Page 4 - current should be less than 30mA; Model Description; A = Rated voltage of unit is 208V; Do not install; Refer to Installation section for other details regarding site; Series HumidiCleanTM Humidifiers
• This disconnecting switch should have leakage current protecting function. The max leakage current should be less than 30mA • The disconnecting switch should have a breaking capacity sufficient to interrupt the largest normal running current of loads. The breaking capacity required should be selec...
Page 6 - Installation; studs or other sturdy structure.; Water Fill Supply
Installation HC-6100/6300 Mounting The HumidiClean models HC-6100/6300 are designed to be wall mounted. A wall mounting bracketand lag screws are provided for mounting on 410 mm (16”) centers. The operating weight of the unit is106 kg (233 lbs). A clearance of 600 mm (23”) on the front and sides of ...
Page 7 - Drainage; Table 7-2. Steam Capacities and Rating Amperages
Drainage Connect HC-6000 drain to suitable waste drainage system. HC-6000 drain water may be as hot as 70°C (158°F). Use clear drain hose provided and 25 mm (1”) copper pipe pitched away from unit at 25 mm (1”) inch per foot. An air gap to prevent back flow is required. See Figure 7-1. 7 1-12 13-15 ...
Page 8 - Duct Steam Distribution
Duct Steam Distribution 1. The dispersion tube should be proper length. Verify correct size from Table 8-1. 2. Install dispersion tube(s) horizontally in duct so holes face upward. Air flow must be vertical up or horizontal. Do not restrict duct with a height of 200 mm (8”) or less. Installations ov...
Page 9 - Area Steam Distribution; for more; Alternative for shortened non-wettable vapor trail; for more information.; Control Wiring; Control Humidistat; below for correct switch settings.
Area Steam Distribution The EHF-3 fan package (minimum of 2 required for HC-6500/6700) is designed to be hung on a wallto operate as a remote mounted, direct area discharge option. It incorporates a blower rated at 120v-2.90 amps. CFM rating is 465 @ 1530 RPM. The fan package requires a separate 120...
Page 12 - Duct pressure switch will be wired in series with high limit; Alarm Circuit
High Limit Humidistat Remove the jumper tab from ground and in of high limit/pressure switch connections and wire the highlimit stat between these terminals. Refer to Figure10-1 (the overall wiring diagram) for more information. A duct mounted high limit humidistat is recommended to prevent over-sat...
Page 13 - Display Menu; Run Menu
The menu can be accessed via the keypad below the LCD, on the front of electric cabinet. Use the UPor DOWN to change the menu in current level; press ESC to previous menu level; press ENTER toaccess the current menu. Pressing ENTER will activate selection cursor, press UP(DOWN) to increase(decrease)...
Page 14 - Operation Setup
14 Enter Password 0000 (Default) Desired RH This menu is displayed when RH sensor is selected Desired RH: XX % Default: 50% Current RH: XX% Steam Generation Steam Gen (Default)Manual DrainManual FillUnit Stop Modulating Fill Cycle Enabled (Default)DisabledIf modulating fill cycle is enabled: Fill Va...
Page 15 - Operation Setup - Continued
15 Drain Frequency 6 Default: 12 hours 12 (Default)244896No DrainReal TimeReal Time Set24 Hour Clock Drain Time 15 (Default)10 Load Default Reset all to Default? Confirm Cancel Signal Type 0-10 Vdc (Default)0-5VDC1.9V - 3.9V4-20mA Sensor Select Humidistat (Default)RH Sensor High Limit Sensor High Li...
Page 16 - Unit Configuration; tightness of connections.
16 Enter Password ARMH Run Mode Run (Default)Test Contactor Count 1234 Control Type PWM (Default)On/Off Power Settings 1000 W3000 W5000 W6650 W8000 W Ionic Time Reset Clear Ionic TimeConfirm Cancel Error Record Clear Clear Error ListConfirm Cancel User Password Reset User Password ResetConfirm Cance...
Page 17 - Principle of Operation
Principle of Operation The HumidiClean humidifier converts ordinary tap water or purified water to steam for distribution toraise the relative humidity level. The demand for humidity is sensed by a humidistat or sensor whichsends a control signal to the HumidiClean. The HumidiClean is connected to t...
Page 18 - Save the settings, consult the OPERATION SETUP; Ionic Bed Inspection; Reset the Ionic Bed service life; Ionic Bed Replacement
Completing a Service Life Cycle When 90% of the setting service time has accumulated, the "STATE" LED on the control panel willblink in yellow. (Refer to EOL settings, for bed life duration settings). If the HumidiClean is not servicedat this time; the unit will continue to operate for the r...
Page 19 - ) Complete the steps for servicing the unit as outlined above.; End of Season Drain; menu
5) Restoring the Unit to Operation a) Turn power on at breaker. b) Unit should begin to fill. Maximum fill time is approximately 30-45 minutes before contactor(s) will be closed. c) If this does not take place, operate the menu, and change the status to "STEAM GEN." B. Modifying the Bed Life...
Page 20 - secure tank access panel.
Figure 20-1 HC-6100/6300 Figure 20-2 HC-6500/6700 4. Inspect tank drain screen and elements inside the tank. The elements should appear to be flaking off scale. If the drain screen appears to building deposits in the screen holes it should be cleaned. Remove any scale that appears in the bottom of t...
