Page 2 - INDEX; Applications & Technical Data; Best
2 SERIES MBS 32 / MBS63 INDEX Mbs32 - 22kA Standard breaking capacity 32 Amp MBS32 SG to 20HP 460V Mbs32 - 50kA High breaking capacity 32 Amp MBS32 HG to 20HP 460V A AE EG G M Mo otto orr C Ciirrc cu uiitt P Prro otte ec ctto orrs s F F E E A A T T U U R R E E S S & & B B E E N N E E F F II ...
Page 3 - MBS32 / MBS63 AEG MOTOR CIRCUIT PROTECTORS; MOTOR CIRCUIT PROTECTORS; The
MULTIPLE UL APPLICATIONS 1. Replaces the up to 50 kA Circuit Breaker or fuses in a combination starter. The overload relay is replaced. 2. Replaces through the door interlocking power disconnects in panels, variable speed drives or Motor Control Machine panels. 3. Group Installations per NEC 430-53....
Page 4 - D e s i g n F e a t u r e s; IC; MID; Emergency mushroom; See page 14 for ordering details.
Catalog Number: MI55 MIT55 Surface Mount Flush Mount MBS32 / MBS63 MBS32 / MBS63 FEATURES & BENEFITS D e s i g n F e a t u r e s • / UL 508 & 508E Listed • Class 10 Overload Trip • Adjustable Thermal Protection 0-63 Amps • Ambient temperature compensated (-20 º C - +60 º C) - 4.0 º F - +140 ...
Page 5 - APPLICATIONS; Save on Panel Space, Component Costs, Wiring and Mounting Time; GROUP INSTALLATIONS; Type E; Motor Load; DO NOT; Require
MBS32 / MBS63 APPLICATIONS 5 Save on Panel Space, Component Costs, Wiring and Mounting Time Applications Include: Pumps, Compressors, Multi Motor Machiner y such as Conveyors, Machine Tools, Textile and Packaging Equipment GROUP INSTALLATIONS INDIVIDUAL INSTALLATIONS The MBS Motor Circuit Protector ...
Page 6 - Thermal and magnetic protection; MBS32 SPECIFICATIONS; F e a t u r e s; D i m e n s i o n s ( M B S 3 2 ) S e r i e s; Range; Te c h n i c a l p e r f o r m a n c e s
MBS32 Thermal and magnetic protection MBS32 SPECIFICATIONS DIMENSIONS F e a t u r e s • Standard (22kA) & High Interruption Version (50kA) (up to 100kA IC for units to 13Amps) • Current Range 0.1 - 32Amp • Thermal and Magnetic Protection • Standard and High Breaking Capacity • Visible Trip Condi...
Page 7 - M B S 3 2 S G; Rotary; M B S 3 2 H G; SELECTION
Rocker Lever Operation, “Standard Interruption”, 1 3/4” 45mm Width M B S 3 2 S G Rotary Operation, “High Interruption”, 1 3/4’’ 45mm Width M B S 3 2 H G 50kA Interruption Capacity (480V) Instantaneous Open Nema 1/3R FLA Three Phase Single Phase Short Circuit Catalog List Enclosed Adjustment HP HP Re...
Page 8 - S t a n d a r d s / A p p r o v a l s
MBS63 SPECIFICATIONS DIMENSIONS Te c h n i c a l p e r f o r m a n c e s • Rated current adjustable 6.3 - 63A • Rated operational current 6.3 - 63A • Utilization category IEC 60947-2 (Circuit Breaker) IEC 60947-4-1 (MMS) • Tripping Class 10 • Magnetic release - -13x max amp setting • Mechanical/elec...
Page 9 - “HIGH INTERRUPTION”; THREE PHASE AND SINGLE PHASE CONNECTIONS
MBS63 CONTROLLER “HIGH INTERRUPTION” Selection of the controller depends on the actual motor full load current and service factor. For motors with service factor of 1.15 or greater, use motor full load current to select the approximate current range. For motors with a service factor less than 1.15, ...
