Page 2 - CONTENTS
Manual 2100-467 Page 2 of 23 CONTENTS Getting Other Informations and Publications ........ 3 General Instructions Important ................................................................ 4Shipping Damage .................................................... 4General ...................................
Page 3 - Getting Other Information and Publications
Manual 2100-467 Page 3 of 23 Getting Other Information and Publications These publications can help you install the airconditioner or heat pump. You can usually find these atyour local library or purchase them directly from thepublisher. Be sure to consult current edition of eachstandard. National E...
Page 4 - GENERAL INSTRUCTIONS; IMPORTANT; TABLE 1
Manual 2100-467 Page 4 of 23 GENERAL INSTRUCTIONS IMPORTANT The equipment covered in this manual is to be installedby trained, experienced service and installationtechnicians. All duct work, supply and return ducts,must be properly sized for the design air flowrequirement of the equipment. ACCA is a...
Page 6 - stl
Manual 2100-467 Page 6 of 23 TABLE 3 OPTIONAL FIELD INSTALLED HEATER PACKAGES ONLY TO BE USED WITH THE MODELS INDICATED e g a k c a P r et a e H l e d o M & stl o V e s a h PA - 1 4 2 3 1 A PA - 1 0 3 3 1 A PA - 1 6 3 3 1 A PB - 1 6 3 3 1 A PA - 1 2 4 3 1 A PB - 1 2 4 3 1 A PA - 1 8 4 3 1 A PB -...
Page 8 - Unit Dimension Chart
Manual 2100-467 Page 8 of 23 FIGURE 1 DIMENSIONS OF UNITS MIS-2142 Unit Dimension Chart Condenser airintake grille Condenser air intake grille Blower motor access door Condenser fan G 47 11/16" H Compressor access door Control panel door Heater package access panel Return opening Supply opening ...
Page 9 - INSTALLATION; LOCATION; GENERAL; TYPICAL INSTALLATIONS; ROOF MOUNTED; – The unit is mounted on a; CRAWL SPACE; – Duct work installed in crawl; SLAB MOUNTED AT GROUND LEVEL; This; THROUGH THE WALL; – This type installation
Manual 2100-467 Page 9 of 23 INSTALLATION LOCATION GENERAL The unit must be located outside, or in a well ventilatedarea. It must not be in the space being heated or cooled.A sound absorbing material should be considered if theunit is to be installed in such a position or location thatmight cause tr...
Page 10 - Side; Supply Duct; Air Outlet
Manual 2100-467 Page 10 of 23 24" min. 36" min. 24" min. The distance between 1 inch clearance Air Inlet Air Inlet Supply and Return Ducts Building Heater Package Access Control Panel Access Blower Service Access Blower and Blower Motor Heater Package Control Panel Comp- ressor Nearest S...
Page 11 - AS REQUIRED
Manual 2100-467 Page 11 of 23 FIGURE 4 ELEVATED MOUNTING PLATFORM 48" min. 32°F or lower climate 12" min. if in on surface of platform Both legs must rest 48" min. 32°F or lower climate 12" min. if in on surface of platform Both legs must rest Metal frame MIS-2144 Platform can be as ...
Page 12 - CONDENSATE DRAIN TRAP; It is impossible to; TABLE 5
Manual 2100-467 Page 12 of 23 FIGURE 5 CONDENSATE DRAIN TRAP 5. OTHER INSTALLATIONS – Many other installations are possible with the packaged airconditioner. No matter what the installation, alwaysconsider the following facts: A. Insure that the discharge air is not obstructed in any way so as to ca...
Page 13 - TRANSFORMER TAPS; TAP; WIRING – MAIN POWER; All models are; THERMOSTATS; TABLE 7
Manual 2100-467 Page 13 of 23 TABLE 6 THERMOSTAT WIRE SIZE A V r e m r o f s n a r T A L F e g u a G e r i W m u m i x a M e c n a t s i D t e e F n I 5 5 3 . 2 0 2 8 1 6 1 4 1 2 1 5 4 0 6 0 0 1 0 6 1 0 5 2 TRANSFORMER TAPS 230/208V, 1 phase and 3 phase equipment employ dualprimary voltage transform...
