1. 120 volts may cause serious injury from electrical shock. Leave

power to all system components disconnected until installation
is complete

WARNING

MODEL 8028 DAMPER POWER DISTRIBUTION PANEL

INSTALLATION INSTRUCTIONS & APPLICATION SHEET

1. Installation must be done in accordance with the NEC and all

other applicable local codes.

2. To prevent excessive transformer heating, do not power more

than the recommended number of dampers to a transformer.

CAUTION

Voltage

24 VAC ±20%

Max. Damper Power Input per Zone

100VA max @ 24 VAC

Damper Fuse Size

5A Fast Acting (spare supplied)

Control Input Current Draw (Zone A and Zone B)

50 mA @ 24 VAC

Max. No. of Aprilaire Dampers per Zone

10 (refer to Diagram 3 on the back if there are
more than 10 dampers in a zone)

Max Wire Size

18 AWG

Application Temperature/RH

158°F / 90% RH (non-condensing)

SPECIFICATIONS

SWITCH SETTINGS AND LED’S

Set to

SINGLE SUPPLY

when used:

• in a

two zone system

when there are

no more than 10 dampers in either ZONE A or ZONE B.

Size the transformer for the zone with the most dampers.

• when there are

no more than 10 total dampers wired to ZONE A plus ZONE B.

Size the transformer

for the total number of dampers connected to both zones.

When set to SINGLE SUPPLY, wire transformer to “POWER A” terminals. Refer to

Diagram 2

on the

back for wiring.

Set to

SEPARATE SUPPLIES

for all other applications. Wire transformers to “POWER A” and “POWER B”

terminals. Refer to

Diagram 1

on the back.

ZONE A

ZONE B

SINGLE

SINGLE

SUPPLY

SEPARATE

SUPPLIES

ZONE A – 5 AMP

ZONE B – 5 AMP

SPARE FUSE – 5 AMP

5

4

3

2

1

ZONE B

DAMPERS

ZONE A

DAMPERS

1

2

3

4

5

POWER

A

POWER

B

ZA

ZB

C

NO

C

NO

Damper Power Input(s)
from Transformers

Dampers Wired to ZONE A and ZONE B Terminals

Control Input(s) from
Zoned Comfort Control
Panel

Power Supply Switch

Zone LED’s

ZA

LED lights when 24-volts is applied to the ZONE A control input.

ZB

LED lights when 24-volts is applied to the ZONE B control input.