Page 10 - INTERNATIONAL SPECIFICATIONS; Technical Specifications
MBS32 / MBS63 INTERNATIONAL SPECIFICATIONS 10 Technical Specifications Frame size Rated insolation voltage Ui Rated operating voltage Ue Rated impulse withstand strength Uimp Rated frequency Total power loss P (W) Utilization category: IEC 947-2 (Circuit Breaker) IEC 947-4-1 (Motor starter) Mechanic...
Page 11 - Accessories; AUXILIARIES
P r o d u c t r a n g e o f A c c e s s o r i e s - Auxiliary contacts (frontal & lateral)- Alarm contact block- Auxiliary and alarm contact block - Short-circuit alarm contact block- Undervoltage release- Undervoltage release with 2NO early make contacts- Shunt Trip Device S t a n d a r d s / A...
Page 12 - AUXILIARY ACCESSORIES; Auxiliary contact blocks; with two “separate contacts”; Auxiliary Explanation; Side Contact Blocks: 4 Amps at 110Vac or 230Vac
Side mounting on the left MBS32... and MBS63... 1NO(Alarm)+1NO(Aux) MAHSS11LL $15 Two contacts NO + NC Mechanical indication marking Side mounting on the left (front alarm MBS32... and MBS63... 1NO(Alarm)+1NO(Aux) MAHSD1010LL $22 contact block can not be used at the MBS32... and MBS63... 1NO(Alarm)+...
Page 13 - Shunt trip device
13 Protection against accidental MBS63... MAPTP63 $6 finger touch (IP20) forMBS63 manual motor starters Side mounting on the “right” MBS32... and MBS63... 24V 50Hz MARLRAD $62 (Can not be used together with MBS32... and MBS63... 24V 60Hz MARLRAC 62 the shunt trip device) MBS32... and MBS63... 48V 50...
Page 14 - Enclosures for MBS32 SG; Mounting accessories for MBS32SG enclosures only
ENCLOSURE & ACCESSORIES FOR MBS32SG ONLY Enclosures for MBS32 SG Description Cat. no. List For MBS32 SG ONLY Mounting accessories for MBS32SG enclosures only Description Cat. no. List IP55Dust Tight / Water Tight Surface Mount Flush Mount Momentary Maintained (Twist Release) Maintained (Key Rele...
Page 15 - ACCESSORIES; External handle operators; Combination Starter Components
LS4...LS5K...LS7K...LS11K AC/DC MBS32 MF32B1 $20 LS12K..., LS15K.. AC MBS32 MF32B4 20 LS12K...,LS15K...,LS18K.. AC/ DC MBS63 MF63B2 30 LS22K...,LS30K.. AC/DC MBS63 MF63B3 30 LS12K...,LS15K.. AC MBS32/63 MF32C11B 6 LS05.. AC/DC MBS32 MF32L05B $6 LS4K...,LS5K...,LS7K.. AC MBS32 MF32L7A 9 LS4K...,LS5K....
Page 16 - Wiring Kits for Reversing Starters; Busbar System
BUSS BAR ACCESSORIES FOR MOTOR PROTECTORS & CONTACTORS 16 Discount Schedule ST MF32R05B LS05 AC or DC $15.00 MF32R7B LS4K, 5K, 7K AC or DC $19.00 MF32R11B LS11K AC or DC $20.00 MF63R15B LS15K AC or DC $31.00 MF63R18B LS18K AC or DC $34.00 MF63R30A LS22K-LS30K AC only $50.00 List Price Cat. No. U...
Page 17 - MOTOR CIRCUIT; MANUAL STARTER; High Fault Current
ELECTRICAL & ELECTRONIC CONTROLS, INC. 7 WEST CROSS ST HAWTHORNE, NY 10532 914-769-5000, FAX 914-769-3641 www.eecontrols.com E-MAIL: [email protected] EECONTROLS, LTD 17 STEWART COURT ORANGEVILLE, ONTARIO CANADA L9W 3Z9 519-941-6845, FAX 519-940-0514 SERIES MBS25 MOTOR CIRCUIT PROTECTOR MANUAL ...