Page 14 - HEAT ON UNITS WITH 15 OR MORE KW; DH; Unit Control Panel; OR; REMOVE JUMPER FOR 2 STAGE ELECTRIC; FIGURE 6
Manual 2100-467 Page 14 of 23 HEAT ON UNITS WITH 15 OR MORE KW W MIS-2149 D1 DH W3 OR E2 Unit 24V Block Y C G R Y1 B W1 W2 L E Y1 C G R W1 B Y2 R Terminal W2 W3 P L D E E L W2 B W1 R G C A1 Unit Control Panel G Y Y T8400C1313 Thermostat Subbase IF93-380 OR T8511G1070 REMOVE JUMPER FOR 2 STAGE ELECTR...
Page 15 - START UP; TOPPING OFF SYSTEM CHARGE
Manual 2100-467 Page 15 of 23 START UP These units require R-410A refrigerant and polyolesteroil. GENERAL: 1. Use separate service equipment to avoid cross contamination of oil and refrigerants. 2. Use recovery equipment rated for R-410A refrigerant. 3. Use manifold gauges rated for R-410A (800 psi/...
Page 16 - NOTE: If compressor is allowed to run in reverse; SEQUENCE OF OPERATION; BLOWER ONLY; INDOOR BLOWER MOTOR; START UP AND OPERATION
Manual 2100-467 Page 16 of 23 THREE PHASE SCROLL COMPRESSORSTART UP INFORMATION (PA1336, 42, 48 and 60 Models) Scroll compressors, like several other types ofcompressors, will only compress in one rotationaldirection. Direction of rotation is not an issue withsingle phase compressors since they will...
Page 17 - soft lockout; ALARM OUTPUT; NOTE: Both high and low pressure switch controls are; ADJUSTMENTS; Optional Low Ambient Control
Manual 2100-467 Page 17 of 23 HIGH PRESSURE SWITCH AND LOCKOUTSEQUENCE (Standard Feature) If the high pressure switch opens, the compressorcontactor will de-energize immediately. The lockouttimer will go into a soft lockout and stay in soft lockout until the high pressure switch closes and the delay...
Page 18 - FAN BLADE SETTINGS; SERVICE AND TROUBLESHOOTING; SERVICE HINTS; Caution homeowner to maintain clean air filters at; PRESSURE SERVICE PORTS
Manual 2100-467 Page 18 of 23 FAN BLADE SETTINGS Shown in Figure 8 are the correct fan blade settingdimensions for proper air delivery across the outdoorcoil. Any service work requiring removal or adjustment inthe fan and/or motor area will require that thedimensions below be checked and blade adjus...
Page 19 - Reinsert tube into fitting.; FIGURE 9
Manual 2100-467 Page 19 of 23 SUCTION AND DISCHARGE TUBEBRAZING Compliant Scroll compressors have copper plated steelsuction and discharge tubes. These tubes are far morerugged and less prone to leaks than copper tubes used onother compressors. Due to different thermal propertiesof steel and copper,...
Page 20 - TROUBLESHOOTING GE ECM
Manual 2100-467 Page 20 of 23 TROUBLESHOOTING GE ECM ™ MOTORS CAUTION: Disconnect power from unit before removing or replacingconnectors, or servicing motor. To avoid electric shock fromthe motor’s capacitors, disconnect power and wait at least 5minutes before opening motor. Symptom Cause/Procedure ...
Page 21 - Replacing ECM Control Module
Manual 2100-467 Page 21 of 23 Motor Motor OK when R > 100k ohm ECM 2.0 Only remove Hex Head Bolts Connector Orientation Between 4 and 8 o'clock Drip Loop Back of Control Figure 5 Winding Test Figure 4 Note: Use the shorter bolts and alignment pin supplied when replacing an ECM 2.0 control. Figure...