THE WALL-MOUNT™ ONE TON AIR CONDITIONER

The Bard Wall-Mount One Ton Air Conditioner is a self contained energy
efficient heating and cooling system, which is designed to offer maximum
indoor comfort at a minimal cost without using valuable indoor floor space or
outside ground space. The One Ton is the ideal product for versatile
applications such as: new construction, modular offices, school
modernization, telecommunication structures, portable structures or
correctional facilities. Factory or field installed accessories are available to
meet specific job requirements.

Alarm Relay:

Dry contacts for remote alarm on
high or low pressure lockouts.

Low Ambient Control:

Permits operation down to 0°F
outdoor ambient. Can be factory
or field installed.

Engineered Features

Optional Product Features

Fully Modulating Economizer:

Can be factory or field installed.

Commercial Room Ventilator:

Can be factory or field installed.

Aluminum Finned Copper Coils

Grooved tubing (evaporator coil only)
and enhanced louvered fin for maximum
heat transfer and energy efficiency.

Quiet Twin Blowers:

Designed to accept full ducted system
or for non-ducted free blow installations.

High Efficiency Rotary
Compressor

R-410A Refrigerant:

Designed with R-410A (HFC) non-ozone
depleting refrigerant in compliance with
the Montreal protocol and 2010 EPA
requirements.

Liquid Line Filter Drier:

Standard on all units. Protects system
against moisture.

Galvanized 20 Gauge Zinc Coated
Steel Cabinet:

Cleaned, rinsed, sealed and dried before
the polyurethane primer is applied. The
cabinet is handsomely finished with a
baked on textured enamel, which allows
it to withstand 1000 hours of salt spray
tests per ASTM B117-03.

Electrical Components:

Are easily accessible for routine
inspection and maintenance through a
right side, service panel opening.

One Inch, Disposable Air Filter:

Easily removed for replacement from
the outside. Optional two-inch pleated
filter, factory or field installed.

Top Rain Flashing:

Standard feature on all models.

Slope Top:

Standard feature for water run-off.

Compressor Control Module:

Standard on all units. Built-in off-delay
timer adjustable from 30 seconds to 5-
minutes. 2-minute on-delay if power
interrupt. 120-second bypass for low
pressure control, and both soft and
manual lockouts for high and low
pressure controls. Alarm output for
alarm relay.

High & Low Pressure Switches are
Auto-Reset:

Standard on all units. Built-in lockout
circuit resets from the room
thermostat. Provides commercial
quality protection to the compressor.

Barometric Fresh Air Damper:

Allows up to 100 CFM of fresh air.

Automatic Condensate
Disposal System:

Eliminates the need to provide a
separate condensate drain. The drain
valve closes at temperatures above
40° and opens when the temperature
drops below 40°. Built-in slinger ring
fan blade.

Full Length Mounting Flanges

:

Built into cabinet for improved
appearance and easy installation.

W12A

60Hz

10,800 Btuh

9.00 EER

Right Side Control Panel

Complies with efficiency requirements of ANSI/ASHRAE/IESNA 90.1-2010.

Certified to ANSI/ARI Standard 390-2003 for SPVU (Single Package Vertical Units).

Intertek ETL Listed to Standard for Safety Heating and Cooling Equipment ANSI/UL

1995/CSA 22.2 No. 236-05, Fourth Edition.

Commercial Product - Not intended for Residential application.

G

REEN

R

EFRIGERANT

R-410A

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Specifications

Form No. S3401-812 Supersedes S3401-510Page 2 of 8 1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. 2 Based on 75°C copper wire. All wiring must conform to NEC and all local codes. 3 These “Minimum Circuit Ampacity” values are to be used f...

Page 3 - Ventilation System Packages

Form No. S3401-812 Supersedes S3401-510 Page 3 of 8 Bard Wall-Mounts are designed to provide optional ventilation packages to meet all of your ventilation and indoor air quality requirements. Allunits are equipped with a barometric fresh air damper as the standard ventilation package. All ventilatio...

Page 5 - This Page Intentionally Left Blank

Form No. S3401-812 Supersedes S3401-510 Page 5 of 8 This Page Intentionally Left Blank