Page 18 - MOTOR CIRCUIT PROTECTOR; A Manual Disconnect and; Typical MBS Trip Curve B; MBS 25 with UV Trip
• Used as a manual motor starer, with the high short-circuit fault breakingcapacity of a circuit breaker, in accordance with VDE 0600, IEC 292, and IEC 157-1.• Single phase sensitivity and ambient temperature compensated thermal over-load trip. (NEMA Class 10)• Main switch and emergency disconnectsw...
Page 19 - MBS-25 Three Phase 3 Pole 600 Volt MCP + Manual Starter; Mounting
ECONOMICAL MOTOR CIRCUIT MBS25 PROTECTOR 19 Discount Schedule ST MBS-25 Three Phase 3 Pole 600 Volt MCP + Manual Starter Thermal Three Phase Overlaod Relay Horse Power Adjustment 200V 230V 460V 575V Range (AMP)* 0.25-0.4 0.4-.63 1/4 1/2 1/2 .63-1.0 1/4 1/3 3/4 1 1.0-1.6 1/2 1/2 1 1-1/2 1.6-2.5 3/4 1...
Page 20 - ENCLOSURES & ACCESSORIES; Overall Dimensions; MBS 25 Accessories
Enclosure Type S4 IP55 Dust/Watertight MBS25-S4 $30 Enclosure, NEMA 7 Hazardous Area MBS25-M7 $665 Flush Plate with Gasket IP55 Dust/Watertight MBS25-S4F $16 Replacement Start/Stop Boot MBS25-S4-116 $8 Neutral Link for mounting above enclosures MBS25-114 $7 Padlock Accessories for enclosures for MBS...
Page 21 - Three Phase 3 Pole 600 Volt; MBS25 MOTOR / CIRCUIT; COMBINATION MANUAL MOTOR CONTROLS; “NEW PRODUCT”
Thermal Three Phase Overlaod Relay Horse Power Adjustment 200V 230V 460V 575V Range (AMP)* 0.25-0.4 0.4-.63 1/4 1/2 1/2 .63-1.0 1/4 1/3 3/4 1 1.0-1.6 1/2 1/2 1 1-1/2 1.6-2.5 3/4 1 2 3 2.5-4 1-1/2 1-1/2 3 5 4-6 2 3 5 7-1/2 6-10 3 5 10 10 10-16 5 7-1/2 15 15 16-20 - 7-1/2 15 20 20-25 Basic Catalog No....
Page 22 - Self Protected Combination; ELECTRICAL & ELECTRONIC; COMPLETE; COMBINATION; Combination Starters; Interruption Capacity; NEMA 4X; NEMA RATED CONTACTORS
B Brreeaakkeerr C Co om mb biin naattiio on nss:: * Type MBS32 and MBS63 Conformity to Standards: UL508E (MBS Type) AEG Type MBS Combinations Meet the NEW UL508 Type E Requirement for Self Protected Combination Controllers & Meets UL508E (Type 2 Coordination) ELECTRICAL & ELECTRONIC CONTROLS...
Page 23 - MBS32 / MBS63 AEG Combination Motor Controllers; General Applications; Combination Controller; Specific Additional Applications; COMBINATION ADVANTAGES; Description; Rating; The accessories include:; Front & Side Mount Auxiliaries; (Short circuit with reset indicator; Shunt Trip; dangerous automatic restarts when
ADVANTAGES : • 1/2 the size! • Cost Savings • Higher Interruption Capacity NEW WAY MBS32/63 LSK Contactor MBS32 / MBS63 AEG Combination Motor Controllers General Applications • Combination Controller (self protected) • Manual Motor Controller • Group Installed Controller Specific Additional Applicat...
Page 24 - TYPICAL ORDER ITEM; Combination Short Circuit KAIC Rating; MBS SERIES; Open MBS Combinations
* For “SW” Add for DC Power Plant, (single winding) LS05..... add $10 List LS4K-LS11K.... add $45 List LS15K-LS22K... add $65 List “TW”; LS30K - add $65 List 0.63-1.0 - - - - 1/2 1/2 1-1.6 - 1/10 1/4 1/3 3/4 3/4 1.6-2.5 - 1/6 1/2 1/2 1 1 1/2 2.5-4 1/8 1/3 3/4 3/4 2 3 4.0-6.3 1/4 1/2 1 1 1/2 3 5 6.3-...