Page 21 - Cleaning the Water Level Electrodes; should energize, and the unit should completely drain.
9. Operate the unit configuration menu “Ionic Time Reset”, to reset the ionic bed life. All the accumulated ionic bed time has been reset to zero. The unit should now be heard filling. NOTE: The accumulated ionic bed time can be reset to zero at anytime. However, the unit should not be reset without...
Page 22 - Unlock and open front and side doors. Remove left side panel.; Troubleshooting; KNOW WHERE THE HIGH VOLTAGE PARTS ARE, AND; All resistance checks should be made with; Humidifier will not fill with water when power is applied.
Removing the Tank, HC-6100/6300 Only 1. Operate menu to "MANUAL DRAIN" and allow unit to complete a deep drain. ( Caution: Tank will still be quite warm). 2. Turn off circuit breaker. 3. Unlock and open front and side doors. Remove left side panel. 4. Disconnect 3 hoses from front of tank; r...
Page 23 - PC board. If continuity is OK, the PC board is likely defective.
8. If drain valve and fill valve are both energized and water is below the 1/3 full level in the electrode canister (float canister for DI units), make sure the status of Steam Generation in menu is "STEAM GEN.". Perform continuity check to be sure. 9. If drain valve only is energized and wa...
Page 24 - Humidifier overfills with water on initial fill.; clean or replace valve.
4. If fuses are OK, check voltage to contactor coil. (a) If voltage is 24-28VAC at contactor coil, check coil resistance. It should be 8 Ω with wires disconnected. If resistance is OK, check voltage drops across the contactor. (b) If no voltage to contactor coil, check continuity of wires from PC bo...
Page 25 - Humidifier does not drain when manual drain.
Humidifier runs continuously, %RH is well under set-point. 1. Verify humidistat/RH sensor is wired correctly and dip switches (S2 & S3, See Fig. 10-1, 11-1 and 11-1) on the PC board are set correctly for the humidistat signal. 2. Check humidistat demand signal at low voltage terminal strip. It s...
Page 26 - Dispersion tube spits water or water is present in duct; recommended to prevent this. See Installation section.; Water in bottom of cabinet; Check steam distribution piping for obstructions.; Diagnostics; FILL TIME OUT TO LOW LEVEL; - - The low level switch has not closed after 35 minutes of fill
Dispersion tube spits water or water is present in duct Hint: It is very helpful to cut a small observation window in the duct and cover it with Plexiglas so the steam discharge from the manifold can be observed. This way the problem can be narrowed down topiping/steam quality (steps 1 and 2) or a c...
Page 30 - HC6100-PAR Single Phase Wiring Layout
Page 39 - Heating Elements
39 Without TC 2PCS/Unit With TC 1PCS/Unit Without TC 2PCS/Unit With TC 1PCS/Unit 208 B5808-1 B5809-1 B5810-1 B5811-1 240 B5808-2 B5809-2 B5810-2 B5811-2 380 B5808-1 B5809-1 B5810-1 B5811-1 480 B5808-3 B5809-3 B5810-3 B5811-3 600 B5808-4 B5809-4 B5810-4 B5811-4 Without TC 2PCS/Unit With TC 1PCS/Unit ...
Page 43 - Procedure of HC6000 Version 7 Soft Refresh; Before refreshing the code, the old code in CPU must be erased:
Procedure of HC6000 Version 7 Soft Refresh This section is used for HC6000 software reprogramming only. Please follow the instructions carefully,or pc board could become un-functional. 1. Install the driver program for Atmel MCU, SAM-BA on your computer first. The link for the Atmel program AT91-ISP...
Page 46 - Introduction to Communications; can select different modules to connect different port)
g. When operation has finished, close the "SAM-BA" window first, and then click the icon "remove the USB hardware" to disconnect the link between computer and board. After reminder by system, disconnect the power supply from breaker and pull out the USB cable. h. The soft refresh of ...
Page 47 - Table 46-1 Modbus Variable Lists
Table 46-1 Modbus Variable Lists 47 data type attribute data address description 10001 Fill valve status 0:off 1:on 10002 Drain valve status 0:off 1:on 10003 contactor 1 status 0:off 1:on 10004 contactor 2 status 0:off 1:on 10005 contactor 3 status 0:off 1:on 10006 contactor 4 status 0:off 1:on 1000...
Page 50 - Physical Data, Capacities and Dimensional Drawings
50 Knock-Out for Humidistat 1” Drain Electrical Supply Knock-Out forHumidistat A H G B J K E D M L R H C F Physical Data, Capacities and Dimensional Drawings Figure 49-1. Models HC-6100 and HC-6300 Table 134-1. Physical Data Inches mm Inches mm "A"-Width 21-15/16 557 26 660 "B"-Heigh...
Page 52 - Limited Warranty and Remedy; DOES NOT MAKE ANY OTHER REPRESENTATIONS OR WARRANTIES, EXPRESS OR; The Limited Warranty and Remedy; armstrong
Armstrong International, Inc. Limited Warranty and Remedy Armstrong International, Inc. ("Armstrong") warrants to the original user of those products supplied byit and used in the service and in the manner for which they are intended, that such products shall befree from defects in material ...