1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
9 Page 9
10 Page 10
11 Page 11
12 Page 12
Page: / 12

Table of Contents:

  • Page 2 – Capacity and Efficiency Ratings
  • Page 3 – Ventilation System Packages
  • Page 4 – Electrical Specifications
  • Page 5 – Commercial Room Ventilator Performance Data - CRV-2; WL18, WL24 & WL25 TOTAL AND VENTILATION AIRFLOW
  • Page 6 – WL30 & WL37 HIGH SPEED TOTAL AND VENTILATION AIRFLOW; Commercial Room Ventilator Performance Data - CRVS-3 and CRVP-3
  • Page 7 – WL42 & WL48 LOW SPEED TOTAL AND VENTILATION AIRFLOW; Commercial Room Ventilator Performance Data - CRVS-5 and CRVP-5
  • Page 8 – WL60 & WL70 HIGH SPEED TOTAL AND VENTILATION AIRFLOW; WL60 & WL70 LOW SPEED TOTAL AND VENTILATION AIRFLOW
  • Page 9 – Unit Service Access Overview; Model WL with Left Side; Indoor Blower Performance - CFM at 230 or 460 Volts
  • Page 10 – Cooling Application Data - Outdoor Temperature
  • Page 11 – For side by side installation of two (2) WL models there; FRONT VIEW
  • Page 12 – WL; Air Conditioning Wall-Mount Model Nomenclature
Loading the manual

Form No.

S3279-206

Supersedes

S3279-106

Page

1 of 12

Aluminum Finned Copper Coils:

Grooved tubing and enhanced
louvered fin for maximum heat transfer
and energy efficiency.

Twin Blowers:

Move air quietly. Most models feature
multispeed blower motors providing
airflow adjustment for high and low
static operation. Motor overload
protection is standard on all models.

Air Conditioner Compressor:

Reciprocating compressors with
crankcase heater and dual discharge
muffler are standard on 1.5 and 2 ton
models.

Scroll Compressors eliminate need for
crankcase heater. Standard on 2.5 to
5 ton, and available on 2 ton models.

Phase Rotation Monitor:

Standard on all 3 phase scroll
compressors. Protects against reverse
rotation if power supply is not properly
connected. Not required on
reciprocating compressors.

Galvanized 20 Gauge Zinc Coated
Steel Cabinet:

Cleaned, rinsed, sealed and dried
before the polyurethane primer is
applied. The cabinet is handsomely
finished with a baked on textured
enamel, which allows it to withstand
1000 hours of salt spray tests per
ASTM B117-03.

Electrical Components:

Are easily accessible for routine
inspection and maintenance through a
left side, service panel opening.
Features a lockable, hinged access
cover to the circuit breaker or pull
disconnect switch.

Electric Heat Strips:

Features an automatic limit and
thermal cut-off safety control. Heater
packages can be factory installed for
all 1.5 through 6 ton models.

One Inch, Disposable Air Filters:

Are standard equipment. Optional one
inch washable filters available and filter
racks permit the addition of 2" pleated
filter. Factory or field installed.

Built-in Circuit Breakers:

Standard on all single (230/208 volt) and
three phase (230/208 volt) equipment.
Toggle disconnects are standard on all
three phase (460 volt) equipment.

Slope Top:

Standard feature for water run-off.

Top Rain Flashing:

Standard feature on all models.

Full Length Mounting Brackets:

Built into cabinet for improved
appearance and easy installation.

NOTE:

Bottom mounting bracket

included to assist in installation.

Auto-Reset High Pressure Switch:

Built-in lock-out circuit resets from the
room thermostat. Provides commercial
quality protection to the compressor.

Auto-Reset Low Pressure Switch:

Built-in lock-out circuit and low pressure
timed bypass circuit. Resets from room
thermostat.

Compressor Control Module:

Built-in off-delay timer adjustable from 30
second to 5-minutes. 2-minute on-delay
if power interrupt. 120-second bypass for
low pressure control, and both soft and
manual lockouts for high and low
pressure controls. Alarm output for alarm
relay.

Low Ambient Control:

Permits cooling operation down to 0°F
outdoor ambient.

Alarm Relay:

Dry contacts for remote alarm capability
on manual high or low pressure controls.

The Bard Wall-Mount Air Conditioner with Left Side Control Panel is
designed to provide complete service access (i.e. compressor, electric heat
strip and electrical controls) when two units are mounted side by side with
minimal space between. The left side unit is the ideal product for
telecommunication and over-the-road medical and communication vans
requiring two wall-mount air conditioners be mounted side by side by using
a WL (left side access) unit and a WA (right side access) unit on the same
building. Factory or field installed accessories are also available to meet
specific job requirements.

All packages are designed
to meet your specific
ventilation requirements
utilizing one of five
ventilation options for the
product. The ventilation
package is mounted within
the unit eliminating the need
for an exterior mounted
hood or damper assembly
on the unit. All assemblies
can be factory installed,
installed in the field at time
of installation or as a retrofit
system after installation.

THE WALL-MOUNT™ AIR CONDITIONERS - WL (60HZ)

with LEFT SIDE CONTROL PANEL

Standard - Barometric

Fresh Air Damper

Optional - Motorized

Fresh Air Damper

Optional - Blank off Plate

Optional - Commercial

Room Ventilator with Exhaust
• CRV - Spring Return
• CRVP - Power Return

Optional - Economizer w/Exhaust

Ventilation System Packages

MEA# 357-93-E

WL - SERIES Refrigerant 22 60Hz
1.5 to 6 Ton (18,300 to 67,000 Btuh)
Left Side Control Panel

Engineered Features

Complies with efficiency requirements of ASHRAE/IESNA 90.1-2004.

Certified to ARI Standard 390-2003 for SPVU (Single Package Vertical Units).

Commercial Product - Not intended for Residential application.

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Capacity and Efficiency Ratings

Form No. S3279-206 Supersedes S3279-106 Page 2 of 12 S L E D O M 2 8 1 L W 2 4 2 L W 3 5 2 L W 2 0 3 L W 2 7 3 L W 3 2 4 L W 4 8 4 L W 2 0 6 L W A - 2 0 7 L W C , B - 1 0 7 L W H U T B y t i c a p a C g n il o o C 1 0 0 3 , 8 1 0 0 0 , 4 2 0 0 0 , 3 2 0 0 0 , 0 3 0 0 0 , 6 3 0 0 0 , 2 4 0 0 5 , 7 4 ...

Page 3 - Ventilation System Packages

Form No. S3279-206 Supersedes S3279-106 Page 3 of 12 Bard Wall-Mounts are designed to provide optional ventilation packages to meet all of your ventilation and indoor air quality requirements.All units are equipped with a barometric fresh air damper as the standard ventilation package. All ventilati...

Page 4 - Electrical Specifications

Form No. S3279-206 Supersedes S3279-106 Page 4 of 12 1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. 2 Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes. 3 These “Minimum Circuit Ampacit...

Other Bard Models

All Bard Other