Page 4 - - for pipes with an inside diameter
4 1. GENERAL 1.1 Description of theappliance Construction of the water heater is inaccordance with the Europeanstandard for gas heated water storageheaters for sanitary application (EN89).The appliance thus meets the EuropeanDirectory for Gas Appliances and istherefore entitled to carry the CE-marki...
Page 6 - Electrical connection
6 1.2 Technical safety equipment 1.2.1 Gas control valve The water heater is equipped with agas control wich regulates the flow ofgas to the burner. The gas block isequipped with a safety valve, gas valveand burner control (on a standardnatural gas setting). To ensureimproved ignition the gas contro...
Page 7 - discharge safety device
7 1.2.3 Operation of the storage water heater. Normal operation When there is a demand for heat awaiting period of about 1 secondelapses before the built-in spark gene-rator and pilot gas valve are switchedon. The ignition sparks ignite the pilotburner and the resulting flame isdetected by the ionis...
Page 8 - Dimensions; Technical information
8 A 1585 1780 B 1450 1640 D 645 675 F 770 775 G 130 130 K 340 340 L 355 370 M 1505 1685 N 1505 1685 P 210 210 R 285 285 S 1280 1460 V 410 410 1 Cold water inlet 2 Hot water outlet 3 Gas control 4 Drain valve 5 T&P relief valve tapping 6 Clean out Dimensions BTI 85 BTI 100 1.3 Technical informati...
Page 10 - device category: II; unit; DESCRIPTION
10 DATA NATUREL GAS G20 - 20 mbar Nominal capacity kW 19.2 20.4 Nominal load (gross) kW 25.1 26.7 Supply pressure mbar 20 20 Burner pressure mbar 12.0 7.9 Gas consumption * m 3 /h 2.40 2.50 Diameter main orifice mm 3.90 4.50 Diameter pilot orifice mm 0.56 / 0.41 0.56 / 0.41 Heating time ∆ T= 45K min...
Page 12 - Installation instructions; For domestic applications:
12 2. FOR THE INSTALLER 2.1 Installation instructions This water heater must be fitted in alocation which will permit the provisionos an approved flue system and ade-quate ventilation. A service clearance of 15 cm at thesides and rear of the unit and 60 cm atthe front of the unit should be allowedfo...
Page 13 - Vented systems
13 Figur 4 - Connection diagram ventedsystems Therefore if this water heater will beused to supply hot water to:- hairdressers, - dry cleaners, - industrial degreasing processesor any other area wherecompounds containing halogens areused and stored, care should be taken that all primary and secondar...
Page 14 - Unvented system
14 Unvented system (See figur 5) To install an A.O. Smith water heater onan unvented cold water supply systema kit of valves and fittings fisted by thewater reseach centre and complyingwith part G3 of the current buildingregulations should be used. Installationshould be carried out generally asshown...
Page 15 - Important; The connecting clamps
15 2.1.3 Gas connection The gas supply to this appliance mustbe installed in accordance with BS 6891(1988) and British Gas Publications UP1and UP2.Fit the 1/2” gas supply cock suppliedwith this unit immediately before the gascontrol. No heat or soldered jointsshould be applied in the vicinity of the...
Page 16 - Commissioning
16 2.2 Commissioning 2.2.1 Filling the water heater 1. Close the drain tap.2. Open the cold water tap to the water heater and open all taps where hotwater can be drained for deaeration. The water heater is filledas soon as cold water flows from alltaps. 3. Close all hot water taps. 2.2.2 Putting int...
Page 17 - Setting the gas pressure
17 2.3 Removing andreplacing the controlpanel front cover Removing the cover (see figure 7) 1. Remove the screw at the top centre of the control panel. 2. Push the cover upwards until the hooks at the lower end clear theburner access opening and base tray. 3. Pull the lower end of the cover slightly...
Page 19 - Maintenance; Open the nearest hot water tap in
19 2.7 Converting to another type of gas For conversion of the appliance fromnatural gas to another type of gas, orvisa versa, it is necessary to exchangethe pilot injector and the main injector.The conversion may only be executedby a qualfied competent person. Procedure:1. Shut the heater down. Clo...
Page 20 - Important warning
20 2.8.2 Cleaning 1. Close the gas supply and demount the burner after it has cooled down 2. Disconnect the burner assembly from the gas control 3. Remove the complete burrner assembly 4. Clean the burner with a soft brush5. Check the pilot burner and clean it if so required 6. Check the combustion ...
Page 21 - Commisioning; Warning
21 3. FOR THE USER 3.1 Commisioning Warning Installing and commissioning of this wa-ter heater should only be carried out bya qualified competent heating engineer. 3.1.1 Filling the water heater 1. Close the drain tap;2. Open the cold water tap to the water heater and open all taps where hotwater ca...
Page 22 - Fault overview; Failure
22 3.2 Fault overview Gas smell If you smell gas you should immediately close the main gas tap, you should not fight any fire or switch on light. electrical switches or bels. Open windows and immediately contact your installer or the local gas company Heater is Burner automat is in lock Reset burner...
Page 25 - APPENDIX 1; Connection diagram BTI models; A = Ignition controller
= b r o w n= blue= yellow/green= black= w h i t e= red * = Optional APPENDIX 1 Connection diagram BTI models A = Ignition controller M = Remote button B = ON/OFF switch N = Terminal block C = Pilot burner P = Terminal block D = Spark electrode R = Earth terminals E = Flame probe S = Connector F = Tr...