Page 2 - Contents
Contents 1. Safety and Conformity 2 Safety Information 2 Hazards of PV Systems 3 PV Load Switch 3 Conformity 4 Approvals and Certifications 4 2. Introduction 5 Introduction 5 Installation Sequence 6 Overview of Inverter 7 3. Installation 8 Installation Dimensions and Patterns 8 Mounting the Inverter...
Page 3 - All persons installing and servicing inverters must be:; Safety and Conformity
1. Safety and Conformity 1.1. Safety Information All persons installing and servicing inverters must be: • Trained and experienced in general safety rules for work on electrical equipment • Familiar with local requirements, rules and regulations for the installation Safety information important for ...
Page 4 - Illustration 1.1: Protect PV PV Load Switch
Before installation:Check for damage to inverter and packaging. If in doubt, contact the supplier be-fore installing the inverter.Installation:For optimum safety, follow the steps described in this manual. Keep in mind thatthe inverter has two voltage carrying sides; the PV input and the AC grid.Dis...
Page 7 - Product Label
Protect PV variant User interface Ancillary services DC power rat- ing Local Web Server Power Level Adjust- ment, Primary Frequency Control Ride Through Fault Ride Through Reactive Power 10 kW 12.5 kW 15 kW Protect PV ✓ ✓ ✓ ✓ ✓ Protect PV easy ✓ ✓ ✓ ✓ ✓ ✓ Table 2.1: Differing Features of Protect PV ...
Page 8 - Illustration 2.3: Overview of AEG PS Protect PV inverter; Live Part
2.1.2. Overview of Inverter Illustration 2.3: Overview of AEG PS Protect PV inverter Live Part 1. AC Connection Area 2. DC Connection Area 3. Terminal block for parallel connection 4. Auxiliary output: Potential free relay PELV (Safe to touch) 5. Auxiliary interface: RS485 6. Auxiliary interface: Te...
Page 9 - Installation Dimensions and Patterns
3. Installation 3.1. Installation Dimensions and Patterns Note: When choosing the installation place, ensure that all labels are visible at all times.For details refer to the section Specifications. Avoid constant stream of water. Avoid direct sunlight. Ensure adequate air flow. Ensure adequate air ...
Page 12 - Loosen the locking screws on either side of the inverter.
Illustration 3.5: Place Inverter in MountingBracket Place the lower part of the inverter againstthe mounting bracket. Illustration 3.6: Fasten screws Lower (4) the inverter and make sure thatthe hook of the inverter base plate is placedin the lower part of the mounting bracket(5). Check that it is n...
Page 21 - ’ to scroll down through the list of coun-; Illustration 4.6: Confirm Country Selection
Illustration 4.4: Installed PV Power Enter the amount of installed PV power foreach of the PV inputs. When two or more PVinputs are connected in parallel, each PV in-put in the parallel group must be set to thetotal amount of PV power installed to thatgroup divided by the number of parallel in-puts....
Page 22 - programmed
Note: If the two country selections do not match they will be cancelled and it will be necessary toredo the selections. If a wrong country is accidentally accepted at the first selection, simplyaccept the “Country: Undefined” in the confirm country screen. This will cancel the countryselection and a...
Page 27 - Ambient temperature
Illustration 5.1: Protect PV 10 kW Cable Losses [%] versus Cable Length [m] Illustration 5.2: Protect PV 12.5 kW Cable Losses [%] versus Cable Length [m] Illustration 5.3: Protect PV 15 kW Cable Losses [%] versus Cable Length [m] Consider also the following when choosing cable type and cross-section...
Page 28 - UV resistance; Parameter
- Layout type (inside wall, under ground, free air etc.) - UV resistance Illustration 5.4: Overview of Inverter with Torque Indications Parameter Screwdriver Tightening Torque 1 Front screws TX 30 6-8 Nm 2 Locking screw TX 30 5 Nm 3 Terminal blocks (small) Straight slot 0.5x3.0 mm 0.5 Nm 4 Terminal ...
Page 33 - Tel.outside office hours
Lit. No. L00410564-01_02 Rev. date 2011-05-25 France & Africa AEG Power SolutionsZI 10 rue Jean Perrin37173 Chambray-lès-ToursTel: + 332 47 80 88 96 Fax: + 332 47 80 88 38 Email: [email protected] United Kingdom AEG Power Solutions Ltd.Vision 25Innova ParkEnfield EN3 7XYTel: +44 (0) 1992 719 ...