APC MXA002 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Table of Contents:
Page 2 – Important safety instructions!; Please read this manual!; PLEASE SAVE THIS MANUAL !; CONSERVER CES INSTRUCTIONS !
Page 8 – Input cable connections; The edge of the knock-out may be sharp!
Page 10 – Unmating of UPS output power connector; Output wiring procedure; Isolation Unit. Power to the UPS must be disconnected at the source!
Page 11 – Diagram showing power distribution plate earth connection
Page 13 – (Alternate of connection scheme
Page 16 – Customer Service; PHONE; American Power Conversion
Loading the manual
The world's most reliable power protection
®
Matrix
TM
UPS
Hard-wire kit accessory
MXA001
MXA002
User's
Manual
American Power Conversion
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
Page 2 - Important safety instructions!; Please read this manual!; PLEASE SAVE THIS MANUAL !; CONSERVER CES INSTRUCTIONS !
Important safety instructions! Please read this manual! Veuillez lire ce manuel! Bitte lesen Sie dieses Anleitungshandbuch! ¡Se ruega leer este manual de instrucciones! PLEASE SAVE THIS MANUAL ! It includes important instructions for the safe use and installation of the UPS and its accessories. CONS...
Page 3 2.0 Presentation Power distribution plate Provides an interface for output hard-wiring of loads. It is used in place of the power distribution plate for cord connected equipment originally furnished with the UPS. Input cable plate Used to replace the input cable plate originally furnished wit...
Page 6 - Input voltage requirements
Page 4 3.0 Installation ■ Warning: Risk of electric shock exists inside the UPS. Input voltage tap selection and power distribution panel replacement should be performed only by qualified service personnel. ■ Avertissement: Un risque de choc électrique existe à lintérieur de lUPS. La sélection des...
Page 7 - Input wiring procedure
Page 5 3.0 Installation Table 3.2.1 Cable Size Strip Length UPS Model Minimum Maximum Input cable Output cable 3000VA 2.5 mm 2 12 AW G 10.0 m m2 8 AW G 12 mm 1/2" 9 mm 3/8" 5000VA 6.0 mm 2 10 AW G 10.0 m m2 8 AW G ■ Cable clamps The UPS is not furnished with cable clamps for strain relief. U...
Page 8 - Input cable connections; The edge of the knock-out may be sharp!
Page 6 3.0 Installation Input cable connections 3.3 Input wiring procedure - continued To remove a knock-out, strike in the area shown with a nail set tool and hammer. Grasp the edge of the knock-out with pliers and twist until the knock-out is separated from the plate. Caution: The edge of the knoc...
Page 10 - Unmating of UPS output power connector; Output wiring procedure; Isolation Unit. Power to the UPS must be disconnected at the source!
Page 8 Unmating of UPS output power connector 3.0 Installation 3.4 Output wiring procedure 3.4.1 Be sure the input circuit breaker is switched off (0) and the input cable is unplugged and/ or has no power applied. Caution: Switching the circuit breaker to off (0) does not remove power to all of the ...
Page 11 - Diagram showing power distribution plate earth connection
Page 9 Diagram showing power distribution plate earth connection 3.0 Installation 3.4 Output wiring procedure - continued 3.4.4 Use a 3/8" wrench to remove the protective earth wire (green with yellow stripes) ring terminal fastened at the earthing stud on the Isolation Unit. 3.4.5 Remove the de...
Page 13 - (Alternate of connection scheme
Page 11 3.0 Installation 3.4 Output wiring procedure - continued Figure 3.4.1 1 f , 208 Vac loads only 3000 VA model with MXA002 hard- wire kit: 15 Amp maximum. 5000 VA model with MXA001 hard- wire kit: 24 Amp maximum. Figure 3.4.2 1 f , 240 Vac loads only 3000 VA model with MXA002 hard- wire kit: 1...
Page 16 - Customer Service; PHONE; American Power Conversion
Customer Service Note: Before calling the customer service number, please have available your UPS's serial number (see the label at the rear of the UPS). ( PHONE (+33) 1.64.62.59.00 in Europe (401) 789-5735 world wide * MAILING American Power Conversion 4, rue Ste Claire Deville Zac du Mandinet-Bâti...