MODEL 8028 DAMPER POWER DISTRIBUTION PANEL
INSTALLATION INSTRUCTIONS & APPLICATION SHEET
1. Installation must be done in accordance with the NEC and all
other applicable local codes.
2. To prevent excessive transformer heating, do not power more
than the recommended number of dampers to a transformer.
CAUTION
Voltage
24 VAC ±20%
Max. Damper Power Input per Zone
100VA max @ 24 VAC
Damper Fuse Size
5A Fast Acting (spare supplied)
Control Input Current Draw (Zone A and Zone B)
50 mA @ 24 VAC
Max. No. of Aprilaire Dampers per Zone
10 (refer to Diagram 3 on the back if there are
more than 10 dampers in a zone)
Max Wire Size
18 AWG
Application Temperature/RH
158°F / 90% RH (non-condensing)
SPECIFICATIONS
SWITCH SETTINGS AND LED’S
Set to
SINGLE SUPPLY
when used:
• in a
two zone system
when there are
no more than 10 dampers in either ZONE A or ZONE B.
Size the transformer for the zone with the most dampers.
• when there are
no more than 10 total dampers wired to ZONE A plus ZONE B.
Size the transformer
for the total number of dampers connected to both zones.
When set to SINGLE SUPPLY, wire transformer to “POWER A” terminals. Refer to
Diagram 2
on the
back for wiring.
Set to
SEPARATE SUPPLIES
for all other applications. Wire transformers to “POWER A” and “POWER B”
terminals. Refer to
Diagram 1
on the back.
ZONE A
ZONE B
SINGLE
SINGLE
SUPPLY
SEPARATE
SUPPLIES
ZONE A – 5 AMP
ZONE B – 5 AMP
SPARE FUSE – 5 AMP
5
4
3
2
1
ZONE B
DAMPERS
ZONE A
DAMPERS
1
2
3
4
5
POWER
A
POWER
B
ZA
ZB
C
NO
C
NO
Damper Power Input(s)
from Transformers
Dampers Wired to ZONE A and ZONE B Terminals
Control Input(s) from
Zoned Comfort Control
Panel
Power Supply Switch
Zone LED’s
ZA
LED lights when 24-volts is applied to the ZONE A control input.
ZB
LED lights when 24-volts is applied to the ZONE B control input.