Page 25 - Enclosed MBS Combinations; Motor Protector
MBS SERIES COMBINATIONS ENCLOSED TYPE 25 Discount Schedule ST MBS32CH-010-* = MBS32HG-010 $101 LS05.10-* $40 MBS32CH-016-* = MBS32HG-016 $101 LS05.10-* $40 MBS32CH-025-* = MBS32HG-025 $101 LS05.10-* $40 MF32L05B $6 None $0 - 0 MBS32CH-040-* = MBS32HG-040 $101 LS05.10-* $40 MBS32CH-063-* = MBS32HG-06...
Page 26 - COMBINATION STARTER; With a “standard” interruption
HAND - OFF - AUTO (Nema 1) -KSL-1 $35.00 OFF - ON - SELECTOR (Nema1) -KSN-1 $35.00 HAND - OFF - AUTO SELECTOR (Nema 12,4X,3R) -KSL-3 $90.00 OFF - ON - SELECTOR (Nema 12,4X,3R) -KSN-3 $90.00 START / STOP OPERATOR (Nema 3R,12,4X) -KSS-3 $90.00 START / STOP OPERATOR (Nema1) -KSS-2 $35.00 HAND-OFF-AUTO ...
Page 27 - “OPEN”; Combination Dimensions; DIMENSIONS; Dimensions; STANDARD SHAFT; Type
27 “OPEN” Combination Dimensions DIMENSIONS MBS MMP & COMBINATIONS Dimensions (Approx. Inches) A B C D E MBS32C”H”-010-063 6 1/8 1 3/4 4 1/2 2 5/8 2 5/8 MBS32C”S”-010-063 6 1/8 1 3/4 3 5/8 2 5/8 2 5/8 MBS32C”H”-100-160 8 1/8 1 3/4 4 1/2 4 1/4 5 1/4 MBS32C”S”-100-160 8 1/8 1 3/4 3 5/8 4 1/4 5 1/4...
Page 28 - COMBINATION STARTERS; TYPE “; LS; ” CONTACTORS; CERTIFIED PER AND; KEY FEATURES; MBS32 & MBS63 Motor Protectors; Example; : LS27 Other Approvals; The additional advantages
28 Group Motor Installation COMBINATION STARTERS THE “NEMA” CONTACTOR OPTION TYPE “ LS ” CONTACTORS NEMA CERTIFIED PER AND Additional Tests Completed and NEMA Certified LS7 - NEMA Size 0 LS27 - NEMA Size 1 NEMA SIZE 0 NEMA SIZE 1 KEY FEATURES 1- UL, NEMA rated Contactor 2- Type 2 Coordination (UL508...
Page 29 - COMBINATION CONTROLLER.; Type BC-XLS Combination Controller includes:; C I R C U I T B R E A K E R T Y P E E N C L O S E D ( L I S T P R I C E ); OVERLOAD RELAY SUFFIX
Order Example: 15 HP 480V #BC XLS27-1E-N-MO1 $684 LIST TYPE 4X ENCLOSED STARTERS Type 4X starters include UL/CSA Listedstarters enclosed in Type 4X U.L. / CSAlisted enclosures. Type 4X enclosures are designed for outdoor/hose down/dust tight applications and are non-metal corrosion resistant. Design...
Page 30 - load break, UL Listed for Motor Load Switching Duty.; Check with factory
COMBINATION STARTERS (Non Reversing) FUSIBLE DISCONNECT TYPE FC-XLS COMBINATION CONTROLLER. Type FC -XLS per UL 508 Industrial Control Standard. Type FC-XLS includes: a. UL/CSA Manual Motor Disconnect with door safety interlocks. Industrial Control Disconnects are load make, load break, UL Listed fo...