; TYPICAL INSTALLATIONS; – The unit is mounted on a; – Duct work installed in crawl
Manual 2100-344Page 5 INSTALLATION LOCATION GENERAL The unit must be located outside, or in a well ventilatedarea. It must not be in the space being heated or cooled. Asound absorbing material should be considered if the unit isto be installed in such a position or location that might causetransmiss...
Page 10 - CONDENSATE DRAIN TRAP
Manual 2100-344Page 8 FIGURE 7 CONDENSATE DRAIN TRAP MIS-136 maintained for proper operation. If this is not done,excessive energy use, poor performance, and multipleservice problems will result. It is impossible to oversize airfilters. Generous sizing will result in cleaner air and coilsas well as ...
Page 11 - WIRING – MAIN POWER
Manual 2100-344Page 9 TABLE 6 – THERMOSTAT WIRE SIZE r e m r o f s n a r T A V A L F e r i W e g u a G h t g n e L m u m i x a M t e e F n I 5 5 3 . 2 0 2 8 1 6 1 4 1 2 1 5 4 0 6 0 0 1 0 6 1 0 5 2 WIRING – MAIN POWER Refer to the unit rating plate for wire sizing information andmaximum fuse size. Ea...
Page 12 - THERMOSTATS
Manual 2100-344Page 10 TABLE 7 HEAT PUMP THERMOSTATS T A T S O M R E H T E S A B B U S N O I T P I R C S E D 5 4 0 - 3 0 4 8 ) 1 6 7 1 A 1 4 8 T ( f o t r a P t a t s o m r e h T r e v o e g n a h c l a u n a M ; b l u b y r u c e M ; t a e h e g a t s 2 , l o o c e g a t s 1 l o o C - f f O - t a e...
Page 13 - TRANSFORMER TAPS; TAP; THERMOSTAT INDICATOR LAMPS
Manual 2100-344Page 11 COMPRESSOR CUTOFF THERMOSTATWIRING (15 KW ONLY) FIGURE 9 UNIT 24V TERMINAL BOARD MIS-1188 FIGURE 10 UNIT 24V TERMINAL BOARD MIS-1189 TABLE 8 5 and 10 KW l e d o M W K s t l o V e s a h P 4 2 2 1 H P 0 1 , 5 , 0 0 3 2 1 0 3 2 1 H P 0 1 , 5 , 0 0 3 2 1 6 3 2 1 H P 0 1 , 5 , 0 0 ...
Page 14 - START UP AND OPERATION; DEFROST CYCLE; SEQUENCE OF OPERATION
Manual 2100-344Page 12 START UP AND OPERATION the reversing valve solenoid constantly whenever the systemswitch on subbase is placed in “Heat” position, the “B”terminal being constantly energized from R. A thermostatdemand for heat completes R-Y circuit, pulling incompressor contactor starting compr...
Page 16 - FAN BLADE SETTINGS; SERVICE AND TROUBLESHOOTING; SERVICE HINTS
Manual 2100-344Page 14 FAN BLADE SETTINGS Shown in Figure 12 are the correct fan blade settingdimensions for proper air delivery across the outdoor coil. Any service work requiring removal or adjustment in the fanand/or motor area will require that the dimensions inFigure 12 be checked and blade adj...
Page 21 - from CAD to get size needed
Manual 2100-344Page 19 Wiring Diagram (4098-123) printed from CAD to get size needed